HomeMy WebLinkAboutDERR-2024-005796 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRODUCT PIPING INTEGRITY TESTING
Facility Name: Point of the Mt. Water Treatment Plant Owner: Metropolitan Water District of SLC and
Sandy
Address: 235 Marion Vista Drive Address: 3430 East Danish Road
City, State, Zip: Draper, Utah 84020 City, State, Zip: Cottonwood Heights, Utah 84093
Facility I.D.#: 4002652 Phone #: 801-718-5846
Testing Company: Westech Phone #: 801-266-2545 Date: 3/12/24
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1 1 1 1
Product Stored DSL DSL DSL DSL
Piping Run 1 2 5 6
Piping Type Flex Flex Flex Flex
Test Pressure (PSI) 50 50 50 50
Test Duration (minutes) 30 30 30 30
Leak Rate (GPH) 0.003 0.003 0.002 0.002
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
D
S
L
A
S
T
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRODUCT PIPING INTEGRITY TESTING
Facility Name: Point of the Mt. Water Treatment Plant Owner: Metropolitan Water District of SLC and
Sandy
Address: 235 Marion Vista Drive Address: 3430 East Danish Road
City, State, Zip: Draper, Utah 84020 City, State, Zip: Cottonwood Heights, Utah 84093
Facility I.D.#: 4002652 Phone #: 801-718-5846
Testing Company: Westech Phone #: 801-266-2545 Date: 3/12/24
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1 1
Product Stored DSL DSL
Piping Run 7 8
Piping Type Flex Flex
Test Pressure (PSI) 50 50
Test Duration (minutes) 30 30
Leak Rate (GPH) 0.000 0.001
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
D
S
L
A
S
T