Loading...
HomeMy WebLinkAboutDDW-2025-006342Sanitary Survey - Deficiency Report PWS Number:UTAH26013 Deficiency Points:40 Survey Date:07/09/2025 Survey Name:CURRANT CREEK CAMPGROUND Surveyor:Melissa Noble Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS001 | CURRENT CREEK SPRING 65. No deep-rooted vegetation is within the 50 ft collection area. Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a means not negatively affecting water quality. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:trees and bushes in collection area Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | CURRENT CREEK SPRING 67. Is a spring collection box present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box to permit spring inspection and testing. Notes:There is no spring box present. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | CURRENT CREEK SPRING 68. Is a spring box vent present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect to venting. Therefore, a junction or collection box requires a vent to be fitted with #14 mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the entrance of contaminants, be located and sized to avoid blockage during winter, and have the end of the vent discharge a minimum of 24 inches above the earth on buried structures. Notes:There is no spring box present Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | CURRENT CREEK SPRING 69. Spring has a permanent flow-measuring device. Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device. Notes:no permanent flow-measuring device. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW