Loading...
HomeMy WebLinkAboutDERR-2024-005718APPENDIX C-9 MECHANICAL AND ELECTRONIC LINE LEAK DETECTORS PERFORMANCE TEST owner: Maverik Inc Addre ss: 185 S State St Ste 800 City, State, Zip Code:SLC UT 84111 Facility Name:Maverik # 516 Address: 1078 E State St City, state, Zip Code: American Fork UT 84003 Facility I.D. #: 1000930 Testing Company: Precision Testing Technologies Inc. Phone #:801-936-5557 Phone #: 801-886-9224 Date: 01/31/2024 This data sheet can be used to test mechanical line leak detectors (MLLD) and electronic line leak detectors (ELLO) with submersible turbine pump (STP) systems. See PEI/RP1200, Sections 9.1 and 9.2 for test procedures. Line Number 1 2 3 4 Product Stored Dsl Prm Reg Cir Leak Detector Manufacturer VR VR VR VR Leak Detector Model PLLD PLLD PLLD PLLD Ty pe of Leak Detector CJ MLLD CJ MLLD CJ MLLD CJ MLLD CJ MLLD CJ MLLD El ELLO El ELLO El ELLO El ELLO □ELLO □ELLO MLLD (ALL PRESSURE MEASUREMENTS ARE MADE IN PSIG) STP Full Operating Pressure Check Valve Holding Pressure Line Resiliency (ml) (line bleed back vol- ume as measured from check valve hold- ing pressure to zero psig) Step Through Time in Seconds (time the MLLD hesitates at metering pressure before going to full operating pressure as measured from O psig with no leak induced on the line) Metering Pressure (STP pressure when simulated leak rate 3 gph at 10 psig) Opening Time in Seconds (the time the MLLD opens to allow full pressure after simulated leak is stopped) Does the STP pressure remain at or below the metering pressure for at least □Yes CJ No □Yes CJ No □Yes CJ No □Yes CJ No □Yes CJ No □Yes □No60 seconds when the simulated leak is induced? Does the leak detector reset (trip) when □Yes □No □Yes □ No □Yes CJ No □Yes □No □Yes □No □Yes □Nothe line pressure is bled off to zero psig? Does the STP properly cycle on/off under □Yes □No □Yes □No □Yes □No □Yes □No □Yes □No □Yes □Nonormal fuel system operation conditions? A "No" answer to either of the above questions indicates the MLLD fails the test. ELLO (ALL PRESSURE MEASUREMENTS ARE MADE IN PSIG) STP Full Operating Pressure 38 39 39 38 How many test cycles are observed 2 2 2 2 before alarm/shutdown occurs? Does the simulated leak cause an alarm? El Yes □No El Yes □No El Yes □No El Yes □No □Yes □No □Yes □No A "No" answer to the above question indi- cates the ELLO fails the test. Does the simulated leak cause an STP Elves □No El Yes CJ No El Yes CJ No EIYes □No □Yes □No □Yes □No shutdown? □NA □NA □NA □NA □NA □NA Test Results El Pass □ Fail El Pass CJ Fail El Pass □ Fail El Pass □ Fail □Pass □ Fail □Pass □ Fail Comments: Tester's Name Danny Jones UT 379 Tester's Signature _ __..,V."'--""47"'"""=i;......��a.LLM""""'4<"""'---- APPENDIX C-7 AUTOMATIC TANK GAUGE OPERATION INSPECTION Owner: Address: City, State, Zip Code: Phone#: Facility Name: Maverik # 516 Address: City, State, Zip Code: Facility I.D. #: 1000930 Testing Company: Precision Testing Technologies Inc. Phone #: 801-886-9224 I Date: 01/31/2024 This procedure is to determine whether the ATG is operating properly. See PEI/RP1200, Section 8.2 for the inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place. Tank Number 1 2 3 4 Product Stored Dsl Cir Prm Reg ATG Brand and Model VR TLS 450+ VR TLS 450+ VR TLS 450+ VR TLS 450+ 1.Tank Volume, gallons 11608 11608 11608 11608 2.Tank Diameter, inches 90.5 90.5 90.5 90.5 3.After removing the ATG from the tank, has itbeen inspected and any damaged or missing parts El Yes □No El Yes □No El Yes □No El Yes □No replaced? 4.Float moves freely on the stem without binding?El Yes □No El Yes □No El Yes □No El Yes □No 5.Does the fuel float level agree with the value El Yes □No El Yes □No El Yes □No El Yes □No programmed into the console? 6.Does the water float level agree with the value El Yes □No El Yes □No El Yes □No El Yes □No programmed into the console? 7.Inch level from bottom of stem when 90% alarm 76.5 76.5 76.5 76.5 is triggered. 8.Does inch level at which the overfill alarm acti-vates correspond with value programmed in the El Yes □No El Yes □No El Yes □No El Yes □No gauge? 9.Inch level from the bottom when the water float 1 1 1 1 first triggers an alarm. 10.Does inch level at which the water float alarmactivates correspond with value programmed in El Yes □ No El Yes □No El Yes □ No El Yes □ No the gauge? If any answers in Lines 3, 4, 5, or 6 are "No," the system has failed the test. Test Results El Pass □ Fail El Pass □Fail El Pass □ Fail El Pass □ Fail Comments: Tester's Name Danny Jones UT 379 Tester's Signature __ D._7-____,�--��---J'UL4.,, ____ _ LIQUID SENSOR FUNCTIONALITY TESTING [ Facility Nam e: Maverik # 516 I Address: City, State, Zip Code: Facility I.D. #: 1 000930 Owner: Address: City, State, Zip Code: Phone#: Testing Company:Precision Testing Technologies Inc.I Phone #: 801-886-9224 I Date: 01/31/2024 This procedure is to determine whether liquid sensors located in the interstitial space of UST systems are able to detect the presence of water and fuel. See PEI/RP1200, Section 8.3 for the test procedure. Sensor Location Product Stored Type of Sensor Test Liquid Is the ATG console clear of any active or recurring warnings or alarms regarding the leak sensor? If the sensor is in alarm and functioning, indicate why. Is the sensor alarm circuit operational? Has sensor been inspected and in good operating condition? When placed in the test liquid, does the sensor trigger an alarm? When an alarm is triggered, is the sensor properly identified on the ATG console? Dsl int Dsl □Discriminating B Non-discrimi- nating□ Water Lift□Product El Yes □ No BYes □ No El Yes □ No El Yes □ No El Yes □ No Any "No" answers indicates the sensor fails the test. Cir int Cir □Discriminating B Non-discrimi- nating□Water Lift□Product BYes □No El Yes □ No El Yes □ No El Yes □ No El Yes □ No Prm int Prm □Discriminating B Non-discrimi- nating□ Water Lift□Product BYes □ No BYes □No El Yes □ No El Yes □ No El Yes □ No Reg int Reg □Discriminating B Non-discrimi- nating□Water Lift□Product BYes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No Dsl stp Dsl □Discriminating B Non-discrimi- nating BWater□Product BYes □No El Yes □ No El Yes □ No El Yes □ No El Yes □ No Cir stp Prm stp Cir Prm □Discriminating □ Discriminating B Non-discrimi-B Non-discrimi- nating nating BWater BWater□Product □Product BYes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No Test Results El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail Comments: Tester's Name Danny Jones UT 379 Tester's Signature D7 y� LIQUID SENSOR FUNCTIONALITY TESTING [ Facility Name: Maverik # 516 I Address: City, State, Zip Code: Facility I.D. #: 1000930 Owner: Address: City, State, Zip Code: Phone#: Testing Company: Precision Testing Technologies Inc. I Phone #: 801-886-9224 I Date: 01/31/2024This procedure is to determine whether liquid sensors located in the interstitial space of UST systems are able to detect the presence of water and fuel. See PEI/RP1200, Section 8.3 for the test procedure. Sensor Location Product Stored Type of Sensor Test Liquid Is the ATG console clear of any activeor recurring warnings or alarms regarding the leak sensor? If the sensor is in alarm and functioning,indicate why. Is the sensor alarm circuit operational? Has sensor been inspected and ingood operating condition? When placed in the test liquid, doesthe sensor trigger an alarm? When an alarm is triggered, is the sensor properly identified on the ATGconsole? Reg stp Reg □ DiscriminatingB Non-discrimi-nating El Water □Product El Yes □ No 0Yes □ No El Yes □ No El Yes □ No El Yes □ No Any "No" answers indicates the sensor fails the test. Disp 1/2 3/4 Lines Lines □ Discriminating □ DiscriminatingB Non-discrimi-B Non-discrimi-nating nating 0Water 0Water □Product □Product 0Yes □No 0Yes □ No BYes □No 0Yes □No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No 5/6 7/8 9/10 11/12 Lines Lines Lines Lines □ Discriminating □ Discriminating □ Discriminating □ DiscriminatingB Non-discrimi-0 Non-discrimi-0 Non-discrimi-B Non-discrimi-nating nating nating nating 0Water 0Water 0Water BWater □Product □Product □Product □Product 0Yes □ No 0Yes □No 0Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No El Yes □ No Test Results El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail I El Pass □ Fail Comments: Tester's Name Danny Jones UT 379 Tester's Signature D7 y�