HomeMy WebLinkAboutDDW-2025-005908Sanitary Survey - Deficiency Report
PWS Number:UTAH26008 Deficiency Points:245 Survey Date:06/19/2025
Survey Name:MIDWAY CITY WATER
SYSTEM
Surveyor:Danielle Zebelean
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH26008 DISTRIBUTION SYSTEM
32. Does your Emergency Response Plan address cybersecurity? (only required for systems over 3,300 population, otherwise mark NA)
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Emergency Response plan sent by Cory does not address cybersecurity. Sent back to add
that the DDW hotline is
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: MR
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH26008 DISTRIBUTION SYSTEM
35. For a community water system or a non-transient non-community water system, did you make your initial service line inventory available to
the public? (if a transient system, enter NA)
Rule: 40 CFR 141.84 (a)(8)The rule requires that the service line materials inventory be publicly accessible.
(a)(8)(ii) The rule requires that water systems serving greater than 50,000 persons
make the publicly accessible inventory available online. (a)(9) The rule requires that
when a water system has no lead, galvanized requiring replacement, or lead status
unknown service lines (regardless of ownership) in its inventory, it may comply with
the requirements using a written statement, in lieu of the inventory, declaring that the
distribution system has no lead service lines or galvanized requiring replacement
service lines. The statement must include a general description of all applicable sources
used to make this determination.
Notes:Midway's service line inventory is available on the DDW online map. However, they did not
provide a letter on how they informed their customers where they could find the information
on their service line.
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: R006 FAILURE TO MAKE THE LEAD SERVICE LINE INVENTORY PUBLICLY
ACCESSIBLE
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH26008 DISTRIBUTION SYSTEM
37. Documentation of annual public awareness and/or employee training
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes providing public education or awareness material or presentations.
Notes:No documentation of public awareness or employee training submitted.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M004 CCC-NO ANNUAL PUBLIC EDUCATION OR AWARENESS
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH26008 DISTRIBUTION SYSTEM
39. Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps
installed within the system)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes written records of cross connection control activities.
Notes:System does not have an inventory, Shane claims that they do not have any backflow
assemblies in the system. Connected Shane with Chris Bowles to work on it.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS005 | ALPENHOF WELL
118B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:Pump to waste is missing a screen inside the building. Sanitary Survey review meeting on
6/26/25 with field service staff required a screen to be located inside the building on pump to
waste.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS007 | ALPENHOF-WEBER WELL
140B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:Pump to waste is missing a screen inside the building. Sanitary Survey review meeting on
6/26/25 with field service staff required a screen to be located inside the building on pump to
waste.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | COTTAGES-ON-GREEN TANK
167A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin?
Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at
an elevation between 12 and 24 inches above the ground surface or the rim of the
receiving basin.
Notes:Overflow and drain discharge into a storm drain below the tank. Directed Shane to apply for
an exception.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND SURFACE
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST005 | GERBER SPRING TANK
203C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gasket was missing in a couple of places.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST005 | GERBER SPRING TANK
210A. Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin
Rule: R309-545-10(1)(d)If the local authority allows discharge to a storm drain, the rule requires the drain
discharge to have a physical clearance of at least 12 inches between the discharge end of
the pipe and the overflow rim of the receiving basin. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Drain line discharges into a vault lacking the required 12-inch clearance. Directed Shane to
apply for an exception.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP001 | GERBER SPRING CHLORINATOR
272. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen.
Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least
susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible
screen. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Chlorine Vent lacked a screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS
NO. 14 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP003 | MAHAGONY SPRING CHLORINATOR
286. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen.
Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least
susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible
screen. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Chlorine vent lacked a screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS
NO. 14 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP005 | WS005/WS007 CL2 GAS
300. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen.
Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least
susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible
screen. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Vent line was broken off outside of building, also lacked a screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS
NO. 14 SCREEN