HomeMy WebLinkAboutDDW-2025-005990BT Engineering
Department of Environmental Quality June 19, 2025
Division of Drinking Water
195 North 1950 West P.O. Box 144830 Salt Lake City, UT 84114-4830
RE: Operating Permit Request for Mayflower/Lincoln Booster Station #2 (PF019)
Jordanelle SSD Water System #26086, File #18719 To Whom It May Concern:
This letter’s purpose is to inform the Division of Drinking Water that JSSD’s Mayflower/Lincoln Booster Station #2 has been constructed, pressure tested, and disinfected. JSSD has requested that we provide adequate information to your office so that an Operating Permit may be obtained. As the newly appointed District Engineer, I have visited the site and taken the attached pictures.
The following details each item of the Operating Permit Checklist (attached):
• Certification of Rule Conformance: Provided on the attached letter by the PE of Record Nick Graue, PE.
• Utah Registered Engineer’s Statement: Provided on the attached letter by the PE of Record Nick Graue, PE.
• JSSD has received the As-Built Drawings for the pump station.
• Clayton Riding, JSSD Inspector, was present during the disinfection and pressure testing of the pump station and associated water lines. He witnessed that the water
line was properly flushed and disinfected per AWWA C651 & 654.
• Water quality sampling data is attached for the pump station.
JSSD looks forward to receiving the Operating Permit from your office. If you have any questions or concerns related to this request or these statements please contact Tavis Timothy, PE at (801) 319-1288. Please call if I can answer any questions or be of further assistance.
Respectfully,
Tavis Timothy, PE
BT Engineering
Air Vent Extended Pump Station Piping
Pump Station Meter, Pump & Piping Exterior Pump Station Completed
Utah Division of Drinking Water June 16, 2025
195 North 1950 West
Salt Lake City, UT 84116
RE: Certification of Rule Conformance
Mayflower Pump Station #2
Jordanelle Special Service District, System #26086
DDW File #18719
To Whom It May Concern:
As the Utah-licensed professional engineer of record for the above-referenced public drinking
water construction project, I hereby certify that, to the best of my knowledge and belief:
1. The project was completed in accordance with the approved engineering plans and
specifications, and
2. All applicable requirements of Utah Administrative Code R309-500 through R309-550
have been satisfied, including but not limited to design, construction, and material
standards, and
3. Any changes made during construction were reviewed and determined to be in
compliance with the applicable rules and do not compromise public health protection or
system performance.
This certification is based on my involvement in the design and construction observation of the
project, including review of construction records and coordination with the owner and contractor.
Please feel free to contact me at 801-299-1327 or nick.graue@aquaeng.com if additional
information is needed.
Sincerely,
Nick Graue, PE
Utah Professional Engineer No. 106383374-2202
Principal Engineer, AQUA Engineering
801-299-1327
A: Absence: R: Routine P: Presence: I: Investigative Page 1 of 1
+ JORDANELLE SPECIAL SERVICE DISTRICT JORDANELLE LABORATORY
Po. Box 519 Phone: 435-333-0475 Heber City Ut. 84032 Form: 28 Fax: 435-333-0513 Microbiological Analysis of Water Samples Standard Methods 20th, 9223B, Presence/ Absence (P/A), Colilert MONTH: June 2025 CUSTOMER: JSSD SYSTEM #:
DATE COLLECTED ID CODE UNIQUE LAB ID # SAMPLING POINT TIME R,I CL2 SAMPLER INITIALS RESULT
Total Coliforms E.coli
06/10/2025 B7139 R006120 Lincoln Pump Sta. 0715 I .32 C.R. A A
06/10/2025 B7137 R006121 Lincoln Pump Sta. 0725 I .69 C.R. A A
06/10/2025 B7005 R006122 Lincoln Tank 3 Discharge Line 0740 I .46 C.R. A A
06/10/2025 B7141 R006123 Lincoln Tank 3 Discharge Line 0750 I .45 C.R. A A
06/10/2025 B7004 R006124 Marcella Place HYD 0800 I 0 C.R. A A
06/10/2025 B7136 R006125 Marcella Plance HYD 0811 I 0 C.R. P A
Analyzed by: M.S. Approved by: Date: 06/12/2025
Wade C. Webster
A: Absence: R: Routine P: Presence: I: Investigative Page 1 of 1
+ JORDANELLE SPECIAL SERVICE DISTRICT JORDANELLE LABORATORY
Po. Box 519 Phone: 435-333-0475 Heber City Ut. 84032 Form: 28 Fax: 435-333-0513 Microbiological Analysis of Water Samples Standard Methods 20th, 9223B, Presence/ Absence (P/A), Colilert MONTH: June 2025 CUSTOMER: JSSD SYSTEM #:
DATE COLLECTED ID CODE UNIQUE LAB ID # SAMPLING POINT TIME R,I CL2 SAMPLER INITIALS RESULT
Total Coliforms E.coli
06/24/2025 B7045 R006167 Marcella Place 1625 I 0 C.R. P A
06/24/2025 B7041 R006168 Far North HYD 1642 I .08 C.R. A A
06/24/2025 B7051 R006169 Lincoln Pump 1635 I .14 C.R. A A
06/24/2025 B7049 R006170 Station 1645 I .74 C.R. A A
Analyzed by: K.M. Approved by: Date: 06/26/2025
Wade C. Webster