HomeMy WebLinkAboutDERR-2025-002971Facility Name:6090 Inspection Time Start/Finish:2024-01-04 10:06:58 2024-01-04 11:34:51 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.56266983333333, -112.1442075 Designated Operator:7G Environmental Compliance GPS End 41.56252690129127, -112.14448065507425 Work Order No.n/a Inspector:James Calamese Facility Rep:Brent Hansen Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X WO 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X DSL2 Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 07 Testing document printed out, please stop following binder 28 Waste oil bucket contains liquid [: WO] [: pcw] 33 DSLmiddle interstitial gauge 1/4 full of liquid [product: DSL2] Items Requiring Follow-Up Actions: #Priority Info 28 None spill bucket - [: WO] - bucket - contains - [: pcw] 33 2 spill bucket - [product: DSL2] - bucket - interstitial - present - liquid Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-02-02 19:31:58 2024-02-02 19:44:10 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.56254294145946, -112.14424204219061 Designated Operator:7G Environmental Compliance GPS End 41.56255403545283, -112.14427873351865 Work Order No.n/a Inspector:James Calamese Facility Rep:6090 Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X DSL2 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X NO 28.Spill buckets are free of damage and liquid/debris upon arrival X DSL, DSL2, DSL3 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 02 L2 DSL middle stp sump contains liquid below the boots [: TLS-450+] [alarm list: Fuel Alarm] 14 DSL2 middle STP sump contains liquid below the boots [product: DSL2] [liquid amounts: below boots] 27 New oil spill bucket lid missing [product: NO] 28 DSL spill bucket contains liquid [: DSL] 28 DSL2 spill bucket contains liquid [: DSL2] 28 DSL3 spill bucket contains liquid [: DSL3] [: pcw] Items Requiring Follow-Up Actions: #Priority Info 02 1 atg - [: TLS-450+] - alarm - present - [alarm list: Fuel Alarm] 14 2 stp sump - [product: DSL2] - sump - present - liquid - [liquid amounts: below boots] 27 2 spill bucket - [product: NO] - cover - not present 28 None spill bucket - [: DSL] - bucket - contains 28 None spill bucket - [: DSL2] - bucket - contains 28 None spill bucket - [: DSL3] - bucket - contains - [: pcw] Memo: Manager unavailable at time of completed inspection Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-02-29 18:41:14 2024-02-29 19:54:23 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.56248763376526, -112.14410826680474 Designated Operator:7G Environmental Compliance GPS End 41.56262732449936, -112.14466858472562 Work Order No.n/a Inspector:James Calamese Facility Rep:Elaine Schmier Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X WO, DSL, DSL2 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X RUL1 28.Spill buckets are free of damage and liquid/debris upon arrival X NO 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 02 Dsl2 and waste oil stp sump fuel alarms active [: TLS-450+] [alarm list: Fuel Alarm] 14 waste oil stp sump contains liquid above the boots [product: WO] [liquid amounts: above boots] 14 RUL1 STP sump contains liquid [product: DSL] [liquid amounts: Trace Amount] 14 DSL2 STP sump contains liquid below the boots [product: DSL2] [liquid amounts: below boots] 27 New oil spill bucket cover nont secured [product: RUL1] 28 New oil spill bucket full of liquid [: NO] [: pcw] Items Requiring Follow-Up Actions: #Priority Info 02 1 atg - [: TLS-450+] - alarm - present - [alarm list: Fuel Alarm] 14 2 stp sump - [product: WO] - sump - present - liquid - [liquid amounts: above boots] 14 2 stp sump - [product: DSL] - sump - present - liquid - [liquid amounts: Trace Amount] 14 2 stp sump - [product: DSL2] - sump - present - liquid - [liquid amounts: below boots] 27 2 spill bucket - [product: RUL1] - cover - damaged 28 None spill bucket - [: NO] - bucket - contains - [: pcw] Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-03-28 20:56:13 2024-03-28 21:42:48 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.562503883422956, -112.14422752009187 Designated Operator:7G Environmental Compliance GPS End 41.562526192263135, -112.14446593557243 Work Order No.n/a Inspector:James Calamese Facility Rep:Elaine Schmire Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X DSL, DSL2 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X NO, WO 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 02 L2 fuel alarm DSL2 sump alarm active contains liquid [: Other] [alarm list: Fuel Alarm] 14 DSL1 STP sump contains liquid below the boots [product: DSL] 14 DSL2 stp sump contains liquid below the boots [product: DSL2] [liquid amounts: below boots] 28 New Oil spill bucket contains liquid [: NO] [: pcw] 28 Waste oil spill bucket contains liquid [: WO] Items Requiring Follow-Up Actions: #Priority Info 02 1 atg - [: Other] - alarm - present - [alarm list: Fuel Alarm] 14 2 stp sump - [product: DSL] - sump - present - liquid 14 2 stp sump - [product: DSL2] - sump - present - liquid - [liquid amounts: below boots] 28 None spill bucket - [: NO] - bucket - contains - [: pcw] 28 None spill bucket - [: WO] - bucket - contains Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-04-25 21:06:08 2024-04-25 21:41:05 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.562392783333344, -112.14489028333334 Designated Operator:7G Environmental Compliance GPS End 41.56251773275436, -112.14423499834717 Work Order No.n/a Inspector:James Calamese Facility Rep:Elaine Schmier Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X DSL, DSL2 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X NO, DSL 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X Satellite 2 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 14 DSL1 STP sump contains liquid below the boots [product: DSL] 14 DSL2 stp sump contains liquid below the boots [product: DSL2] [liquid amounts: below boots] 28 New oil spill bucket contains liquid [: NO] [: pcw] 28 DSL 1 spil bucket contains liquid [: DSL] 37 Dispenser 2 satellite nozzle sleeve missing [dc pump list: Satellite 2] Items Requiring Follow-Up Actions: #Priority Info 14 2 stp sump - [product: DSL] - sump - present - liquid 14 2 stp sump - [product: DSL2] - sump - present - liquid - [liquid amounts: below boots] 28 None spill bucket - [: NO] - bucket - contains - [: pcw] 28 None spill bucket - [: DSL] - bucket - contains 37 2 dispenser - [dc pump list: Satellite 2] - nozzle - damaged Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-05-23 20:28:28 2024-05-23 20:39:35 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.562515725407394, -112.1442568369604 Designated Operator:7G Environmental Compliance GPS End 41.56164727731501, -112.14452055045047 Work Order No.n/a Inspector:James Calamese Facility Rep:Elaine Schmier Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X RUL2 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X RUL1 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X WO 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 12 DSL2 inner sump lid stuck closed [product: RUL2] 14 RUL1 stp sump contains liquid below the boots [product: RUL1] [liquid amounts: below boots] 28 New oil spill bucket contains liquid [: WO] [: pcw] Items Requiring Follow-Up Actions: #Priority Info 12 2 stp sump - [product: RUL2] - inner lid - damaged 14 2 stp sump - [product: RUL1] - sump - present - liquid - [liquid amounts: below boots] 28 None spill bucket - [: WO] - bucket - contains - [: pcw] Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-06-21 17:05:50 2024-06-21 17:40:39 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.562539359411154, -112.14418848229576 Designated Operator:7G Environmental Compliance GPS End 41.562364921012694, -112.14483026425553 Work Order No.n/a Inspector:James Calamese Facility Rep:Jeremiah Moss Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X NO, WO, DSL, DSL2 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 06 Can you pick it up financial responsibility on file and binder 28 New oil spill bucket contains liquid [: NO] 28 Waste oil spill bucket contains liquid [: WO] [: pcw] 28 DSL spillbucket contains liquid [: DSL] 28 DSL2 spill bucket contains liquid [: DSL2] 50 Notified manager of missing certificate of financial responsibility Items Requiring Follow-Up Actions: #Priority Info 06 None records - certificate - financial responsibility - expired 28 None spill bucket - [: NO] - bucket - contains 28 None spill bucket - [: WO] - bucket - contains - [: pcw] 28 None spill bucket - [: DSL] - bucket - contains 28 None spill bucket - [: DSL2] - bucket - contains Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-07-18 14:55:10 2024-07-18 15:42:51 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.562509666666664, -112.1442 Designated Operator:7G Environmental Compliance GPS End 41.56246578488218, -112.1444142088903 Work Order No.n/a Inspector:James Calamese Facility Rep:Brent Hansen Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X NO, DSL2 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X DSL 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X DSL, DSL2 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X Master 2, Satellite 1, Satellite 2 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 12 New Oils inner sump lid handle damaged [product: NO] 12 DSL2 inner sump lid handle missing [product: DSL2] 20 DSL atg probe lid damaged [product: DSL] 28 DSL spill bucket contains liquid [: DSL] 28 DSL2 spill bucket contains liquid [: DSL2] [: pcw] 40 Dispenser 1 main udc contains liquid [dc pump list: Master 2] 40 Dispenser 1 satellite UDC contains trace amounts of liquid [dc pump list: Satellite 1] [liquid amounts: Trace Amount] 40 Dispenser 2 Satellite UDC contains liquid below the boots [dc pump list: Satellite 2] [liquid amounts: below boots] Items Requiring Follow-Up Actions: #Priority Info 12 2 stp sump - [product: NO] - inner lid - damaged 12 2 stp sump - [product: DSL2] - inner lid - damaged 20 2 tank probe - [product: DSL] - manhole cover - damaged 28 None spill bucket - [: DSL] - bucket - contains 28 None spill bucket - [: DSL2] - bucket - contains - [: pcw] 40 2 dispenser - [dc pump list: Master 2] - udc - udc - present - liquid 40 2 dispenser - [dc pump list: Satellite 1] - udc - udc - present - liquid - [liquid amounts: Trace Amount] 40 2 dispenser - [dc pump list: Satellite 2] - udc - udc - present - liquid - [liquid amounts: below boots] Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-08-16 13:56:08 2024-08-16 14:49:36 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.56252566666667, -112.14422466666667 Designated Operator:7G Environmental Compliance GPS End 41.562409366557205, -112.14453203120222 Work Order No.n/a Inspector:James Calamese Facility Rep:Elaine Schmier Phone:805-286-5270 Signature:Signature: ATG Y N NA 02.ATG is free of CURRENT priority alarms X 03.Sensor status, alarm status, and summary status reports printed and filed.X 05.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X DSL2 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 05.Current UST permit/registration is present (where applicable)X 06.Current Certificate of Financial Responsibility is present X 07.UST System Test Report is available with passing tests within past 365 days X 08.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 09.Class A/B Operator Training Certificates are current and filed X 10.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X DSL, DSL2, DSL3 28.Spill buckets are free of damage and liquid/debris upon arrival X 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 45.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 46.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 47.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 05 Utah USt Certificate of registration on file expired 12 DSL2 inner sump lid handle damaged [product: DSL2] 27 DSL1 spillbucket lid painted by 7g inspector [product: DSL] 27 DSL2 spillbucket lid painted by 7g inspector [product: DSL2] 27 spillbucket lid painted by 7g inspector [product: DSL3] Items Requiring Follow-Up Actions: #Priority Info 05 None records - permit - not present 12 2 stp sump - [product: DSL2] - inner lid - damaged Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-09-12 17:25:49 2024-09-12 17:57:10 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.56256115431489, -112.14410811733148 Designated Operator:7G Environmental Compliance GPS End 41.562520326413654, -112.14410820036284 Work Order No.n/a Inspector:James Calamese Facility Rep:Jeremiah Moss Phone:805-286-5270 Signature:Signature: ATG Y N NA 01.ATG is powered on and is functional X 02.ATG printer has paper and is functional X 03.ATG is free of CURRENT priority alarms X 04.Sensor status, alarm status, and summary status reports printed and filed.X 07.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 06.Current UST permit/registration is present (where applicable)X 07.Current Certificate of Financial Responsibility is present X 08.UST System Test Report is available with passing tests within past 365 days X 09.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 10.Class A/B Operator Training Certificates are current and filed X 11.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 32.Spill bucket fill caps are present, seal tightly, and free of damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 43.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 44.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 45.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment Items Requiring Follow-Up Actions: #Priority Info Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-10-11 14:58:55 2024-10-11 15:44:31 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.5625523619857, -112.14422410620875 Designated Operator:7G Environmental Compliance GPS End 41.56255537459161, -112.14444433543262 Work Order No.n/a Inspector:James Calamese Facility Rep:Jeremiah Moss Phone:805-286-5270 Signature:Signature: ATG Y N NA 01.ATG is powered on and is functional X 02.ATG printer has paper and is functional X 03.ATG is free of CURRENT priority alarms X 04.Sensor status, alarm status, and summary status reports printed and filed.X 07.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X DSL2, DSL3 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 06.Current UST permit/registration is present (where applicable)X 07.Current Certificate of Financial Responsibility is present X 08.UST System Test Report is available with passing tests within past 365 days X 09.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 10.Class A/B Operator Training Certificates are current and filed X 11.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X DSL 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X NO, DSL 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 32.Spill bucket fill caps are present, seal tightly, and free of damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 43.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 44.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 45.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 06 Certificate of registration on file expired 12 DSL2 inner sump lid handle broken [product: DSL2] 12 DSL3 inner sump knob bolts damaged and missing [product: DSL3] [lid closure parts: knobs] 20 DSL1 Probe lid cracked [product: DSL] 28 New oil spillbucket contains liquid [: NO] [: pcw] 28 DSL3 spillbucket drain valve damaged [: DSL] [: other] Items Requiring Follow-Up Actions: #Priority Info 06 None records - permit - not present 12 2 stp sump - [product: DSL2] - inner lid - damaged 12 2 stp sump - [product: DSL3] - inner lid - lid closure - damaged - [lid closure parts: knobs] 20 2 tank probe - [product: DSL] - manhole cover - damaged 28 None spill bucket - [: NO] - bucket - contains - [: pcw] 28 2 spill bucket - [: DSL] - bucket - floor - damaged - [: other] Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-11-07 17:59:57 2024-11-07 18:12:39 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.56250243589414, -112.14426944055342 Designated Operator:7G Environmental Compliance GPS End 41.562798139481295, -112.14450779461518 Work Order No.n/a Inspector:James Calamese Facility Rep:Jeremiah Moss Phone:805-286-5270 Signature:Signature: ATG Y N NA 01.ATG is powered on and is functional X 02.ATG printer has paper and is functional X 03.ATG is free of CURRENT priority alarms X 04.Sensor status, alarm status, and summary status reports printed and filed.X 07.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 06.Current UST permit/registration is present (where applicable)X 07.Current Certificate of Financial Responsibility is present X 08.UST System Test Report is available with passing tests within past 365 days X 09.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 10.Class A/B Operator Training Certificates are current and filed X 11.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X WO, DSL, DSL2 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 32.Spill bucket fill caps are present, seal tightly, and free of damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X Satellite 1 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 43.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 44.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 45.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 28 New oil spill bucket contains liquid [: WO] [: pcw] 28 DSL1 Spillbucket contains liquid [: DSL] 28 DSL2 spillbucket contains liquid [: DSL2] 40 Dispenser 1 satellite UDC contains liquid below the boots [dc pump list: Satellite 1] [liquid amounts: below boots] Items Requiring Follow-Up Actions: #Priority Info 28 None spill bucket - [: WO] - bucket - contains - [: pcw] 28 None spill bucket - [: DSL] - bucket - contains 28 None spill bucket - [: DSL2] - bucket - contains 40 2 dispenser - [dc pump list: Satellite 1] - udc - udc - present - liquid - [liquid amounts: below boots] Memo: Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619 Facility Name:6090 Inspection Time Start/Finish:2024-12-05 19:00:35 2024-12-05 19:54:55 Facility Address:5400 W. HIGHWAY 83, Corinne, UT GPS Start 41.562493740773206, -112.14410825458188 Designated Operator:7G Environmental Compliance GPS End 41.56249416666667, -112.14423249999999 Work Order No.n/a Inspector:James Calamese Facility Rep:Na Phone:805-286-5270 Signature:Signature: ATG Y N NA 01.ATG is powered on and is functional X 02.ATG printer has paper and is functional X 03.ATG is free of CURRENT priority alarms X 04.Sensor status, alarm status, and summary status reports printed and filed.X 07.ATG shows no more than .25" of water present in the tank X STP Containment Sump Y N NA Product 04.All outer lid gaskets securely in place X 12.STP Sump Inner Lids, Closing Hardware, and Labeling are Present, Free of Damage, and/or Seal Tightly X 13.STP Sumps Are Free of Damage X 14.STP Sumps are free of liquid/debris.X DSL2 15.STP Components (piping, leak detectors, flex connectors, entry boots) are free of damage, leaks and corrosion X 17.STP Sump Piping Interstices Communication Are Open (except MD)X 18.STP Sump Sensors are positioned properly in the lowest part of the sump and below the piping entry X Recordkeeping / Document Retention Y N NA 06.Current UST permit/registration is present (where applicable)X 07.Current Certificate of Financial Responsibility is present X 08.UST System Test Report is available with passing tests within past 365 days X 09.Last month's DO Inspections Present with Sensor/Liquid Status Report X Training Y N NA 10.Class A/B Operator Training Certificates are current and filed X 11.Was C Training Conducted? If yes, provide number of C operators trained.X Safety Y N NA 13.Safety work area around tank pad properly secured X Monitoring Wells Y N NA 19.Monitoring Well cover and/or well cap is secured, properly identified, and free of damage X Tank Probes Y N NA Product 20.Tank Probe Port Lids are Free of Damage X 21.Tank Probe Caps Are Secure and Free of Damage X Vapor Recovery Y N NA 22.Vapor Recovery Bucket Lids Are Present, Seal Tightly, and API Compliant X 23.Vapor Recovery Buckets are Free of Damage and Liquid/Debris upon arrival X 25.Vapor Recovery Bucket Caps are Present, Free of Damage, and Seal Tightly X 26.Vapor Recovery Poppet Valves Are Free of Damage and Seal Tightly X Spill Buckets Y N NA Product 27.Spill Bucket Lids Are Present, Seal tightly, and have proper API color coding.X 28.Spill buckets are free of damage and liquid/debris upon arrival X 30.Fill adaptors are tight on the riser pipe X 31.Flapper valves are free of obstruction or damage X 32.Spill bucket fill caps are present, seal tightly, and free of damage X 33.Spill bucket interstices are free of liquid and visi-gauge is free of damage X Dispensers Y N NA Dispensers 37.Hanging Hardware (Hoses, Hose Breakaway Connectors, Nozzles) are Free of Damage and Leaks X 38.UDC Hardware (meters, piping, filters or flex connectors) Are Free of Leaks X 39.Shear valves are properly anchored and set X 40.UDCs are free of damage (cracks, bulges and other defects) and liquid/debris upon arrival X Master 2, Satellite 1 41.UDC entry boots are free of damage X 42.UDC piping interstice are open to UDC Upon Arrival (except MD)X 43.UDC Sensor Properly Mounted at Bottom of Sump X Tank Vents Y N NA 43.Vent caps and piping are present, properly identified, and free of damage X Emergency Response Y N NA 44.Kiosk Emergency Shutoff Is Free of Damage and Unobstructed X 45.Fuel Island Emergency Shutoff Is Free of Damage and Unobstructed X 48.Undercounter emergency shutoff is free of damage and unobstructed.X Additional Info Y N NA 49.Did you complete any state forms?X 50.Was management notified about items that can be corrected? (caps, lids, documents, etc.)X Visual Inspection Report Regulatory ID: 100619 Comments: #Comment 02 Printer out of paper 14 DSL2 sump stp sump contains liquid [product: DSL2] [liquid amounts: below boots] 40 Dispenser 2 UDC contains liquid [dc pump list: Master 2] 40 Dispenser 1 satellite udc contains liquid [dc pump list: Satellite 1] [liquid amounts: Trace Amount] Items Requiring Follow-Up Actions: #Priority Info 02 None atg - printer - not functioning 14 2 stp sump - [product: DSL2] - sump - present - liquid - [liquid amounts: below boots] 40 2 dispenser - [dc pump list: Master 2] - udc - udc - present - liquid 40 2 dispenser - [dc pump list: Satellite 1] - udc - udc - present - liquid - [liquid amounts: Trace Amount] Memo: Manager unavailable to sign completed inspection Visual Inspection Report Regulatory ID: 100619 Photos: Visual Inspection Report Regulatory ID: 100619