HomeMy WebLinkAboutDDW-2025-003843Rio Tinto Kennecott
4700 Daybreak Parkway
South Jordan, Utah 84009
T (801) 304-1256
M (385) 246-7937
E-mail trevor.paulson@riotinto.com
Trevor Paulson
Senior Advisor – Water
April 8, 2025 DDWreports@utah.gov Utah Division of Drinking Water
Via e-mail
Subject: First Quarter 2025 Point of Use Treatment Report Kennecott Section 21 Public Water System 18003, (File #06826)
In accordance with Kennecott Utah Copper’s Operation Permit (File #06826) issued on January 10, 2006, enclosed is the First Quarter 2025 Point of Use Treatment and Monitoring Report for arsenic for the Section 21 Public Water System 18003.
Seven Reverse Osmosis (RO) treatment units were sampled and analyzed for arsenic during this reporting period.
Sincerely,
Trevor Paulson Senior Advisor – Water
Attachments (8)
Operation - RO
Filter
Sample Date Results ug/L mho/cm Days January-25 February-25 March-25
Central Lab CL1 02/12/25 < 5 12 154 20 14 20
Administration Upstairs RF2 02/12/25 < 5 115 182 111 113 139
Precious Metals Lunch Room RF6 270 267 262
2nd Floor West Admin Break room SM1 02/12/25 < 5 146 36 197 175 180
2nd Floor Admin 264 SM2 02/12/25 < 5 212 141 239 199 201
Hot Metals - Reliability Shop SM5 02/12/25 < 5 180 251 201 192 203
EDX Building Lunchroom SM11 248 240 242
Hot Metals - Materials Handling SM17 124 177 180
Anodes Office - Trailer SM18 145 197 200
Smelter Women's Change Room SM20 424 424 444
Smelter Men's Change Room SM21 247 246 200
Materials Handling Shop SM36 183 288 280
Filter Plant Lunchroom SM39 177 202 201
Records Building SM41 192 233 230
Garage SM42 270 272 273
Contractors Lunchroom SM43 240 241 241
MEIT Shop SM44 262 260 264
Engineering East SM46 155 117 Removed
Engineering West SM47 59 60 65
Hot Metals Bldg 3rd Fl Sou End SM52 200 184 185
Admin Northwest SM51 390 455 200
Admin North East SM50 120 125 127
3rd Floor So End Hot Metal ice machine SM53 126 116 117
North Tailings Administration NT54 273 274 148
Refinery Gym RF7 274 280 286
Sample Prep CL2 02/12/25 < 5 230 130 209 210 298
Sample Prep RO CL3 02/12/25 < 5 336 130 205 212 243
Machine Location & Description Arsenic and Conductivity Conductivity Results (mho/cm)/Maintenance Conducted
Kennecott Section 21 System 18003 First Quarter 2025 POU Arsenic Report
RTKC ID
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 1 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
CL1 T
JA02365KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 12
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 2 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
CL2 T
JA02366KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 230
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 3 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
CL3 T
JA02367KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 336
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 4 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
RF2 T
JA02368KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 115
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 5 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
SM1 T
JA02370KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 146
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 6 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
SM2 T
JA02371KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 212
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)
Kennecott Environmental Laboratory
Certificate of Analysis ---March 11, 2025
Well Designation:
Collection Date:
Submission Date:
02/12/2025
02/13/2025
Page 7 of 7
9180 W 2500 S
Magna, UT 84044
Phone (801) 569-7952
SM5 T
JA02369KEL Sample ID Numbers:
Total Dissolved
Metals Metals
CRDL Result Unit Method Analyte Result
*Micro mho/cm 1* Conductivity (Field) 180
ug/L 5Arsenic 200.8 < 5
* =Included for information purposes only, not performed by KEL.
NA = Not Analyzed
The Contract Required Detection Limits (CRDL) are minimum reporting limits required by the
Ground Water Characterization and Monitoring Plan (GCMP)