HomeMy WebLinkAboutDDW-2025-006233Sanitary Survey - Deficiency Report
PWS Number:UTAH28005 Deficiency Points:65 Survey Date:06/18/2025
Survey Name:LYMAN WATER SYSTEM Surveyor:Brent Arns
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH28005 DISTRIBUTION SYSTEM
28A. System lacks up to 20% of required source capacity
Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak
day demand and the average yearly demand.
Notes:System lacks 20% source capacity
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY
Sanitary Survey Category: OC
SDWIS Severity Code: Significant Deficiency
Cross Connection and Operator Certification | DS001 | UTAH28005 DISTRIBUTION SYSTEM
40. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT )
Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that
utilize treatment/filtration to have at least one operator certified at the classified grade
of the water system. Certification must be appropriate for the type of system operated
(treatment and/or distribution). This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:Need Backflow 101 Certification
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE
REQUIRED LEVEL