RE:Request for Petroleum Storage Tank Records
UTAH STATE ITS, located at 350 S 900 W, RICHFIELD
Facility Identification No. 2000689
Dear TODD KING:
PST operators are required to ensure that certain tests are conducted for their tank system.
Dates highlighted in "Yellow" - tests are due soon.
Dates highlighted in "Red" - tests are due and you are out of compliance.
Tank ID/Alt
ID
Description LTT
--------------------
LLD
Spill Bucket
--------------------
Overfill
Tank or Flex
--------------------
Pipe CP
ATG
--------------------
Sump
1/1 Diesel-Diesel #2 (U.L.S.)-12000 N/A N/A N/A 3/14/2025
N/A N/A N/A N/A
LTT - Line Tightness Test
LLD - Line Leak Detector
Overfill ±Overfill Device
Tank or Flex/Pipe CP - Corrosion Tests
ATG ±Automatic Tank Gauging
Sump - Tank Top Sump and applicable Dispenser Sumps
Please note that UDC tests are not listed, but are required on your facility's next sump test
cycle starting July 1, 2023, if applicable. Also, effective immediately pressure vent valves
must be tested every three years for gasoline tanks.
Please submit a copy of the required tests to the DERR within 30 days of the date due.
If you have any questions please call Sean Warner at 801-536-4100.
195 North 1950 West - Salt Lake City, UT
Mailing Address: - P.O. Box 144840 - Salt Lake City, UT 84114-4840
Telephone (801) 536-4100 - Fax (801) 359-8853 - T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
April 08, 2025
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Tim Davis
Executive Director
DIVISION OF ENVIRONMENTAL
RESPONSE AND REMEDIATION
Brent H. Everett
Director
APPLIED ENVIRONMENTAL SERVICES, L.C.
PO BOX 1073 BOUNTIFUL, UTAH 84011 801-540-9258
TEI 5000 NON VOLUMETRIC, TEI 4000 VOLUMETRIC, TEI ULLAGE, TEI LT3
PRECISION TANK & LINE TEST RESULTS SUMMARY
INVOICE ADDRESS:TANK LOCATION: WORK ORDER #
TECH # 94027
TECHNICIAN: SM
STATE TECH #
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
RICHFIELD DATA CENTER
350 SOUTH 900 WEST
RICHFIELD, UTAH
25022
UT 0121
DATE:
3-25-2025
TIME START:
09:30
TIME END:
11:00
GROUNDWATER DEPTH:
N/A DW TK
TANK TANK
CAPACITY
12031
PRODUCT
DSL
TANK
PASS
VENT
PASS
PRODUCT
LINE
PASS
LINE LEAK
DETECTOR
N/A
WATER IN
TANK
0.0"
PUMP
TYPE
SUCTION
TANK
MATERIAL
DWS1.
2.
3.
4.
5.
6.
PRODUCT LINES TESTED AT PSI FOR MIN
LINE RATES (GPH)
1.
2.
3.
5.
6.
ADDITIONAL INFORMATION:SUPPLY AND RETURN LINE TESTED WITH TANK
EMERGENCY GENERATOR TANK
CERTIFIED TECHNICIAN SIGNATURE:DATE:3-25-2025
These systems meet all requirements set forth by USEPA 40 CFR and has received third party certification.
4.
TEST METHODS USED FOR THIS LOCATION
TEI 5000 NON VOLUMETRIC TANK TEST TEI 4000 VOLUMETRIC TANK TEST TEI TANK ULLAGE TEST TEI LT3 LINE TESTX
LINE LEAK DETECTOR TYPE & SIMULATED LEAK RATE
1.
2.
3.
M = MECHANICAL E = ELECTRONIC # = (GPH) RATE
4.
5.
6.
All tests were performed according to manufacturer protocol, and within the common practices of the industry. However due to the variables of
tightness testing, these results cannot be guaranteed. There are no warranties expressed, written or implied.
DEQ ID#200689
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 14:44:09 -07'00'
Reason: I am the author of this document
RICHFIELD DATA CENTER
350 SOUTH 900 WEST
RICHFIELD, UTAH
200689
APPLIED ENVIRONMENTAL SERVICES
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258 3-25-2025
PIPING SMP
DSL
X
X
X
X
X
X
X
X
TK INTER
DSL
X
X
X
X
X
X
X
X
STEVEN B MARTIN
APPLIED ENVIRONMENTAL SERVICES, L.C. PO BOX 1073 BOUNTIFUL, UTAH 84011
801-540-9258 AESUTAH@AOL.COM
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 14:47:17 -07'00'
Reason: I am the author of this document
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
Owner:
Address:
City, State, Zip Code:
Phone #
Testers Phone #
Date:
This procedure is to determine whether the ( ATG) is operating properly. See PEI/RP1200 Section 8.2 for the proper inspection procedure.
This procedure is applicable to tank level monitor stems that touch the botom of the tank when in place.
Tank Number
Product Stored:
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing
parts replaced?
4. Float moves freely on the stem without
5. Fuel float level agrees with the
value programmed into the console?
6. Water float level agrees with the value
programmed into the console?
7. Inch level from bottom of stem when 90%
alarm is triggered.
8. Inch level at which the overfill alarm
activates corresponds with value programmed
in the gauge?
9. Inch level from the bottom when the water
float first triggers an alarm.
10. Inch level at which the float alarm activates
corresponds with value programmed in the
gauge?
If any answers in Lines 3,4,5, or 6 are "NO" the system has failed the test.
TEST RESULTS
Comments:
Testers Name: Steven B. Martin Testers Signature:
RICHFIELD - DTS SERVICE CENTER
350 SOUTH 900 WEST
RICHFIELD, UTAH
2000689
APPLIED ENVIRONMENTAL, L.C.
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
3-25-2025
1
DSL
TLS-350
12031
95.75
YES
YES
YES
YES
81
YES
2.0
YES
PASS
TANK MONITOR BACKUP BATTERY FUNCTIONS PROPERLY, SETUP REPORT PRINTED
BOTH SUMP SENSOR AND TANK INTERSTICIAL SENSORS FUNCTION PROPERLY
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.04.09 14:45:41 -07'00'
Reason: I am the author of this document