HomeMy WebLinkAboutDDW-2025-004122Sanitary Survey - Deficiency Report
PWS Number:UTAH06004 Deficiency Points:25 Survey Date:04/28/2025
Survey Name:FARMINGTON CITY WATER
SYSTEM
Surveyor:Chris Bowles
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | RUDD CREEK SPRING
74. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:Current water operator has no
idea where the spring is located and it has
not been connected to distribution since the
flood in the 80's
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | RUDD CREEK SPRING
75. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:Current water operator has no
idea where the spring is located and it has
not been connected to distribution since the
flood in the 80's
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST011 | C-2A STORAGE
309. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:Condensation accumulating inside first vault that needs to be addressed. Currently no signs
of leakage into tank since water is accumulating.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN