HomeMy WebLinkAboutDDW-2025-006238Sanitary Survey - Deficiency Report
PWS Number:UTAH28004 Deficiency Points:5 Survey Date:06/18/2025
Survey Name:LOA TOWN WATER SYSTEM Surveyor:Brent Arns
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS003 | WELL #2
69. Well discharge line has a check valve.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:No Check valve on discharge line
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING