HomeMy WebLinkAboutDERR-2025-004132Wheeler Tank Testing LLC.
Line Tightness Test Report
Station Market Express 3 Phillips
Address 755 South Carbon Ave
City State Price, UT
Zip
Wheeler Tank Testing LLCP.O. Box 1008Blackfoot , Idaho83221Kevin Wheeler 208-221-1662wheelertanktesting.inc@gmail.com
UST Compliance
Inspections
Leak Detectors
Line Tightness
Cathodic Protection
Tank Tightness
GPHTime Data GPL RES-/+
1500 62 -0-.0037 -0--0-
Product Line Test Report
Leak Detector Testing Report
Estabrook's EZY Chek
Date:May 19, 2025
-.0148-.0037.0037-1 611515
-0--0-.0037-0-611530
Product Type Unleaded Product Type
GPHTime Data GPL RES-/+
1500 28 -0-.0037 -0--0-
-.0148-.0037.0037-1 271515
-0--0-.0037-0-271530
Premium
Product Type
GPHTime Data GPL RES-/+
1500 56 -0-.0037 -0--0-
-0--0-.0037-0-561515
-0--0-.0037-0-561530
Diesel Product Type
GPHTime Data GPL RES-/+
1500 41 -0-.0037 -0--0-
-0--0-.0037-0-411515
-0--0-.0037-0-411530
Ethanol Free
Product Type
GPHTime Data GPL RES-/+
Product Type
GPHTime Data GPL RES-/+
Wheeler Tank Testing LLC.
Line Tightness Test Report
Comments:All Mechanical Leak Detectors are functioning properly. Test Pressure= 50 PSI.
Leak Detectors tested using Estabrook's Leak Detector tester. Simulated leak rate 3gph at 10psi.
Technician Name And Number:Kevin Wheeler UT 0233
Zip
City State Price, UT
Address 755 South Carbon Ave
Station Market Express 3 Phillips
UST Compliance
Inspections
Leak Detectors
Line Tightness
Cathodic Protection
Tank Tightness
Wheeler Tank Testing LLC.P.O. Box 1008Blackfoot , Idaho83221
Kevin Wheeler 208-221-1662 wheelertanktesting.inc@gmail.com
Product Type Pass/FailLine ID
Product Line Test
Final Results
Unleaded Pass
Pass-Premium
Pass-Diesel
Pass-Ethanol Free
Pass3 GPHRed Jacket FX-1DV
Pass3 GPHRed Jacket FX-1DV
Pass3 GPHRed Jacket FX-1V
Pass3 GPHRed Jacket FX-1V
Pass/FailDetected GPHLeak Detector Make
Leak Detector Testing
Final Results
-0-
-0-
-0-
-0-
GPH
Date:May 19, 2025
Ethanol Free
Diesel
Premium
Unleaded
Product Type