Loading...
HomeMy WebLinkAboutDERR-2025-002945Wheeler Tank Testing LLC P.O. Box 1008 Blackfoot, ID 83221 Piping Sump and UDC Integrity Test Form Century Link 673090 70 South State Salt Lake City, UT UT Kevin Wheeler UT-0233 3/20/26 Wheeler Tank Testing 208-221-1662 WTTI Vacuum Spill Containment Tester OPW OPW OPW Single Wall Single Wall Single Wall 11.5" 11.5" 11.5" 13" 13" 13" 5 gal 5 gal 5 gal Vacuum Vacuum Vacuum 1229 1143 1053 33.6 in WC 34.0 in WC 32.4 in WC 1230 1144 1054 33.0 in WC 33.9 in WC 30.4 in WC 1 Min 1 Min 1 Min -0.6 in WC -0.1 in WC -2.0 in WC ->3.9 in WC ->3.9 in WC ->3.9 in WC All Containments pass testing. Next testing due in 2028. Kevin Wheeler Digitally signed by Kevin Wheeler DN: cn=Kevin Wheeler, o=Wheeler Tank Testing, ou, email=wheelertanktesting.inc@gmail.com, c=US Date: 2025.03.26 11:39:28 -06'00'3/24/25 Used Oil North DSL South DSL North DSL South DSL Used Oil Facility Name: Owner: Address: Address: City, State, Zip Code: City, State, Zip Code: Facility I.D. #: Phone #: Testing Company: Phone #: Date: This procedure is to determine whether liquid sensors located in the interstitial space of UST systems are able to detect the presence of water and fuel. See PEI/RP1200 Section 8.3 for the test procedure. Sensor Location Product Stored Type of Sensor Discriminating Non-discrimi- nating Discriminating Non-discrimi- nating Discriminating Non-discrimi- nating Discriminating Non-discrimi- nating Discriminating Non-discrimi- nating Discriminating Non-discrimi- nating Discriminating Non-discrimi- nating Test Liquid Water Product Water Product Water Product Water Product Water Product Water Product Water Product Is the ATG console clear of any active or recurring warnings or alarms regarding the leak sensor? If the sensor is in alarm and functioning, indicate why. Yes No Yes No Yes No Yes No Yes No Yes No Yes No Is the sensor alarm circuit operational? Yes No Yes No Yes No Yes No Yes No Yes No Yes No Has sensor been inspected and in good operating condition? Yes No Yes No Yes No Yes No Yes No Yes No Yes No When placed in the test liquid, does the sensor trigger an alarm? Yes No Yes No Yes No Yes No Yes No Yes No Yes No When an alarm is triggered, is the sensor properly identified on the ATG console? Yes No Yes No Yes No Yes No Yes No Yes No Yes No Any “No” answers indicates the sensor fails the test. Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Tester’s Name (print) ___________________________________ Tester’s Signature _______________________________________________