HomeMy WebLinkAboutDERR-2025-002320TODD KING
UTAH STATE FUEL NETWORK
4315 S 2700 W
SALT LAKE CITY, UT 84129
RE:Request for Petroleum Storage Tank Records
SAN JUAN SCHOOL DISTRICT NAVAJO MOUNTAIN HIGH SCHOOL, located at RESERVATION ROAD #16,
BLANDING
Facility Identification No. 5000744
Dear TODD KING:
PST operators are required to ensure that certain tests are conducted for their tank system.
Dates highlighted in "Yellow" - tests are due soon.
Dates highlighted in "Red" - tests are due and you are out of compliance.
Tank ID/Alt
ID
Description LTT
--------------------
LLD
Spill Bucket
--------------------
Overfill
Tank or Flex
--------------------
Pipe CP
ATG
--------------------
Sump
1/1 Gasoline-Regular-4000 2/28/2025 N/A N/A N/A
N/A N/A N/A N/A
2/2 Diesel-Diesel #2 (U.L.S.)-10000 2/28/2025 N/A N/A N/A
N/A N/A N/A N/A
LTT - Line Tightness Test
LLD - Line Leak Detector
Overfill ±Overfill Device
Tank or Flex/Pipe CP - Corrosion Tests
ATG ±Automatic Tank Gauging
Sump - Tank Top Sump and applicable Dispenser Sumps
Please note that UDC tests are not listed, but are required on your facility's next sump test
cycle starting July 1, 2023, if applicable. Also, effective immediately pressure vent valves
must be tested every three years for gasoline tanks.
Please submit a copy of the required tests to the DERR within 30 days of the date due.
If you have any questions please call David Wilson at 801-536-4100.
195 North 1950 West - Salt Lake City, UT
Mailing Address: - P.O. Box 144840 - Salt Lake City, UT 84114-4840
Telephone (801) 536-4100 - Fax (801) 359-8853 - T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
February 05, 2025
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF ENVIRONMENTAL
RESPONSE AND REMEDIATION
Brent H. Everett
Director
APPLIED ENVIRONMENTAL SERVICES, L.C.
PO BOX 1073 BOUNTIFUL, UTAH 84011 801-540-9258
T.E.I. SYSTEM 4000 / T.E.I. LT3 / T.E.I. ULLAGE
PRECISION TANK & LINE TEST RESULTS SUMMARY
INVOICE ADDRESS: TANK LOCATION: WORK ORDER #
TECH # 94027 VAN # 8502
TECHNICIAN: SM
STATE TECH #
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
NAVAJO MOUNTAIN HIGH
25015
UT 0121
DATE:2-28-2025 TIME START: TIME END: GROUNDWATER DEPTH:N/A ASTS
TIME SYSTEM FILLED OR TOPPED:
TANK TANK
CAPACITY
4071
10079
PRODUCT
R/UL
DSL
TANK
AST
AST
VENT PRODUCT
LINE
PASS
PASS
LINE LEAK
DETECTOR
NONE
NONE
WATER IN
TANK
PUMP
TYPE
PRESS
PRESS
TANK
MATERIAL
CONVAULT
CONVAULT
1
2
3
4
5
6
PRODUCT LINES TESTED AT 50 PSI FOR 15 MINUTES
LINE RATES (GPH)
1
2
3
4
5
6
R/UL -.013
DSL -.011
ADDITIONAL INFORMATION:AST'S WITH UNDERGROUND PRODUCT LINES
INSTALLED NEW PV VALVE ON UNLEADED VENT
CERTIFIED TECHNICIAN SIGNATURE: DATE:2-28-2025
All tests are performed in a professional manner, and within common practices of the industry. However due to the
variables of tank testing, these results cannot be guaranteed. There are no warranties expressed, written or implied.
These systems meet all requirements set forth by USEPA 40 CFR and has recieved third party certification.
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.03.11 15:17:40 -07'00'
Reason: I am the author of this document
UTAH STATE FUEL NETWORK AST ANNUAL INSPECTION
Facility Name and Site Address: Date:
Facility ID #
Purpose:Regular Reinspection Complaints Annual Inspection
Nu
m
b
e
r
Te
s
t
e
d
Sa
t
i
s
f
i
e
d
Re
j
e
c
t
e
d
A
d
v
i
s
e
Pumps Tested for Calibration
Is tank grounding strap in good condition ?
Is tank coating free of corrosion / damage ?
Is tank free of noticable distortion, denting, buckeling ?
Flanged connection bolts appear tight ?
Normal and emergency vents appear in good condition ?
Inspection Remarks:
Technician signature
Inspected By: Steven B. Martin UT121
Applied Environmental Services L.C.
NAVAJO MOUNTAIN HIGH SCHOOL
2-28-2025
X
X
X
X
X NO DEDICATED GROUND STRAPS
X
X
X
X
X INSTALLED NEW PV VALVE
X
State Fuel Contact : Brett Gurney 385-602-4872
801-540 9258 Aesutah@aol.com
Email: Brettgurney@utah.gov
X
X
X
X
X NO OVERFILL PREVENTION
X
Fill and vapor connections in good condition ?
ASTS WITH UNDERGROUND PRODUCT LINES
INSTALLED NEW PV VALVE AND ADAPTER ON UNLEADED VENT
XTank containment structure in satisfactory condition ?
Free of tank settlement and foundation washout ?
Tank supports in satisfactory condition ?
Is water able to drain off tank pad and tank top ?
Gasoline vent has P/V valve installed where required ?
Valves / syphons / solenoids appear in good condition ?
Spill containment visable and appears in good condition
Electrical junction boxes and conduits in good condition
Tank monitor free of active alarms ?
Emergency shutoff installed ?
Dispenser static test ?
Tank overfill equipment installed ?
Piping sumps appear in good condition ?
COMMENTS / ACTION
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.03.11 15:29:10 -07'00'
Reason: I am the author of this document
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
Owner:
Address:
City, State, Zip Code:
Phone #
Testers Phone #
Date:
This procedure is to determine whether the ( ATG) is operating properly. See PEI/RP1200 Section 8.2 for the proper inspection procedure.
Tank Number
Product Stored:
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing
parts replaced?
4. Float moves freely on the stem without
5. Fuel float level agrees with the
value programmed into the console?
6. Water float level agrees with the value
programmed into the console?
7. Inch level from bottom of stem when 90%
alarm is triggered.
8. Inch level at which the overfill alarm
activates corresponds with value programmed
in the gauge?
9. Inch level from the bottom when the water
float first triggers an alarm.
10. Inch level at which the float alarm activates
corresponds with value programmed in the
gauge?
If any answers in Lines 3,4,5, or 6 are "NO" the system has failed the test.
TEST RESULTS
Comments:
Testers Name: Steven B. Martin Testers Signature:
NAVAJO MOUNTAIN HIGH SCHOOL
NAVAJO MOUNTAIN
AES UTAH TESTER # UT 0121
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
2-28-2025
1
R/UL
VED TLS 300C
4071
58
YES
YES
YES
YES
53
YES
2.0
YES
2
DSL
VED TLS 300C
10079
86
YES
YES
YES
YES
78
YES
2.1
YES
PASS PASS
BATTERY BACKUP FUNCTIONS PROPERLY
ABOVEGROUND FUEL TANKS
SETUP REPORT PRINTED
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2025.03.11 15:31:04 -07'00'
Reason: I am the author of this document
BILLING ADDRESS FACILITY ADDRESS
WORK ORDER # DATE:
CONTACT: DEQ ID#
APPLIED ENVIRONMENTAL SERVICES, L.C.
SEND PAYMENT TO : APPLIED ENVIRONMENTAL SERVICES
ALL TESTS WERE PERFORMED IN A PROFESSIONAL MANNER, AND WITHIN COMMON PRACTICES OF THE INDUSTRY.
DUE TO VARIABLES OF TIGHTNESS TESTING, THESE RESULTS CANNOT BE GUARANTEED. THERE ARE NO WARRANTIES.
EXPRESSED, WRITTEN, OR IMPLIED.
PO BOX 1073 BOUNTIFUL, UTAH 84011
.
PO#
801-540-9258
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
NAVAJO MOUNTAIN HIGH SCHOOL
BRETT GURNEY 246107 FD # 1174
25015 2-28-2025
MONITOR CERTIFICATION
275.00
SITES SHARE OF TRAVEL
108 MI @ 2.00 216.00
PRODUCT LINE TIGHTNESS TESTS
2 @ 250.00 500.00
AST ANNUAL INSPECTION
50.00
INSTALLED STATE SUPPLIED OPW623 PV VALVE ( AND ADAPTER )
ON UNLEADED VENT 1 HR @ 70.00 70.00
1111.00TOTAL DUE: