Loading...
HomeMy WebLinkAboutDDW-2025-003939 April 25, 2025 Mike Rau Central Utah WCD - Utah Valley 1426 East 750 North Suite 400 Orem, Utah 84097 Subject:New Source Approval, Strawberry Reservoir Diversion (WS013) for DACRWTP (TP001); Central Utah WCD - Utah Valley, System #25112, File #15883 Dear Mike Rau:On July 25, 2024, the Division of Drinking Water (the Division) received a request to review source data as part of a potential new source to be treated by the following surface water treatment plants:Don A. Christiansen Regional Water Treatment Plant (TP001) for Central Utah Water Conservancy District-Utah Valley (System #25112). Little Cottonwood (TP002) and Point of the Mountain (TP003) for Metropolitan Water District of Salt Lake and San (System #18016).Jordan Valley WTP (TP002) for Jordan Valley Water Conservancy District (WCD) (System #18027)The potential new source is identified as the Strawberry Reservoir Diversion. It is identified as WS013 in the Division’s database.The Strawberry Reservoir Diversion (WS013) will be treated by the Don A. Christiansen Regional Water Treatment Plant (DACRWTP). The DACRWTP is operated by Central Utah Water Conservancy District - Utah Valley water system (the District). The Division received the following information for the project: Map showing source flow to the DACRWTP (TP001). Strawberry Reservoir New Source Application Data including new source chemistry data, historical water quality data, Strawberry Reservoir conventional piloting summary, and DACRWTP treatment of the Strawberry Reservoir source. Map of sampling locations and langelier saturation index (LSI) related data. Water Rights confirmation. Baseline LSI data from DACRWTP (TP001) finished water and distribution system. Information from DACRWTP treatment of Strawberry Reservoir Diversion (WS013) during Olmstead radial gate failure on August 24, 2024. Infrastructure timeline. Our understanding of the project is that a new surface water source will be provided to increase system resiliency. The new source is from the Strawberry Reservoir, which is conveyed through the existing infrastructure of the Utah Lake Drainage Basin Water Delivery System (ULS). The ULS system consists of buried pipelines extending from the terminus of the Diamond Fork System at the mouth of Diamond Fork Canyon in Utah County, down Spanish Fork Canyon to the western side of the Wasatch Mountains. The Strawberry Reservoir water flows into the Alpine Aqueduct via the penstock, and the Olmstead hydro completed in October 2018. Central Utah Water Conservancy District (CUWCD) provided LSI data from DACRWTP finished water and the North Shore Terminal Reservoir. The LSI for the DACRWTP finished water ranges from -0.655 to 0.308 with an average of 0.083 from February 24, 2024, to February 24, 2025. Based on the provided data, the LSI measured at the North Shore Terminal Reservoir is similar to the DACRWTP finished water. On August 24, 2024, the Olmstead radial gate malfunctioned, requiring the DACRWTP to treat a mixture of Provo River water with Strawberry Reservoir water. The monitored water quality parameters, such as turbidity, pH, and LSI, remained unchanged without significant operational changes, including primary coagulant dose using ferric chloride. We have completed our review of the submittaland hereby approve the Strawberry Reservoir Diversion (WS013) to be treated by the Don A. Christiansen Regional Water Treatment Plant (TP001) with the following conditions: You must notify the Division when you first begin to use the new source. You must submit seven days of operational data included in the monthly Surface Water Treatment Rule report. You must submit source chemistry data for the new finished water source. You must complete two rounds of LT2 monitoring on the Strawberry Reservoir Diversion (WS013) per R309-215-15. Contact Sarah Page at sepage@utah.gov to set up an approved LT2 sampling schedule. You must fulfill and comply with all of the conditions of approvalor this approval is invalid. Monitoring RequirementFor one year, submit a monthly report stating whether the Strawberry Reservoir (WS013) was introduced that month. If it was, then provide weekly LSI, chloride, and sulfate sample data from the DACRWTP while it was in use. Facility with new requirements Analyte(s) Required # of samples Sampling Frequency TP001 pH, Alkalinity, Calcium, Conductivity, Temperature 1 Weekly (when Strawberry Reservoir is being treated) TP001 Chloride 1 Weekly (when Strawberry Reservoir is being treated) TP001 Sulfate 1 Weekly (when Strawberry Reservoir is being treated) Drinking Water Source Protection Requirement R309-605 states that PWSs who jointly submit an acceptable DWSP plan for one surface water source above common point(s) of diversion will be considered to have met the requirements of R309-605-7(1)(a). If you have any questions about the Source Protection requirements, please reach out to Melissa Noble, P.G., at (385) 271-7043 or mnoble@utah.gov. If you have any questions regarding this approval, please contact Chris Martin, P.E., of this office, at (385) 271-7040, or me at (385) 515-1464. Sincerely, Michael Newberry, P.E. Permitting and Engineering Support Manager CM/mrn/mdbcc:Daymon Swensen, Utah County Health Department, daymons@utahcounty.govMike Rau, Central Utah WCD - Utah Valley, miker@cuwcd.govErik Cram, Central Utah WCD - Utah Valley, Erik@cuwcd.govJoe Crawford, Central Utah WCD - Utah Valley, Joe@cuwcd.govShaun Hilton, Central Utah WCD - Utah Valley, shaun@cuwcd.govWill Garner, Central Utah WCD - Utah Valley, will@cuwcd.govSarah Page, Ph.D., Division of Drinking Water, sepage@utah.gov (surface water treatment)Julie Cobleigh, P.E., Division of Drinking Water, jcobleigh@utah.govNagendra Dev, P.E., Division of Drinking Water, ndev@utah.govChris Martin, P.E., Division of Drinking Water, cmartin@utah.gov Melissa Noble, P.G., Division of Drinking Water, mnoble@utah.gov David Kruse, Division of Drinking Water, dbkruse@utah.gov (arsenic, inorganics, organics, nitrate, rads) Dylan Martinez, Division of Drinking Water, dmartinez@utah.gov (lead and copper)CMartin 25112 15883 WS013 for TP001 PA - Strawberry Reservoir Source