HomeMy WebLinkAboutDAQ-2024-011078
Small Source Registration
DAQE-EN116230003-24
{{$d1 }}
Ulysses Davis
National Oceanic and Atmospheric Administration - National Weather Service Salt Lake City Office
2242 West North Temple Street
Salt Lake City, UT 84116
ulysses.davis@noaa.gov
Dear Ulysses Davis:
Re: Request for Evaluation of Compliance with Rule R307-401-9, UAC: Small Source Exemption
Project Fee Code: N116230003
On September 10, 2024, the Division of Air Quality (DAQ) received your request for a small source
exemption for the National Oceanic and Atmospheric Administration (NOAA)-National Weather Service (NWS) Salt Lake City Office. The source is located at 2242 West North Temple Street in Salt Lake City,
Salt Lake County. On-site equipment includes one (1) diesel-fired, 376 horsepower (380 kilowatt)
emergency generator engine. DAQ has determined the small source exemption applies to the source, as long as the equipment and associated processes operate as specified in the registration request.
The small source exemption does not exempt a source from complying with other applicable federal,
state, and local regulations and the current Utah Administrative Code. Based on the emissions that you
submitted to DAQ with your registration request, the NAAO-NSW Salt Lake City Office is not required
to obtain an approval order under R307-401. If you change your operation such that there is an increase in
emissions, we recommend that you notify us, as an approval order may be required.
As authorized by the Utah Legislature, the fee for issuing this small source exemption is a one-time filing
fee in addition to the actual time spent by the review engineer and all other staff on the project. Payment
should be sent to DAQ upon receipt of the invoice.
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144820 • Salt Lake City, UT 84114-4820
Telephone (801) 536-4000 • Fax (801) 536-4099 • T.D.D. (801) 903-3978
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF AIR QUALITY
Bryce C. Bird
Director
" - 1 " * " / Ú Û Û Ù Û Ý
DAQE-EN116230003-24
Page 2
Thank you for registering your source with the DAQ. If you have any additional questions, please contact
Christine Bodell at (385) 290-2690 or cbodell@utah.gov.
Sincerely,
Bryce C. Bird
Director
{{$s }}
Alan D. Humpherys, Manager
New Source Review Section
BCB:ADH:CB:jg
{{#d1=date1_es_:signer1:date:format(date, "mmmm d, yyyy")}} {{#s=Sig_es_:signer1:signature}}
Equipment Details
Rating 376 hp = (280.6 kw)
Operational Hours 100 hours/yearSulfur Content 15 ppm or 0.0015%
Criteria Pollutant
Emission
Standards
(g/hp-hr)
Emission Factor
(lb/hp-hr)
Emission
Rate
(lbs/hr)
Emission
Total
(tons/year)Reference
NOX 0.031 11.66 0.58
CO 6.68E-03 2.51 0.13
PM10 2.20E-03 0.83 0.04
PM2.5 2.20E-03 0.83 0.04
VOC 2.51E-03 0.95 0.05
SO2 1.21E-05 0.00 0.00 AP-42 Table 3.4-1
HAP 0.01 0.00 See Below
Green House Gas Pollutant
Global
Warming
Potential
Emission Factor
(lb/hp-hr)
Emission
Rate
(lbs/hr)
Emission
Total
(tons/year)Reference
CO2 (mass basis)1 1.15 432 22
Methane (mass basis)25 0 0CO2e22
Hazardous Air Pollutant
Emission
Rate
(lbs/hr)
Emission
Total
(tons/year)Reference
Benzene 9.33E-04 2.46E-03 1.23E-04
Toluene 4.09E-04 1.08E-03 5.38E-05
Xylenes 2.85E-04 7.50E-04 3.75E-051,3-Butadiene 3.91E-05 1.03E-04 5.15E-06
Formaldehyde 1.18E-03 3.11E-03 1.55E-04
Acetaldehyde 7.67E-04 2.02E-03 1.01E-04
Acrolein 9.25E-05 2.43E-04 1.22E-05
Naphthalene 8.48E-05 2.23E-04 1.12E-05
Acenaphthylene 5.06E-06 1.33E-05 6.66E-07
Acenaphthene 1.42E-06 3.74E-06 1.87E-07
Fluorene 2.92E-05 7.69E-05 3.84E-06
Phenanthrene 2.94E-05 7.74E-05 3.87E-06
Anthracene 1.87E-06 4.92E-06 2.46E-07
Fluoranthene 7.61E-06 2.00E-05 1.00E-06
Pyrene 4.78E-06 1.26E-05 6.29E-07
Benz(a)anthracene 1.68E-06 4.42E-06 2.21E-07
Chrysene 3.53E-07 9.29E-07 4.65E-08
Benzo(b)fluoranthene 9.91E-08 2.61E-07 1.30E-08
Benzo(k)fluoranthene 1.55E-07 4.08E-07 2.04E-08
Benzo(a)pyrene 1.88E-07 4.95E-07 2.47E-08
Indeno(1,2,3-cd)pyrene 3.75E-07 9.87E-07 4.94E-08
Dibenz(a,h)anthracene 5.83E-07 1.53E-06 7.67E-08
Benzo(g,h,l)perylene 4.89E-07 1.29E-06 6.44E-08
AP-42 Table 3.3-2,
Table 3.4-3, &
Table 3.4-4
(1,3-Butadiene will
not popluate if the
engine size is greater
than 600 hp. AP-42 does not list 1,3-
Butadiene for engines
greater than 600 hp.)
Diesel-Fired Engines
AP-42 Table 3.3-1
& Table 3.4-1
Manufacturer Data,
AP-42 Table 3.3-1,
& Table 3.4-1
Emission Factor
(lb/MMBtu)
Emergency Engines should equal 100 hours of operation per year
Page 1 of 1 Version 1.1February 21, 2019
Response Summary:
To be eligible businesses shall not do any of the follow:
1) Emit more than 5 tons per year of each of the following pollutants: Sulfur Dioxide (SO2), Carbon Monoxide (CO),
Nitrogen Oxides (NOx), Particulate Matter (PM10), Ozone (O3), or Volatile Organic Compounds (VOCs).
2) Emit more than 500 lbs/yr of any single Hazardous Air Pollutant (HAP), and emit more than 2000 lbs/yr of any
combination of HAPs
3) Emit more than 500 lbs/yr of any combination of air contaminants not listed in 1 or 2
A copy of this registration notice and worksheets are required on site to verify permit exemption status.
Please be aware a the Small Source Exemption ONLY exempts the site from the air permitting requirements of R307-
401-5 thru R307-401-8 of the Utah Administrative Code, all other air quality regulations still apply.
Q4.
Please fill out the following contact information:
Site Contact Site Owner
Name Ulysses Davis National Weather Service NOAA-NWS
Mailing Address 2242 West North Temple
St
2242 West North Temple
St
2242 West North Temple
St
Mailing Address 2
City Salt Lake City Salt Lake City Salt Lake City
State UT UT UT
Zip Code 84116 84116 84116
Phone 801-524-5710 801-524-5710 801-524-5710
Fax Na NA NA
Email ulysses.davis@noaa.gov ulysses.davis@noaa.gov ulysses.davis@noaa.gov
Q5. County the Site is located in:
Salt Lake County
Q6. Briefly describe the process including the end products, raw materials, and process equipment used.
One single 280KW emergency power generator. Expected to run 26 hours per year.
Q7. List emission units
If run 100 hours:
NOx – 0.58 tons
CO – 0.13 tons
PM10 – 0.04 tons
PM2.5 – 0.04 tons
VOC – 0.05 tons
SO2 – 0 tons
HAP 0 tons
Q8. List any pollution control equipment
None.
Q9. Please include Annual Emission Rates calculation spreadsheet.
[Click here]
Q11. Contact Information: (person filling out form - signature will be required)
Name Ulysses Davis
Title Electronic Systems Analyst
Phone 801-524-5710
Date Sept 10, 2024
Q10. By signing below, I hereby certify that the information and data submitted in this notice fully describes
this site and ONLY this site. The information provide is true, accurate, and complete to the best of my
knowledge. I understand that I am responsible for determining whether the site remain eligible for this
exemption before making operational or process changes in the future, and agree to notify the Division of
Air Quality when this site is not longer eligible for this exemption. (Signature of Owner/Manager)
[Click here]
Embedded Data:
N/A