HomeMy WebLinkAboutDERR-2025-002703 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS
Facility Name: SALT LAKE CITY AIRPORT AUTHORITY Owner: AIRPORT NORTH SUPPORT
Address: PO BOX 145550 Address: 4000 WEST 1020 NORTH
City, State, Zip: SALT LAKE CITY, UTAH 84114 City, State, Zip: SALT LAKE CITY, UTAH 84114
Facility I.D.#: 4001950 Phone #: 801-531-4571
Testing Company: Westech Phone #: 801-266-2545 DATE: 1/13/2025
This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine
pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures.
Line Number 1 2 3
Product Stored DIESEL GAS DIESEL
Leak Detector Manufacturer VEEDER
ROOT
VEEDER
ROOT
VEEDER
ROOT
Leak Detector Model FX2 FX1 FX2
Type Of leak Detector
☒MLLD
☐ELLD
☒MLLD
☐ELLD
☒MLLD
☐ELLD
☐MLLD
☐ELLD
MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure 28 28 28
Check valve holding pressure 19 19 19
Line resiliency (ml) (line bleedback volume as measured
from check valve holding pressure to 0 psig) 105 105 105
Step through time in seconds (time the MLLD hesitates at
metering pressure before going to full operating pressure as
measured from 0 sig with no leak induced on the line)
3 3 3
Metering pressure (STP pressure when simulated leak rate 3
gph at 10 psig) 15 15 15
Opening time in seconds (the time the MLLD opens to allow
full pressure after simulated leak is stopped) 3 3 3
Does the STP pressure remain at or below the metering
pressure for at least 60 seconds when the simulated leak is
induced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Does the leak detector reset (trip) when the line pressure is
bled off to zero psig? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Does STP properly clycle on/off under normal fuel system
operating conditions? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
A "No" answer to any of the above questions indicates that the MLLD fails the test.
ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure
How many test cycles are observed before alarm/shutdown
occurs?
Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" answer to the above question indicates that the ELLD fails the test.
Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Jon Sainsbury Tester’s Signature Jon Sainsbury
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054