HomeMy WebLinkAboutDERR-2025-002625Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name LUMEN
Address 9111 HARLEQUIN CIRCLE
FREDERICK, CO 80504
Contact LUMEN
Phone
Email Stephanie.Miller@lumen.com
TANK LOCATION
Name DRAPER/SANDY CENTRAL OFFICE
Address 11351 S 1000 E
SANDY, UT 84070
A Operator CORY GENE WHITE
Phone (501) 680-8141
B Operator SAME
Phone SAME
Facility ID: 4000591 Inspection Date: 04/10/2025
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
TANK DETAILS
Tank ID/Alt ID 3 / 3
E-Gen/AST Yes / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc May 3, 2001 / 3000 / Single
Substance
Stored Diesel /
Tank Material-
Mod
Fiberglass Reinforced Plastic-
Double-Walled
ATG Veeder Root / TLS-300
LTT Test None
LLD Test None
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Safe Suction / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Per Prod. APST Cont. Sump
/ Automatic shutoff / No
PST Fund/Other
Type No / Insurance
Tank/Pipe Rel
Det TankATG PipeLineTightness
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
Title: monthly leak detection
sensor reports. Looks good.
No Photos
Title: failed spill and overfill
vacuum tested spill 3/24/2025 failed tested overfill 3/24/2025 failed
2025-04-10 Page 1 of 4
FACILITY RESPONSES
Financial Responsibility
Financial responsibility method is ok?Yes
The above accurately represents the
facility's release detection records Yes
Operator Training
A Operator current?Yes
B Operator current?Yes
Monthly checklist available and
complete?Yes
Is the site unmanned?No
Is a sign posted in a conspicuous area
giving the name and telephone number
of a person in case of an emergency
and if the station is manned part of the
time, are C operators trained?
Yes
TANK RESPONSES
Tank 3 Spill/Overfill
Tank has a spill prevention device?Yes
Is the tank exempt from having a spill
prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Does the Spill Prevention device have a
potential to release product into the
environment?
No
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 3 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Tank 3 Suction Piping Leak Detection
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
Tank 3 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
No
Does the overfill device have a valid 3-
year test or the tank is exempt?No
2025-04-10 Page 2 of 4
Tank 3 ATG/IM
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 3 ATG/IM
Does the ATG system have a valid
annual test?Yes
DISPENSER RESPONSES
MONTHLY LEAK DETECTION MONITORING
Apr '24 May '24 Jun '24 Jul '24 Aug '24 Sep '24 Oct '24 Nov '24 Dec '24 Jan '25 Feb '25 Mar '25
Tank 3 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
TANK 3
No Photos
Question:Does the spill bucket have a valid 3-year test, valid monthly monitoring for DW buckets, or the tank is
exempt?
Comments:None
TANK 3
No Photos
Question:Does the overfill device have a valid 3-year test or the tank is exempt?
Comments:None
2025-04-10 Page 3 of 4
Prepared by fueloperator.com
Inspection Information
Inspector:Wilson, David
Record Created:April 10, 2025, 9:18 a.m.
Inspection Date:April 10, 2025
2025-04-10 Page 4 of 4