HomeMy WebLinkAboutDAQ-2025-000188
Small Source Registration
DAQE-EN162420001-25
{{$d1 }}
Corey Bailey
Amazon.com Services, LLC
P.O. Box 80842
Seattle, WA 98108
amazon-eap-northamerica@amazon.com
Dear Corey Bailey:
Re: Request for Evaluation of Compliance with Rule R307-401-9, UAC: Small Source Exemption
Project Fee Code: N162420001
On December 19, 2024, the Division of Air Quality (DAQ) received your request for a small source
exemption for the Amazon.com Services LLC diesel-fired, 389-horsepower emergency generator. The source is located at 346 East 1600 South in American Fork, Utah County. DAQ has determined the small
source exemption applies to the source, as long as the equipment and associated processes operate as
specified in the registration request.
The small source exemption does not exempt a source from complying with other applicable federal,
state, and local regulations and the current Utah Administrative Code. Based on the emissions that you
submitted to DAQ with your registration request, the Amazon.com Services LLC American Fork
emergency generator is not required to obtain an approval order under R307-401. If you change your
operation such that there is an increase in emissions, we recommend that you notify us, as an approval
order may be required.
As authorized by the Utah Legislature, the fee for issuing this small source exemption is a one-time filing
fee in addition to the actual time spent by the review engineer and all other staff on the project. Payment
should be sent to DAQ upon receipt of the invoice.
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144820 • Salt Lake City, UT 84114-4820
Telephone (801) 536-4000 • Fax (801) 536-4099 • T.D.D. (801) 903-3978
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF AIR QUALITY
Bryce C. Bird
Director
+ 2 / 6 à Û Ù Û Þ
DAQE-EN162420001-25
Page 2
Thank you for registering your source with the DAQ. If you have any additional questions, please contact
Christine Bodell at (385) 290-2690 or cbodell@utah.gov.
Sincerely,
Bryce C. Bird
Director
{{$s }}
Alan D. Humpherys, Manager
New Source Review Section
BCB:ADH:CB:jg
{{#d1=date1_es_:signer1:date:format(date, "mmmm d, yyyy")}} {{#s=Sig_es_:signer1:signature}}
Response Summary:
To be eligible businesses shall not do any of the follow:
1) Emit more than 5 tons per year of each of the following pollutants: Sulfur Dioxide (SO2), Carbon Monoxide (CO),
Nitrogen Oxides (NOx), Particulate Matter (PM10), Ozone (O3), or Volatile Organic Compounds (VOCs).
2) Emit more than 500 lbs/yr of any single Hazardous Air Pollutant (HAP), and emit more than 2000 lbs/yr of any
combination of HAPs
3) Emit more than 500 lbs/yr of any combination of air contaminants not listed in 1 or 2
A copy of this registration notice and worksheets are required on site to verify permit exemption status.
Please be aware a the Small Source Exemption ONLY exempts the site from the air permitting requirements of R307-
401-5 thru R307-401-8 of the Utah Administrative Code, all other air quality regulations still apply.
Q4.
Please fill out the following contact information:
Site Contact Site Owner
Name Corey Bailey Amazon.com Services LLC
- SUT2 Amazon.com Services LLC
Mailing Address PO Box 80842 346 East 1600 South PO Box 80842
Mailing Address 2 N/A N/A N/A
City Seattle American Fork Seattle
State WA UT WA
Zip Code 98108 84003 98108
Phone 1(800) 575-0171 1(800) 575-0171 1(800) 575-0171
Fax N/A N/A N/A
Email amazon-eap-
northamerica@amazon.com
amazon-eap-
northamerica@amazon.com
amazon-eap-
northamerica@amazon.com
Q5. County the Site is located in:
Utah County
Q6. Briefly describe the process including the end products, raw materials, and process equipment used.
General warehousing and storage facility with one diesel-fueled emergency generator
engine. No processing equipment or activities take place onsite.
Q7. List emission units
One diesel-fueled emergency generator engine (Generac/SD200).
Q8. List any pollution control equipment
N/A
Q9. Please include Annual Emission Rates calculation spreadsheet.
[Click here]
Q11. Contact Information: (person filling out form - signature will be required)
Name Mark Tanner
Title Business Environmental Leader
Phone 1(800) 575-0171
Date 12/19/2024
Q10. By signing below, I hereby certify that the information and data submitted in this notice fully describes
this site and ONLY this site. The information provide is true, accurate, and complete to the best of my
knowledge. I understand that I am responsible for determining whether the site remain eligible for this
exemption before making operational or process changes in the future, and agree to notify the Division of
Air Quality when this site is not longer eligible for this exemption. (Signature of Owner/Manager)
[Click here]
Embedded Data:
N/A
Internal Combustion Engines
Description Make/Model # Serial Number Date
Manufactured Date Installed Fuel Type KW HP
(Max Rating)Fuel Consumption (gal/hr)Engine Operator Engine Owner
Emergency Generator Generac / SD200 3014870030 2024 2024 Diesel 200 389 19.1 Amazon Amazon
AE3 FACILITY EMISSION CALCULATIONS
Emissions Calculations
Diesel‐Fired Internal Combustion Engines, up to 600 HP
Name Plate Power Rating (hp) 389
Name Plate Power Rating (kw) 200
Fuel Consumption Rate (gal/hr): 19
Heat Input Capacity (MMBtu/hr): 2.62
Annual Operating Hours (hours/year): 500
Hourly Emissions Annual
Emissions
Value Units Value Units (lb/hr)(ton/yr)
NOx 3.36 g/kw‐hr 1 7.41E‐03 lb/kw‐hr 1.48 0.37
CO 0.50 g/kw‐hr 1 1.10E‐03 lb/kw‐hr 0.22 0.06
SO2 2.05E‐03 lb/hp‐hr 2 2.05E‐03 lb/hp‐hr 0.80 0.20
VOC 2.47E‐03 lb/hp‐hr 2 2.47E‐03 lb/hp‐hr 2 0.49 0.12
PM 0.07 g/kw‐hr 1 1.54E‐04 lb/kw‐hr 0.03 0.01
PM2.5 0.07 g/kw‐hr 1 1.54E‐04 lb/kw‐hr 0.03 0.01
PM10 0.07 g/kw‐hr 1 1.54E‐04 lb/kw‐hr 0.03 0.01
CH4 3.00E‐03 kg/MMBtu 3 6.60E‐03 lb/MMBtu 1.73E‐02 4.32E‐03
N2O 6.00E‐04 kg/MMBtu 3 1.32E‐03 lb/MMBtu 3.45E‐03 8.64E‐04
CO2 73.96 kg/MMBtu 4 1.63E+02 lb/MMBtu 4.26E+02 106.47
Acetaldehyde 7.67E‐04 lb/MMBtu5 7.67E‐04 lb/MMBtu 2.01E‐03 5.02E‐04
Benzene 9.33E‐04 lb/MMBtu 5 9.33E‐04 lb/MMBtu 2.44E‐03 6.10E‐04
Formaldehyde 1.18E‐03 lb/MMBtu5 1.18E‐03 lb/MMBtu 3.09E‐03 7.72E‐04
Naphthalene 8.48E‐05 lb/MMBtu5 8.48E‐05 lb/MMBtu 2.22E‐04 5.55E‐05
Toluene 4.09E‐04 lb/MMBtu 5 4.09E‐04 lb/MMBtu 1.07E‐03 2.68E‐04
Xylene 2.85E‐04 lb/MMBtu 5 2.85E‐04 lb/MMBtu 7.46E‐04 1.86E‐04
Total HAPs 3.66E‐03 lb/MMBtu 5 3.66E‐03 lb/MMBtu 9.58E‐03 2.39E‐03
1Emission factors from EPA certificate RFPXL08.7TR3‐002 provided in units of g/kw‐hr and converted to lb/kw‐hr by dividing by 453.59 g/lb.
Pollutant
NOx 0.37 0.37
CO 0.06 0.06
SO2 0.20 0.20
VOC 0.12 0.12
PM 0.01 0.01
PM2.5 0.01 0.01
PM10 0.01 0.01
CH4 4.32E‐03 4.32E‐03
N2O 8.64E‐04 8.64E‐04
CO2 1.06E+02 106.47
Acetaldehyde 5.02E‐04 5.02E‐04
Benzene 6.10E‐04 6.10E‐04
Formaldehyde 7.72E‐04 7.72E‐04
Naphthalene 5.55E‐05 5.55E‐05
Toluene 2.68E‐04 2.68E‐04
Xylene 1.86E‐04 1.86E‐04
Total HAPs 2.39E‐03 2.39E‐03
PERMITTING EVALUATION (UT DEQ Air Quality Rules R307)
Pollutant
UT DEQ* Major
Source Threshold
Potential to Emit
(tons/yr)1
UT DEQ* Small Source
Exemption Threshold
Actual Emissions
(tons/yr)2
Facility Potential to
Emit (tons/yr)
CO 100 5 0.06
NOx 100 5 0.37
SOx 100 5 0.20
PM 100 5 0.01
PM2.5 70 5 0.01
PM10 100 5 0.01
VOC 100 5 0.124
Single HAP 10 0.25 7.721E‐04
Total HAPs 25 1 2.394E‐03
* Utah Department of Environmental Quality
1 Major Source thresholds found in Utah Administrative Regulation R307‐415‐3(k)
2 Small Source Exemption thresholds found in Utah Administrative Rule R307‐401‐9. Note: Thresholds are based on actual emissions. The Facility potential to emit can conservativelly be used as the Faciliy actual emissions.
Diesel‐Fired Internal Combustion
Engines
Published Emission Factors Final Emission Factors
* This value is calculated using the Global Warming Potentials required under 40 CFR Part 98, as amended on 11/29/2013.
2Emission factors from AP‐42, Table 3.3‐1 provided in units of lb/hp‐hr.
3Emission factors from 40 CFR Part 98, Table C‐2 provided in units of kg/MMBtu and converted to lb/MMBtu by multiplying by 2.2 lb/kg.4Emission factor from 40 CFR Part 98, Table C‐1 provided in units of kg/MMBtu and converted to lb/MMBtu by multiplying by 2.2 lb/kg.
5Emission factors from AP‐42, Table 3.3‐2 for HAPs greater than 1x10‐5 lb/MMBtu.
Site‐Wide Emissions Inventory Diesel-Fired Internal CombustionEngines (Tons/Yr)
Site-Wide Potentialto Emit (Tons/Yr)