PST operators are required to ensure that certain tests are conducted for their tank system .
Dates highlighted in "Yellow" -tests are due soon.
Dates highlighted in "Red" -tests are due and you are out of compliance .
Tank ID/Alt
ID
1/105-UGTA
2/216-UGTA
Description
Gasoline-Regular-6000
Gasoline-Premium-6000
3/217-UGTA Diesel-Diesel #2 (U.L.S.)-6000
L TT -Line Tightness Test
LLD -Line Leak Detector
Overfill -Overfill Device
LTT Spill Bucket -----------·-----------
LLD Overfill
NIA N/A . . . . . . . . . . . . . . . . . . . . . . . . . .
N/A N/A
N/A N/A
• • • • • • • • ■ •••• .............
N/A N/A
N/A N/A . . . . . . . . . . . . . .............
N/A N/A
Tank or Flex/Pipe CP -Corrosion Tests
ATG -Automatic Tank Gauging
Tank or Flex
----
Pipe CP
N/A
••••••••••• ■ •
N/A
N/A .............
N/A
N/A .............
N/A
Sump -Tank Top Sump and applicable Dispenser Sumps
ATG __ ,_. ___ , __
Sump
Please note that UDC tests are not listed, but are required on your facility's next sump test
cycle starting July 1, 2023, if applicable. Also, effective immediately pressure vent valves
must be tested every three years for gasoline tanks.
Please submit a copy of the required tests to the DERR within 30 days of the date due.
If you have any questions please call David Wilson at 801-536-4100.
195 Nor th 1950 We st -Sa l t Lake City. UT
Mailing Address: -P.O Box 144840 -Salt Lake City. LT 84114-4840
Telephone (801) 536-4100 -Fax 1801) 359-8853 -T.D.D. (801) 536-4414
1t·11w dL·q.1~ruh.g01·
\>1 intc<l on I oon.-;I rc1,,;yclcd paper
Patriot Petroleum Solution s
10312™STSE
AUTOMATIC TANK GAUGE (ATG) OPERATION INSPECTION Unit: 181
Loveland, Colorado 80537'
Facility Name: #516 Montezuma Creek UT owner: Red Mesa
Address: US Hwy 262 and Indian Hwy 35 Address: 501 Airport Drive suite 100
City, State, Zip Code: UT City, State, Zip Code: farmington NM
Facility I.D. #: 5493 Phone #: 505-564-6813
Testing Company: Patriot Petroleum Solutions Phone#: 435-651-3485 I Date: 04/10/25
This procedure is to determine whether the ATG is operating properly. See PEI/RP1200, Section 8.2 for the inspection procedure.
This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place.
Tank Number T1 T2 T3
Product Stored Regular Premium Diesel
ATG Brand and Model VR 450plus VR450plus VR450plus
1 . Tank Volume, gallons 6016 6016 6016
2. Tank Diameter, inches 96 96 96
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing parts Iii Yes □No Iii Yes □No Iii Yes □No □Yes □No
replaced?
4. Float moves freely on the stem without binding? Iii Yes □No lil Yes □No ~Yes □No □Yes □No
5 . Does the fuel float level agree with the value Iii Yes □No Iii Yes □No Iii Yes □No □Yes □No programmed into the console?
6. Does the water float level agree with the value Iii Yes □No Iii Yes □No Iii Yes □No □Yes □No programmed into the console?
7. Inch level from bottom of stem when 90% alarm 80 80 80 is triggered.
8. Does inch level at which the overfill alarm acti-
vates correspond with value programmed in the Iii Yes □No Iii Yes D No Iii Yes D No □Yes □No
gauge?
9. Inch level from the bottom when the water float 2 2 2 first triggers c1n alarm.
10. Does inch level at which the water float alarm
activates correspond with value programmed in Iii Yes D No Iii Yes □No Iii Yes O No □Yes □No
the gauge?
If any answers in Lines 3, 4, 5, or 6 are "No," the system has failed the test.
Test Results Iii Pass □Fail lil Pass □Fail lil Pass □ Fail □ Pass □Fail
Comments:
Tester's Name Luis Ledesma Tester's Signature ____________ _
2/3/25, 10:06 AM Veeder-Root K ATG
Issue Date: August 23, 1999
Revision Date: July 23, 2015
Veeder-Root
TLS-300, 350, 350R, 350Plus, 8600 Series (Consoles TLS· 450 and TLS-450PLUS), TLS2, Red Jacket ProMax and
ProPlus
Certification
Leak
Threshold
Applicability
Tank
Capacity
Waiting Time
Test Period
Temperature
Water Sensor
Calibration
Comments
(Models 8463, 8473, 8493 Magnetostrictive Probes)
AUTOMATIC TANK GAUGING METHOD
Leak rate of 0.2 gph with PD = 95.6% and PFA = 0.3%.
0.126 gph.
A tank system should not be declared tight if the testTesult indicates a loss or gain that equals or exceeds this
threshold.
Gasoline, diesel, aviation fuel, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM
D6751.
Maximum of 30,000 gallons.
Tanks less than 95% full may be tested.
Minimum product level required is based on tank diameter as follows:
48" dia/min 18";
64" dia/min 21";
72" dia/min 24";
96" dia/min 30";
126" dia/min 39";
132" dia/min 39".
For other tank diameters, see evaluation report.
Minimum of 8 hours between delivery and testing.
Minimum of 30 minutes between dispensing and testing.
There must be no delivery during waiting time.
Minimum of 2 hours.
Test data are acquired and recorded by system's computer.
Leak rate is calculated from the difference between the first and last data collected.
There must be no dispensing or delivery during test.
Average for product is determined by probe which contains 5 thermistors.
At least two thermistors must be submerged in product during test.
Must be used to detect water ingress.
Minimum detectable water level in the tank is 0.66 inch for model 8463 and 8493 probe.
Minimum detectable water level in the tank is 0.75 inch for model 8473 probe.
Minimum detectable water level in the tank is 0.38 inch when using TLS 350 with model 8463 probe with
88610x-0x0 water float and software version 30B or higher, or 8600 series with software version 3A or higher.
Minimum detectable change in water level is 0.005 inch.
Minimum detectable change in water level in tank is 0.01 inch when using TLS 350 with model 8463 probe
with 88610x-0x0 water float and software version 30B or higher, or 8600 series with software version 3A or
higher.
Thermistors and probe must be checked and, if necessary, calibrated in accordance with manufacturer's
instructions.
Not evaluated using manifolded tank systems. Therefore, this certification is only applicable when there is a
probe used in each tank and the siphon is broken during testing.
Tests only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank decreases (due to lower head pressure).
Consistent testing at low levels could allow a leak to remain undetected.
EPA leak detection regulations require testing of the portion of the tank which routinely contains product.
https://neiwpcc.org/nwglde-files/evals/veeder_root_k.html 1/2