HomeMy WebLinkAboutDDW-2025-003664Sanitary Survey - Deficiency Report
PWS Number:UTAH23039 Deficiency Points:530 Survey Date:03/25/2025
Survey Name:US MAGNESIUM Surveyor:Chris Martin
Sanitary Survey Category: MR
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH23039 DISTRIBUTION SYSTEM
35. For a community water system or a non-transient non-community water system, did you make your initial service line inventory available to
the public? (if a transient system, enter NA)
Rule: 40 CFR 141.84 (a)(8)The rule requires that the service line materials inventory be publicly accessible.
(a)(8)(ii) The rule requires that water systems serving greater than 50,000 persons
make the publicly accessible inventory available online. (a)(9) The rule requires that
when a water system has no lead, galvanized requiring replacement, or lead status
unknown service lines (regardless of ownership) in its inventory, it may comply with
the requirements using a written statement, in lieu of the inventory, declaring that the
distribution system has no lead service lines or galvanized requiring replacement
service lines. The statement must include a general description of all applicable sources
used to make this determination.
Notes:System didn't provide any information related to this question.
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: R006 FAILURE TO MAKE THE LEAD SERVICE LINE INVENTORY PUBLICLY
ACCESSIBLE
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH23039 DISTRIBUTION SYSTEM
38. Documentation of personnel trained to manage the program (ALL COMUNITY WATER SYSTEMS REQUIRE A DDW CERTIFIED CCC
PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM BACKFLOW 101 OR EQUIVALENT/
GREATER CCC TRAINING)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes an operator with adequate training in the area of cross connection control
or backflow prevention.
Notes:Needs backflow 101 (https://deq.utah.gov/drinking-water/backflow-101)
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M005 CCC-LACKS OPERATOR TRAINING
Sanitary Survey Category: OC
SDWIS Severity Code: Significant Deficiency
Cross Connection and Operator Certification | DS001 | UTAH23039 DISTRIBUTION SYSTEM
41. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT )
Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that
utilize treatment/filtration to have at least one operator certified at the classified grade
of the water system. Certification must be appropriate for the type of system operated
(treatment and/or distribution). This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:Current operator needs T1 certification
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE
REQUIRED LEVEL
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | 150K DEMIN TANK
68. Roof or wall penetrations sealed
Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control
apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have
additional proper shielding to prevent vandalism. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:There are holes in the roof of the tank.
Deficiency Points: 100
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS
ON TANK ROOF OR SIDEWALLS
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | I MG TANK (RAW WATER)
79C. Vent covered with #14 or finer non-corrodible mesh screen.
Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-
corrodible screen and vents 6-inches or greater in diameter to be fitted with additional
heavy gauge screen or substantial covering to protect the #14 mesh screen from
vandalism or damage. This significant deficiency must be corrected within 120 days of
notification or have a compliance action plan approved by DDW.
Notes:Screen looks damaged from distance.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | I MG TANK (RAW WATER)
80C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Bolted lid does not appear to have a gasket.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | I MG TANK (RAW WATER)
82. Roof or wall penetrations sealed
Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control
apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have
additional proper shielding to prevent vandalism. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:There is signs of leakage along the bottom of the tank.
Deficiency Points: 100
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS
ON TANK ROOF OR SIDEWALLS
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | I MG TANK (RAW WATER)
83. Area surrounding ground-level or buried storage tank is graded to prevent surface water from standing within 50 feet.
Rule: R309-545-7(4)Rule requires the area surrounding a ground-level or buried water storage tank be
graded in a manner to prevent surface water from standing within 50 feet of the tank.
This significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Surface water is ponded around the tank.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V001 STORAGE TANK SURROUNDING AREA NOT GRADED TO PREVENT STANDING
WATER WITHIN 50 FEET OF THE TANK
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER)
94C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:There is no gasket on the lid.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER)
95. Access opening locked
Rule: R309-545-14(3)Rule requires the lid to any access opening to have a locking device. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:This is a bolted tank lid but it is currently unbolted.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER)
96. Roof or wall penetrations sealed
Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control
apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have
additional proper shielding to prevent vandalism. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:There is corrosion near the tank vent with apparent holes.
Deficiency Points: 100
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS
ON TANK ROOF OR SIDEWALLS
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER)
100B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:There is a hole in the screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP004 | US MAGNESIUM RO AND CHLORINATOR
155. If continuous disinfection is needed, automatic switch over of chlorine cylinders is provided.
Rule: R309-520-7(2)(a), R309-520-6(1)Rule requires automatic switch over of chlorine cylinders be provided if continuous
disinfection is required.
Notes:Still deficient.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD01 CONTINUOUS DISINFECTION IS REQUIRED BUT CHLORINATOR LACKS
AUTOMATIC SWITCHOVER