HomeMy WebLinkAboutDERR-2024-005841Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name 7-ELEVEN INC
Address PO BOX 711
DALLAS, TX 75221
Contact 7-ELEVEN INC
Phone
Email Marc.Westfall@7-11.com
TANK LOCATION
Name 7-ELEVEN 33985
Address 692 E 12300 S
DRAPER, UT 84020
A Operator MARC WESTFALL
Phone (214) 415-0146
B Operator SAME
Phone SAME
Facility ID: 4002160 Inspection Date: 04/02/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
6 - 1/2 Gas/Diesel Yes Steel Flex in Sump Oct.
10,
2022
Oct.
10,
2022
Yes No Oct.
18,
2022
None
7 - 3/4 Gas/Diesel Yes Steel Flex in Sump Oct.
10,
2022
Oct.
10,
2022
Yes No Oct.
18,
2022
None
8 - 5/6 Gas/Diesel Yes Steel Flex in Sump Oct.
10,
2022
Oct.
10,
2022
Yes No Oct.
18,
2022
None
9 - 7/8 Gas/Diesel Yes Steel Flex in Sump Oct.
10,
2022
Oct.
10,
2022
Yes No Oct.
18,
2022
None
10 -
9/10
Gas/Diesel Yes Steel Flex in Sump Oct.
10,
2022
Oct.
10,
2022
Yes No Oct.
18,
2022
None
TANK DETAILS
Tank ID/Alt ID 1 / 1
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc April 16, 1998 / 12000 / West
Substance
Stored Gasoline / Premium
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG Veeder Root / Simplicity CSLD
No Manifold
LTT Test None
LLD Test April 17, 2023
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Vaporless LD2000
Spill/Overfill/Sm
Delivery
5 gal. Double Walled Spill Bucket /
Automatic shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankATG
PipeAutoLineLeakDetection /
PipeInterstitialDblWalled
CP Tank Test None
CP Pipe Test None
2024-04-02 Page 1 of 7
Tank ID/Alt ID 2 / 2
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc April 16, 1998 / 12000 / Center
Substance
Stored Diesel / Diesel #2 (U.L.S.)
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG Veeder Root / Simplicity CSLD
No Manifold
LTT Test None
LLD Test April 17, 2023
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Vaporless LD2000
Spill/Overfill/Sm
Delivery
5 gal. Double Walled Spill Bucket /
Automatic shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankATG
PipeAutoLineLeakDetection /
PipeInterstitialDblWalled
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 3 / 3
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc April 16, 1998 / 12000 / East
Substance
Stored Gasoline / Regular
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG Veeder Root / Simplicity CSLD
No Manifold
LTT Test None
LLD Test April 17, 2023
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Vaporless LD2000
Spill/Overfill/Sm
Delivery
5 gal. Double Walled Spill Bucket /
Automatic shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankATG
PipeAutoLineLeakDetection /
PipeInterstitialDblWalled
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-04-02 Page 2 of 7
FACILITY RESPONSES
Financial Responsibility
Financial responsibility method is ok?Yes
The above accurately represents the
facility's release detection records Yes
Operator Training
A Operator current?Yes
B Operator current?Yes
Monthly checklist available and
complete?Yes
Is the site unmanned?No
C Operators trained?Yes
TANK RESPONSES
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 1 ATG/IM
IM - Type of Documentation Used?ATG
IM - System capable of detecting a
release of regulated substances from
any portion of the primary tank/piping
within one month of release?
Yes
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 1 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Tank 1 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 2 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
2024-04-02 Page 3 of 7
Tank 1 ATG/IM
Does the ATG system have a valid
annual test?Yes
Does the Containment Sump have a
valid 3-year test?Yes
Tank 2 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 2 ATG/IM
IM - Type of Documentation Used?ATG
IM - System capable of detecting a
release of regulated substances from
any portion of the primary tank/piping
within one month of release?
Yes
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 2 ATG/IM
Does the ATG system have a valid
annual test?Yes
Does the Containment Sump have a
valid 3-year test?Yes
Tank 2 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 2 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 3 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Tank 3 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 3 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
2024-04-02 Page 4 of 7
Tank 3 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 3 ATG/IM
IM - Type of Documentation Used?ATG
IM - System capable of detecting a
release of regulated substances from
any portion of the primary tank/piping
within one month of release?
Yes
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 3 ATG/IM
Does the ATG system have a valid
annual test?Yes
Does the Containment Sump have a
valid 3-year test?Yes
DISPENSER RESPONSES
2024-04-02 Page 5 of 7
Dispenser 3/4
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 7/8
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 1/2
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 5/6
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 9/10
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
MONTHLY LEAK DETECTION MONITORING
Apr '23 May '23 Jun '23 Jul '23 Aug '23 Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24
Tank 1 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Tank 2 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Tank 3 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
NON-COMPLIANCE ITEMS
All items are in compliance.
2024-04-02 Page 6 of 7
Prepared by fueloperator.com
Inspection Information
Inspector:Wilson, David
Record Created:April 2, 2024, 10:41 a.m.
Inspection Date:April 2, 2024
2024-04-02 Page 7 of 7
Facility Compliance Report
Period: March 1 - March 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
3/1/2023 7,216.67 62.76 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
3/1/2023 2,971.78 26.06 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
3/1/2023 4,635.77 39.31 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 3/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 3/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 3/1/2023 Sensor Normal
Automatically approved by System on 4/2/2023 4:05:47 AM -04:00
Report Generated on 4/2/2023 4:05:47 AM -04:00
33985 - MARCH 1 - MARCH 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: April 1 - April 30, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
4/1/2023 6,934.72 60.31 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
4/2/2023 6,453.90 56.59 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
4/2/2023 5,867.59 49.75 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 4/2/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 4/2/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 4/2/2023 Sensor Normal
Automatically approved by System on 5/2/2023 4:06:27 AM -04:00
Report Generated on 5/2/2023 4:06:27 AM -04:00
33985 - APRIL 1 - APRIL 30, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: May 1 - May 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
5/1/2023 6,624.71 57.61 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
5/1/2023 8,999.62 78.91 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
5/1/2023 6,863.13 58.20 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 5/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 5/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 5/1/2023 Sensor Normal
Automatically approved by System on 6/2/2023 4:06:16 AM -04:00
Report Generated on 6/2/2023 4:06:16 AM -04:00
33985 - MAY 1 - MAY 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: June 1 - June 30, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
6/1/2023 7,402.24 64.37 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
6/1/2023 8,999.06 78.90 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
6/1/2023 7,212.18 61.16 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 6/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 6/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 6/1/2023 Sensor Normal
Automatically approved by System on 7/2/2023 4:06:27 AM -04:00
Report Generated on 7/2/2023 4:06:27 AM -04:00
33985 - JUNE 1 - JUNE 30, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: July 1 - July 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
7/1/2023 6,753.85 58.73 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
7/2/2023 8,807.31 77.22 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
7/2/2023 6,434.86 54.57 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 7/2/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 7/2/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 7/2/2023 Sensor Normal
Automatically approved by System on 8/4/2023 4:07:17 AM -04:00
Report Generated on 8/4/2023 4:07:17 AM -04:00
33985 - JULY 1 - JULY 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: August 1 - August 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
8/1/2023 7,053.75 61.34 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
8/1/2023 5,722.21 50.17 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
8/1/2023 7,340.32 62.24 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 8/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 8/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 8/1/2023 Sensor Normal
Automatically approved by System on 9/2/2023 4:07:06 AM -04:00
Report Generated on 9/2/2023 4:07:06 AM -04:00
33985 - AUGUST 1 - AUGUST 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: September 1 - September 30, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
9/1/2023 8,119.63 70.61 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
9/1/2023 6,872.44 60.26 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
9/1/2023 9,209.69 78.09 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 9/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 9/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 9/1/2023 Sensor Normal
Automatically approved by System on 10/2/2023 4:07:03 AM -04:00
Report Generated on 10/2/2023 4:07:03 AM -04:00
33985 - SEPTEMBER 1 - SEPTEMBER 30, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: October 1 - October 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
10/1/2023 6,684.04 58.13 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
10/1/2023 8,788.67 77.06 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
10/1/2023 8,643.79 73.30 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 10/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 10/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 10/1/2023 Sensor Normal
Automatically approved by System on 11/2/2023 4:07:04 AM -04:00
Report Generated on 11/2/2023 4:07:04 AM -04:00
33985 - OCTOBER 1 - OCTOBER 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: November 1 - November 30, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
11/1/2023 8,238.71 71.65 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
11/1/2023 9,777.32 85.73 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
11/1/2023 6,657.51 56.45 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 11/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 11/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 11/1/2023 Sensor Normal
Automatically approved by System on 12/2/2023 4:05:28 AM -05:00
Report Generated on 12/2/2023 4:05:28 AM -05:00
33985 - NOVEMBER 1 - NOVEMBER 30, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: December 1, 2023 - December 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
12/1/2023 8,152.53 70.90 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
12/1/2023 7,983.22 70.00 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
12/1/2023 9,231.49 78.28 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 12/1/2023 Sensor Normal
Stp Sump 2 PUL STP SUMP 12/1/2023 Sensor Normal
Stp Sump 3 RUL STP SUMP 12/1/2023 Sensor Normal
Automatically approved by System on 1/2/2024 4:09:40 AM -05:00
Report Generated on 1/2/2024 4:09:40 AM -05:00
33985 - DECEMBER 1, 2023 - DECEMBER 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: January 1 - January 31, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
1/1/2024 7,700.92 66.97 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
1/1/2024 8,083.46 70.88 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
1/1/2024 7,015.35 59.49 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 1/1/2024 Sensor Normal
Stp Sump 2 PUL STP SUMP 1/1/2024 Sensor Normal
Stp Sump 3 RUL STP SUMP 1/1/2024 Sensor Normal
Automatically approved by System on 2/2/2024 4:05:30 AM -05:00
Report Generated on 2/2/2024 4:05:30 AM -05:00
33985 - JANUARY 1 - JANUARY 31, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: February 1 - February 29, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name:33985
State ID:4002160
Status:Managed (by Company)
Address:692 EAST 12300 SOUTH
DRAPER, UT 84020
County:Salt Lake County
Phone Number:(801)571-4982
Gas Brand:7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert #Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
2/1/2024 7,768.92 67.56 PASS
2 / 2 Diesel ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
2/1/2024 6,746.49 59.15 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
2/1/2024 6,123.70 51.93 PASS
Sensor Status
Sensor Category Sensor #Sensor Label Test Date Status
Stp Sump 1 DSL STP SUMP 2/1/2024 Sensor Normal
Stp Sump 2 PUL STP SUMP 2/1/2024 Sensor Normal
Stp Sump 3 RUL STP SUMP 2/1/2024 Sensor Normal
Automatically approved by System on 3/2/2024 4:05:29 AM -05:00
Report Generated on 3/2/2024 4:05:29 AM -05:00
33985 - FEBRUARY 1 - FEBRUARY 29, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000