HomeMy WebLinkAboutDDW-2025-006347Sanitary Survey - Deficiency Report
PWS Number:UTAH26019 Deficiency Points:135 Survey Date:07/09/2025
Survey Name:LODGEPOLE CAMPGROUND Surveyor:Melissa Noble
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS004 | CAMP WELL
71. Well discharge line has a smooth-nosed sampling tap, which samples the well water before any chemical injection. (first item from the
wellhead).
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with a smooth nosed sampling tap, a
check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. (smooth
nosed sampling tap being the first item from the well head and the shut-off valve as the
last item)
Notes:no smooth nosed sampling tap
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S023 NO SMOOTH NOSED SAMPLING TAP ON DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS004 | CAMP WELL
74. Well discharge line has a means to measure flow.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:No means to measure flow
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S026 NO FLOW METER ON WELL DISCHARGE PIPING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | LODGEPOLE CG TANK
87. Roof or wall penetrations sealed
Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control
apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have
additional proper shielding to prevent vandalism. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:electrical tube/pipe beside access opening unable to take off the lid to verify it is sealed.
Deficiency Points: 100
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS
ON TANK ROOF OR SIDEWALLS
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | LODGEPOLE CG TANK
91B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:screen missing
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN