Loading...
HomeMy WebLinkAboutDDW-2025-004122Sanitary Survey - Deficiency Report PWS Number:UTAH06004 Deficiency Points:25 Survey Date:04/28/2025 Survey Name:FARMINGTON CITY WATER SYSTEM Surveyor:Chris Bowles Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | RUDD CREEK SPRING 74. Is a spring collection box present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box to permit spring inspection and testing. Notes:Current water operator has no idea where the spring is located and it has not been connected to distribution since the flood in the 80's Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | RUDD CREEK SPRING 75. Is a spring box vent present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect to venting. Therefore, a junction or collection box requires a vent to be fitted with #14 mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the entrance of contaminants, be located and sized to avoid blockage during winter, and have the end of the vent discharge a minimum of 24 inches above the earth on buried structures. Notes:Current water operator has no idea where the spring is located and it has not been connected to distribution since the flood in the 80's Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST011 | C-2A STORAGE 309. Storage tank roof is sloped to prevent ponding Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding. Notes:Condensation accumulating inside first vault that needs to be addressed. Currently no signs of leakage into tank since water is accumulating. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO DRAIN