HomeMy WebLinkAboutDERR-2025-002933 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRODUCT PIPING INTEGRITY TESTING
Facility Name: Salt Palace Owner: Salt Lake County Fleet Management
Address: 100 South West Temple Address: 7125 South 600 West
City, State, Zip: Salt Lake City, Utah 84101 City, State, Zip: Midvale, Utah 84047
Facility I.D.#: 4000892 Phone #: 385-468-0475
Testing Company: Westech Phone #: 801-266-2545 Date: 4/3/25
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1
Product Stored DSL
Piping Run Supply
Piping Type FRP
Test Pressure (PSI) 50
Test Duration (minutes) 30
Leak Rate (GPH) 0.003
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
Diesel
Su
p
p
l
y
(
2
"
F
R
P
p
r
i
m
a
r
y
,
3"
F
R
P
s
e
c
o
n
d
a
r
y
)
Re
t
u
r
n
(
2
"
F
R
P
p
r
i
m
a
r
y
,
3"
F
R
P
s
e
c
o
n
d
a
r
y
)
Tunnel Wall
Secondary ends and
is sealed to primary
Sump Sensor
Fill
STP
Interstitial Sensor ATG
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: Salt Palace Owner: Salt Lake County Fleet Management
Address: 100 South West Temple Address: 7125 South 600 West
City, State, Zip: Salt Lake City, Utah 84101 City, State, Zip: Midvale, Utah 84047
Facility I.D.#: 4000892 Phone #: 385-468-0475
Testing Company: Westech Phone #: 801-266-2545 Date: 4/3/25
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the in spection
procedure. This procedure is applicable to tank monitor stems the touch the bottom of the tank when in place.
Tank Number 1
Product Stored DSL
ATG Brand and Model TLS 350
1. Tank Volume, gallons 11,527
2. Tank Diameter, inches 89.75
3. After removing the ATG from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. Float moves freely on the stem without binding? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
5. Fuel float level agree with the value programmed
into the console? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
6. Water float level agree with the value programmed
into the console? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
7. Inch level from the bottom of the stem when 90%
alarm is triggered? 75
8. Inch level at which the overfill alarm activates
corresponds with the value programmed in the
gauge?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
9. Inch level from the bottom when the water float
first triggers an alarm? 1
10. Inch level at which the water float alarm activates
corresponds with the value programmed in the
gauge?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test.
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments: Battery OK
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: Salt Palace Owner: Salt Lake County Fleet Management
Address: 100 South West Temple Address: 7125 South 600 West
City, State, Zip: Salt Lake City, Utah 84101 City, State, Zip: Midvale, Utah 84047
Facility I.D.#: 4000892 Phone #: 385-468-0475
Testing Company: Westech Phone #: 801-266-2545 Date: 4/3/25
This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to detect the presence of water and fuel. See
PEI/RP1200, Section 8.3 for the test procedure.
Sensor Location L-1 STP L-2 INT
Product Stored DSL DSL
Type of Sensor
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
Test Liquid ☒ Water
☐ Product
☒ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm
and functioning, indicate why.
☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Is sensor alarm circuit
operational? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Has sensor been inspected and in good
operating condition? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
When placed in test liquid, does the
sensor trigger an alarm? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
When alarm is trigger, is the sensor
identified on the ATG console? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail
Comments:
Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
CONTAINMENT SUMP INTEGRITY TESTING
HYDROSTATIC TESTING METHOD
Facility Name: Salt Palace Owner: Salt Lake County Fleet Management
Address: 100 South West Temple Address: 7125 South 600 West
City, State, Zip: Salt Lake City, Utah 84101 City, State, Zip: Midvale, Utah 84047
Facility I.D.#: 4000892 Phone #: 385-468-0475
Testing Company: Westech Phone #: 801-266-2545 Date: 4/3/25
This procedure is to test the leak integrity of containment sumps. See PEI/RP1200 Section 6.5 for the inspection procedure.
Containment Sump ID STP
Containment Sump Material FRP
Liquid and debris removed from sump?* ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Visual Inspection (No cracks, loose parts or separation of
the containment sump.) ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Containment Sump Depth 24 1/2”
Height From Bottom to Top of Highest Penetration 11”
Starting Water Level 15 1/8”
Test Start Time 12:40
Ending Water Level 15 1/8”
Test End Time 1:40
Test Period (Minimum test time: 1 hour) 1 Hour
Water Level change 0”
Pass/fail Criteria: Must pass visual inspection. Water level drop of less than 1/8 inch.
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
*All Liquids and debris must be disposed of properly.
Tester’s Name Taber DeHart UT-0394 Tester’s Signature