HomeMy WebLinkAboutDERR-2025-002812TODD KING
UTAH STATE FUEL NETWORK
4315 S 2700 W
SALT LAKE CITY, UT 84129
RE:Request for Petroleum Storage Tank Records
UDOT # 4468, located at 255 W CENTER ST, JUNCTION
Facility Identification No. 2000203
Dear TODD KING:
PST operators are required to ensure that certain tests are conducted for their tank system.
Dates highlighted in "Yellow" - tests are due soon.
Dates highlighted in "Red" - tests are due and you are out of compliance.
Tank ID/Alt
ID
Description LTT
--------------------
LLD
Spill Bucket
--------------------
Overfill
Tank or Flex
--------------------
Pipe CP
ATG
--------------------
Sump
1/1 Diesel-Diesel #2 (U.L.S.)-8000 3/12/2025 N/A N/A 3/12/2025
3/12/2025 N/A N/A N/A
4/4 Gasoline-Regular-6000 3/12/2025 N/A N/A 3/12/2025
3/12/2025 N/A N/A N/A
LTT - Line Tightness Test
LLD - Line Leak Detector
Overfill ±Overfill Device
Tank or Flex/Pipe CP - Corrosion Tests
ATG ±Automatic Tank Gauging
Sump - Tank Top Sump and applicable Dispenser Sumps
Please note that UDC tests are not listed, but are required on your facility's next sump test
cycle starting July 1, 2023, if applicable. Also, effective immediately pressure vent valves
must be tested every three years for gasoline tanks.
Please submit a copy of the required tests to the DERR within 30 days of the date due.
If you have any questions please call Sean Warner at 801-536-4100.
195 North 1950 West - Salt Lake City, UT
Mailing Address: - P.O. Box 144840 - Salt Lake City, UT 84114-4840
Telephone (801) 536-4100 - Fax (801) 359-8853 - T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
April 08, 2025
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Tim Davis
Executive Director
DIVISION OF ENVIRONMENTAL
RESPONSE AND REMEDIATION
Brent H. Everett
Director
APPLIED ENVIRONMENTAL SERVICES, L.C.
PO BOX 1073 BOUNTIFUL, UTAH 84011 801-540-9258
TEI 5000 NON VOLUMETRIC, TEI 4000 VOLUMETRIC, TEI ULLAGE, TEI LT3
PRECISION TANK & LINE TEST RESULTS SUMMARY
INVOICE ADDRESS:TANK LOCATION: WORK ORDER #
TECH # 94027
TECHNICIAN: SM
STATE TECH #
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
UTAH DOT # 4468
255 WEST CENTER
JUNCTION, UTAH
25024
UT 0121
DATE:
3-26-2025
TIME START:
12:00
TIME END:
17:00
GROUNDWATER DEPTH:
N/A DW TKS
TANK TANK
CAPACITY
7841
5998
PRODUCT
DSL
R/UL
TANK
PASS
PASS
VENT
PASS
PASS
PRODUCT
LINE
PASS
PASS
LINE LEAK
DETECTOR
PASS
PASS
WATER IN
TANK
0.0"
0.0"
PUMP
TYPE
PRESS
PRESS
TANK
MATERIAL
DWF
DWF
1.
2.
3.
4.
5.
6.
PRODUCT LINES TESTED AT 50 PSI FOR 15 MIN
LINE RATES (GPH)
1.
2.
3.
5.
6.
DSL -.007
R/UL -.004
ADDITIONAL INFORMATION:
CERTIFIED TECHNICIAN SIGNATURE:DATE:3-26-2025
These systems meet all requirements set forth by USEPA 40 CFR and has received third party certification.
4.
TEST METHODS USED FOR THIS LOCATION
TEI 5000 NON VOLUMETRIC TANK TEST TEI 4000 VOLUMETRIC TANK TEST TEI TANK ULLAGE TEST TEI LT3 LINE TESTX X
LINE LEAK DETECTOR TYPE & SIMULATED LEAK RATE
1.
2.
3.
M = MECHANICAL E = ELECTRONIC # = (GPH) RATE
4.
5.
6.
M 3
M 3
All tests were performed according to manufacturer protocol, and within the common practices of the industry. However due to the variables of
tightness testing, these results cannot be guaranteed. There are no warranties expressed, written or implied.
DEQ ID#2000203
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 15:15:56 -07'00'
Reason: I am the author of this document
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UT 84141-1152
(801) 619-7232
GAS STATION INSPECTION REPORT
Facility ID#
Facility Name and Site Address: Date:
Purpose:Regular______Reinspection_____Complaints______Annual Inspection ______
Nu
m
b
e
r
Te
s
t
e
d
Sa
t
i
s
f
i
e
d
Re
j
e
c
t
e
d
Ad
j
u
s
t
e
d
Pumps tested for calibration
Water tests/Fuel storage
Storage tanks properly labeled
Fill caps and underground storage covers-good
Fuel filters on pumps
Overfill prevention valves
Security seals intact
MOTOR FUEL PRODUCTS USED FOR INSPECTION
Regular_____ gallons Unleaded Regular_____ gallons Unleaded Plus_____ gallons
Unleaded Premium_____ gallons Diesel_____ gallons
Product was returned to fuel storage tanks.
Inspection Remarks:
Received by:Inspected by:Steven B. Martin UT0121
Applied Environmental Services L.C.
ACTION TAKEN
UTAH DOT # 4468
255 WEST CENTER
JUNCTION, UTAH
3-26-2025
2000203
X
XX
X
X
X
X
X
Dispenser Continuity Test
UTAH DOT # 4468
255 WEST CENTER
JUNCTION, UTAH
2000203
STATE FUEL NETWORK
APPLIED ENVIRONMENTAL SERVICES
PO BOX 141152
SALT LAKE CITY, UT
BRETT GURNEY 385-602-4872
801-540-9258 3-26-2025
1
DSL
RED J
FX2DV
X
24
10
50
1
9
1
X
X
X
X
2
R/UL
RED J
FX1
X
25
10
50
1
9
1
X
X
X
X
STEVEN B MARTIN
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 15:21:28 -07'00'
Reason: I am the author of this document
APPLIED ENVIRONMENTAL SERVICES, L.C.
PO BOX 1073 BOUNTIFUL, UTAH 84011 801-540-9258
Location: Test Date:
Technician:
Certification #
Pressure/Vacuum (P/V) Vent Valve Data Sheet
Steven B. Martin
UT 0121
TANK 1
P/V Valve Manufacturer:Model Number:Pass Fail
P/V Valve Manufacturer:
P/V Valve Manufacturer:
P/V Valve Manufacturer:
Model Number:
Model Number:
Model Number:Pass
Pass
Pass Fail
Fail
Fail
Comments:
Signature:
Manufacturers Specified
Positive Leak Rate (CFH)
Measured Positive Leak Rate (CFH)
Positive Cracking Pressure (in. H2O)
Manufacturers Specified
Positive Leak Rate (CFH)
Measured Positive Leak Rate (CFH)
Positive Cracking Pressure (in. H2O)
Manufacturers Specified
Positive Leak Rate (CFH)
Measured Positive Leak Rate (CFH)
Positive Cracking Pressure (in. H2O)
Manufacturers Specified
Positive Leak Rate (CFH)
Measured Positive Leak Rate (CFH)
Positive Cracking Pressure (in. H2O)
Manufacturers Specified
Negative Leak Rate (CFH)
Measured Negative Leak Rate (CFH)
Negative Cracking Pressure (in. H2O)
Manufacturers Specified
Negative Leak Rate (CFH)
Measured Negative Leak Rate (CFH)
Negative Cracking Pressure (in. H2O)
Manufacturers Specified
Negative Leak Rate (CFH)
Measured Negative Leak Rate (CFH)
Negative Cracking Pressure (in. H2O)
Manufacturers Specified
Negative Leak Rate (CFH)
Measured Negative Leak Rate (CFH)
Negative Cracking Pressure (in. H2O)
TANK 2
TANK 3
TANK 4
JUNCTION DOT 326
255 WEST CENTER
JUNCTION, UTAH
3-26-2025
OPW 623V X
2.5" to 6" wc
.03
4.11"
6" to 10" wc
.11
-8.2"
Product:
Product:
Product:
Product:
R/UL
TP-201.1E
<=0.05 cfh @ 2" wc <=0.21 cfh @ 4" wc
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 16:25:11 -07'00'
Reason: I am the author of this document
UTAH DOT # 326
255 WEST CENTER
JUNCTION, UTAH
2000203
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258 3-26-2025
AES UTAH 801-540-9258
DSL STP
FIBER
X
X
42
21
26. 1/2
14:00
15:00
1 HR
0
X
R/UL STP
FIBER
X
X
42
22
25 3/4
15:25
16:25
1 HR
0
X
SO DISP
PLASTIC
X
X
29
16
19
14:00
15:00
1 HR
0
X
NO DISP
PLASTIC
X
X
29
16
19
15:25
16:25
1 HR
0
X
UTAH TESTER UT 0121
STEVEN B MARTIN
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 15:32:57 -07'00'
Reason: I am the author of this document
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
Owner:
Address:
City, State, Zip Code:
Phone #
Testers Phone #
Date:
This procedure is to determine whether the ( ATG) is operating properly. See PEI/RP1200 Section 8.2 for the proper inspection procedure.
This procedure is applicable to tank level monitor stems that touch the botom of the tank when in place.
Tank Number
Product Stored:
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing
parts replaced?
4. Float moves freely on the stem without
5. Fuel float level agrees with the
value programmed into the console?
6. Water float level agrees with the value
programmed into the console?
7. Inch level from bottom of stem when 90%
alarm is triggered.
8. Inch level at which the overfill alarm
activates corresponds with value programmed
in the gauge?
9. Inch level from the bottom when the water
float first triggers an alarm.
10. Inch level at which the float alarm activates
corresponds with value programmed in the
gauge?
If any answers in Lines 3,4,5, or 6 are "NO" the system has failed the test.
TEST RESULTS
Comments:
Testers Name: Steven B. Martin Testers Signature:
UTAH DOT # 4468
255 WEST CENTER
JUNCTION, UTAH
2000203
APPLIED ENVIRONMENTAL, L.C.
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
3-26-2025
1
DSL
TLS-350
7841
90
YES
YES
YES
YES
75
YES
2.0
YES
2
R/UL
TLS-350
5998
90
YES
YES
YES
YES
75
YES
1.5
YES
PASS PASS
MONITOR BACKUP BATTERY FUNCTIONS PROPERLY, SETUP REPORT PRINTED
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 15:17:26 -07'00'
Reason: I am the author of this document