HomeMy WebLinkAboutDDW-2025-004960Sanitary Survey - Deficiency Report PWS Number:UTAH06021 Deficiency Points:80 Survey Date:05/13/2025 Survey Name:WOODS CROSS CITY WATER SYSTEM Surveyor:Danielle Zebelean Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL #1 (1500S 300W) 61B. Pump to waste line equipped with #4 non-corrodible mesh screen Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh corrosion-resistant screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Could not see or feel the screen Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL #1 (1500S 300W) 73C. Air vacuum relief valve on well discharge piping has at least 6 inches of clearance above floor Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well discharge piping to be at least 6 inches above the well house floor. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Was immediately remedied on site. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S030 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS A CLEARANCE OF AT LEAST 6 INCHES Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS002 | WELL #2 (720W 1500S) 96. Wells that pump directly into a distribution system have means to release trapped air from pump discharge piping (for example, pumps directly to a tank, has an air release valve or pump to waste line) Rule: R309-515-6(12)(d)(v)Rule requires a well that pumps directly into the distribution system be equipped with an air release/vacuum relief valve located upstream of the check valve, unless the wellhead valve and piping provide for pumping to waste all trapped air before water is introduced into the distribution system. Notes:Still deficient on survey Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SL01 WELL THAT PUMPS DIRECTLY TO DISTRIBUTION LACKS A MEANS TO RELEASE TRAPPED AIR Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | 2600 S SOUTH STORAGE 205A. Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin Rule: R309-545-10(1)(d)If the local authority allows discharge to a storm drain, the rule requires the drain discharge to have a physical clearance of at least 12 inches between the discharge end of the pipe and the overflow rim of the receiving basin. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Based on drawings from 1992 when the tanks were constructed, the drain line for ST003, ST004, and ST005 end in the storm drain to the west of the facility. Will need an exception. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES