Loading...
HomeMy WebLinkAboutDDW-2025-004833ZION NATIONAL PARK SYSTEM DESIGNATION PLAN WATER SYSTEM 27051 WTP001, WTP003, WTP004 This document outlines the required actions to reestablish Zion Canyon WS 27051(WTP001, WTP003 and WTP004) to groundwater designation. Currently WS27051-WTP001 (Birch Creek) utilizes the following filtration components: 1. Existing Birch System Description: Floor mounted housing with three replaceable elements for removing suspended particles from water. The system consists of two parallel trains of two filter housings in series: with prefilter cartridges in the initial housing and compliance filters in the second housing. a. Harmsco, Inc. Municipal-3 model 1) Material: 304 Stainless steel. 2) Pressure Rating: 150 psig. 3) Seals: EPDM. 4) Diameter: 20 inches. 5) Height or Length: 63 inches. 6) Inlet and Outlet Size: 3 NPS. 7) Drain Size: 1-1/2 NPS. b. Pre-Filter Elements: 1) Number Required: Three. 2) Harmsco HC/170-1 3) Media: Pleated polyester. 4) Maximum loading: 0.5 gpm / ft2of filter area. 5) DWG 116, PG 6 designator-Filter #3, Filter #4 c. Compliance Filter Elements 1) Number Required: Three. 2) Harmsco HC/170-LT2 3) Media: borosilicate glass. 4) Maximum loading: 0.75 gpm / ft2of filter area.5) DWG 116, PG. 6 designator-Filter #1, Filter #2 To meet the new ground water designation, all six (6) existing compliance filter media (HC/170-LT2) will be replaced with Harmsco media HC/170-1. See attached drawing. All other existing components in WTP001 will remain the same. Currently WS27051-WTP003 (Lower Grotto) and WTP004 (Upper Grotto) utilize the following filtration components: 1. Existing Upper and Lower Grotto System Description: Floor-mounted housing with a single replaceable element for removing suspended particles from water. Each system consists of two parallel trains of two filter housings in series; with prefilter cartridges in the initial housing and compliance filters in the second housing. Filter Design: 1) Continuous Flow: 30 gpm. 2) Peak Flow: 60 gpm. 3) Combined Filtration Efficiency: Shall meet the Challenge Test Method defined in the Long Term Two Enhanced Surface Water Treatment Rule Toolbox Guidance Manual. 4) Pressure Drop: Not to exceed 2 psig at filter peak design flow rate when clean. b. Harmsco, Inc. Municipal-1 model: 1) Material: 304 Stainless steel. 2) Pressure Rating: 150 psig. 3) Seals: EPDM. 4) Diameter: 11 inches. 5) Height or Length: 48 inches. 6) Inlet and Outlet Size: 2 NPS. 7) Drain Size: 3/4 NPS. c. Pre-Filter Elements: 1) Number Required: One. 2) Harmsco HC/170-1 3) Media: Pleated polyester. 4) Maximum loading: 0.5 gpm / ft2 of filter area. 5) DWG 116, PG 13 designator-LG Filter #3, LG Filter #4 and UG Filter #3, UG Filter #4 d. Compliance Filter Elements 1) Number Required: One. 2) Harmsco HC/170-LT2 3) Media: borosilicate glass. 4) Maximum loading: 0.75 gpm / ft2 of filter area. 5) DWG 116, PG 13 designator-LG Filter #1, LG Filter #2 and UG Filter #1 and UG Filter #2 To meet the new ground water designation, all four (4) existing compliance filter media (HC/170-LT2) will be replaced with Harmsco media HC/170-1. See attached drawing. All other existing components in WTP003 and WTP004 will remain the same.