HomeMy WebLinkAboutDDW-2025-004940Sanitary Survey - Deficiency Report
PWS Number:UTAH10004 Deficiency Points:130 Survey Date:05/23/2025
Survey Name:THOMPSON SPECIAL
SERVICES DISTRICT
Surveyor:Tom McOmie
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | NORTH STEEL TANK
74A. Vent is either down-turned or shielded from contaminants (at least 2 inches below the bottom of the opening)
Rule: R309-545-15(1)Rule requires inverted vents on water storage tanks to be down-turned a minimum of 2
inches below any opening and shielded to prevent the entrance of contaminants. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:The vent on this tank does not meet the rule. It needs to be covered with so the screens are
not exposed to the elements.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V005 STORAGE FACILITY VENT NOT DOWNTURNED AT LEAST 2 INCHES BELOW
ANY OPENING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | NORTH STEEL TANK
76. Access opening locked
Rule: R309-545-14(3)Rule requires the lid to any access opening to have a locking device. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:There is not a lock on this opening. Might need to replace a bolt with a lock.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | SOUTH STEEL TANK
88A. Vent is either down-turned or shielded from contaminants (at least 2 inches below the bottom of the opening)
Rule: R309-545-15(1)Rule requires inverted vents on water storage tanks to be down-turned a minimum of 2
inches below any opening and shielded to prevent the entrance of contaminants. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:The vent on this tank does not meet the rule. It needs to be covered with so the screens are
not exposed to the elements.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V005 STORAGE FACILITY VENT NOT DOWNTURNED AT LEAST 2 INCHES BELOW
ANY OPENING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | SOUTH STEEL TANK
90. Access opening locked
Rule: R309-545-14(3)Rule requires the lid to any access opening to have a locking device. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:There is not a lock on this opening. Might need to replace a bolt with a lock.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | SPRING 1 CHLORINATOR
130. Exhaust fan takes suction near the floor as far as practical from the door and air inlet, and discharges outside away from air inlets.
Rule: R309-520-7(2)(d)(iii)Rule requires a chlorine room exhaust fan to take suction inside the chlorine room near
the floor, as far as practical from the door and air inlet, and discharge air outside of the
building away from air inlets.
Notes:Still needs and exhaust fan.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD09 CHLORINE ROOM EXHAUST FAN SUCTION NOT LOCATED NEAR FLOOR
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | SPRING 1 CHLORINATOR
131. Air inlets are located near the ceiling and fitted with louvers.
Rule: R309-520-7(2)(d)(iv)Rule requires chlorine room air inlets to be through wall louvers near the ceiling.
Notes:No air inlet or louvers.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD10 CHLORINE ROOM AIR INLET NOT LOCATED NEAR CEILING THROUGH WALL
LOUVERS