Loading...
HomeMy WebLinkAboutDDW-2025-006233Sanitary Survey - Deficiency Report PWS Number:UTAH28005 Deficiency Points:65 Survey Date:06/18/2025 Survey Name:LYMAN WATER SYSTEM Surveyor:Brent Arns Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH28005 DISTRIBUTION SYSTEM 28A. System lacks up to 20% of required source capacity Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak day demand and the average yearly demand. Notes:System lacks 20% source capacity Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY Sanitary Survey Category: OC SDWIS Severity Code: Significant Deficiency Cross Connection and Operator Certification | DS001 | UTAH28005 DISTRIBUTION SYSTEM 40. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT ) Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that utilize treatment/filtration to have at least one operator certified at the classified grade of the water system. Certification must be appropriate for the type of system operated (treatment and/or distribution). This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Need Backflow 101 Certification Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE REQUIRED LEVEL