Loading...
HomeMy WebLinkAboutDDW-2025-005142Sanitary Survey - Deficiency Report PWS Number:UTAH02016 Deficiency Points:30 Survey Date:05/30/2025 Survey Name:HONEYVILLE TOWN WATER SYSTEM Surveyor:Cameron Draney Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Gaseous Chlorination | TP001 | FLINT-WHEATLY#1 CHLORINATOR 311. Exhaust fan takes suction near the floor as far as practical from the door and air inlet, and discharges outside away from air inlets. Rule: R309-520-7(2)(d)(iii)Rule requires a chlorine room exhaust fan to take suction inside the chlorine room near the floor, as far as practical from the door and air inlet, and discharge air outside of the building away from air inlets. Notes:Facility lacks exhaust fan. Door will need to be replaced to accommodate proper fan suction and visual inspection of chlorine tanks. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TD09 CHLORINE ROOM EXHAUST FAN SUCTION NOT LOCATED NEAR FLOOR Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Gaseous Chlorination | TP001 | FLINT-WHEATLY#1 CHLORINATOR 312. Air inlets are located near the ceiling and fitted with louvers. Rule: R309-520-7(2)(d)(iv)Rule requires chlorine room air inlets to be through wall louvers near the ceiling. Notes:Air inlet is through the ceiling. No louvers observed. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TD10 CHLORINE ROOM AIR INLET NOT LOCATED NEAR CEILING THROUGH WALL LOUVERS