HomeMy WebLinkAboutDERR-2025-004130Wheeler Tank Testing LLC. Line Tightness Test Report Station Market Express 2 (Chevron) Address 121 Carbonville Ave City State Price, UT Zip Wheeler Tank Testing LLCP.O. Box 1008Blackfoot , Idaho83221Kevin Wheeler 208-221-1662wheelertanktesting.inc@gmail.com UST Compliance Inspections Leak Detectors Line Tightness Cathodic Protection Tank Tightness GPHTime Data GPL RES-/+ 2045 43 -0-.0037 -0--0- Product Line Test Report Leak Detector Testing Report Estabrook's EZY Chek Date:May 19, 2025 -.0148-.0037.0037-1 422100 -.0148-.0037.0037-1 412115 Product Type Unleaded Product Type GPHTime Data GPL RES-/+ 2045 62 -0-.0037 -0--0- -.0148-.0037.0037-1 612100 -.0148-.0037.0037-1 602115 Premium Product Type GPHTime Data GPL RES-/+ 2045 80 -0-.0037 -0--0- -0--0-.0037-0-802100 -0--0-.0037-0-802115 Ethanol Free Product Type GPHTime Data GPL RES-/+ 2045 38 -0-.0037 -0--0- -0--0-.0037-0-382100 -.0148-.0037.0037-1 372115 Diesel Product Type GPHTime Data GPL RES-/+ Product Type GPHTime Data GPL RES-/+ Wheeler Tank Testing LLC. Line Tightness Test Report Comments:Leak Detectors functioning properly. Test Pressure= 50 PSI. Leak Detectors tested using Estabrook's Leak Detector tester. Simulated leak rate 3gph at 10psi. Technician Name And Number:Kevin Wheeler UT 0233 Zip City State Price, UT Address 121 Carbonville Ave Station Market Express 2 (Chevron) UST Compliance Inspections Leak Detectors Line Tightness Cathodic Protection Tank Tightness Wheeler Tank Testing LLC.P.O. Box 1008Blackfoot , Idaho83221 Kevin Wheeler 208-221-1662 wheelertanktesting.inc@gmail.com Product Type Pass/FailLine ID Product Line Test Final Results Unleaded Pass Pass-Premium Pass-Diesel Pass-Non Eth UL Pass3 GPHVMI 99-ld 2000 Pass3 GPHRed Jacket FX-1V Pass3 GPHVMI 99-ld 2000 Pass3 GPHRed Jacket FX-1V Pass/FailDetected GPHLeak Detector Make Leak Detector Testing Final Results -0- -.0148 -.0148 -.0148 GPH Date:May 19, 2025 Non Ethanol Premium Diesel Unleaded Product Type