HomeMy WebLinkAboutDDW-2025-006229Sanitary Survey - Deficiency Report
PWS Number:UTAH13055 Deficiency Points:75 Survey Date:06/12/2025
Survey Name:ZION MOUNTAIN RESORT Surveyor:Rich Peterson
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | BIG SPRING
60. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:to be re-developed in the fall
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | BIG SPRING
67. No roots seen in collection boxes and junctions.
Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep-
rooted vegetation to prevent root growth from clogging collection lines. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:to be re-developed in the fall
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | BIG SPRING
69. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:to be re-developed in the fall
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | BIG SPRING
70. Spring has a permanent flow-measuring device.
Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device.
Notes:to be re-developed in the fall
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | BUFFALO RIDGE 355,000 GAL TANK
105B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:hole in screen, but repaired with photo
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN