HomeMy WebLinkAboutDDW-2025-004965Sanitary Survey - Deficiency Report
PWS Number:UTAH07002 Deficiency Points:15 Survey Date:05/23/2025
Survey Name:MYTON CITY Surveyor:Matt Hinckley
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
61A. Access opening framed at least 4 inches above roof surface or 18 inches above earthen cover.
Rule: R309-545-14(1)Rule requires tank access opening to be framed at least 4 inches above the surface of
the roof, or on a buried tank, to be at least 18 inches above any earthen cover over the
tank.
Notes:Access opening has been upgraded from the original opening, but new access hatch
assembly is mounted to a wood base (wood is between hatch frame and tank roof) and not
properly sealed to the roof surface.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V008 TANK ACCESS HEIGHT LESS THAN 4 INCHES ABOVE TANK ROOF OR LESS
THAN 18 INCHES ABOVE EARTHEN COVER