HomeMy WebLinkAboutDAQ-2025-0017761
DAQC-312-25
Site ID 16121 (B4)
MEMORANDUM
TO: STACK TEST FILE – CRUSOE ENERGY SYSTEMS, INC. – Duchesne Data Center
Power Plant
THROUGH: Harold Burge, Major Source Compliance Section Manager
FROM: Robert Sirrine, Environmental Scientist
DATE: March 20, 2025
SUBJECT: Location: 1 mile Northeast of Upalco, Duchesne County, Utah
Contact: Ken Parker 720-495-3656, Kaitlin Meszaros 631-245-0308
Tester: Great Plains Analytical Services (GAS), Macie McClellan 580-225-0403
Source: Two Waukesha H24 530 HP Compressor Engines
FRS Site ID#: UT0000004901300215
Permit #: TV Permit 1300141001 Dated December 27, 2024
Subject: Review of pretest protocol dated March 11, 2025, with additional
information dated March 25, 2025
On March 14, 2025, the Utah Division of Air Quality (DAQ) received a pretest protocol, with additional
information dated March 25, 2025, for emissions testing of the Crusoe Energy Systems – Duchesne Data
Center Power Plant’s two Waukesha H24 530 HP compressor engines located Northeast of Upalco,
Duchesne County, Utah. Testing will be performed on April 14-18, 2025, to determine compliance with
permit Conditions II.B.2.a, II.B.2.b, II.B.2.c, II.B.2.d, 40 CFR 63 Subpart ZZZZ and NSPS 40 CFR 60,
Subpart JJJJ for NOX, CO, and VOC emissions.
PROTOCOL CONDITIONS:
1. RM 1 used to determine sample and velocity traverses: OK
2. RM 2 used to determine exhaust effluent flows and mass emission rates: OK
3. RM 3A used to determine dilution concentration of exhaust oxygen: OK
4. RM 4 used to determine moisture content: OK
5. ASTM D6348-03 used to quantify gas phase concentrations of NOx emissions: OK
6. ASTM D6348-03 used to quantify gas phase concentrations of CO emissions: OK
7. ASTM D6348-03 used to quantify gas phase concentrations of VOC emissions: OK
* - / $ - - $ )
2
DEVIATIONS: No deviations were noted.
CONCLUSION: The pretest protocol received March 14, 2025, with additional information
received March 25, 2025, appear to be acceptable.
RECOMMENDATION: Send protocol review and test date confirmation notice
ATTACHMENT: Pretest protocol dated March 11, 2025
Additional information received March 25, 2025
Ses
itl-i ll'tst -ir'r1,.\1ri't'l . I:.lA ( itt'. ()Alttlt()tu(t -i()-l.l . -{\1)-l.r5-l)ll)-i
March 10,2025
Utah Department of Environmental Quality
State Office Building - Air Quality Division
195 North 1950 West
Salt Lake City, Utah 841l4
RE: Crusoe Energy Systems, Inc.
40 CFR Part 60 Subpart JJJJ - Test Notification
To Whom lt May Concem,
l- '-- urnl+1x-runnirw-Nr or-I E-ryv_Lr3olyEll_rAL -QUA!!TY
,l ,r 1,1 )i)r
ilL ___._ |
r I\/ISION OF AIR OUALITY
We are notifying you of performance testing dates for 40 CFR Part 60, Subpart JJJJ on behalf of
Crusoe Energy Systems, Inc. Please see below for the information pertinent to the testing. The
testing will take place the week of April7,2025.
Our testing protocol is included. for information regarding our protocol or the performance test,
you can contact me by email at mholsapple@gasinc.us or by phone at 580-225-0403. For
information regarding engine or location information, please contact Kaitlin Meszaros by email
at meszaros@pinyon-env.com or by phone at (63 l)-245-0308.
Regards,
k*;, llrlrd"
Macie Holsapple
Client Services Supervisor
GAS Inc.
Facility Unit #Serial #Location
Duchesne Data Center Power Station r 663358 Duchesne County. Utah
Duchesne Data Center Power Station 3221509 Duchesne County, Utah
( i. lS 1rr,
II ll 1l'. g(/\'il/('. i/,\
Performance Test Protocol
40 CFR Part 60 Subpart JJJJ
Facility: Duchesne Data Center Power Station
State of Utah
Perm it I D : #DAQE-AN 151210002-23
Unit lDs
Type
Annual
Prepared on behalf of
Crusoe Energy Systems, lnc.
Prepared by
Qns
303 West 3'd Street
Elk City, OK 73644
Great Plains Analytical Services, lnc.
Table of Contents
1.0 lntroduction. ..........3
7.7 Contact lnformation.. ............3
2.O Test lnformation................ ...........3
3.0 Method Synopsis........ .................. 5
4.0 Emission Point lnformation................ ................,5
4.1 Target Analytes........ ..............5
4.2 Test Quality Objectives.... ............................ 6
5.0 Quality Control lnformation.. ............................. 7
6.0 Additional lnformation and Reportin8...................................... 8
7.O Example Calculations. ................. 8
8.0 Health and Safety Concerns....... ........................ 9
Table(s)
1.1 Contact lnformation.. .................. 3
2,O Source lnformation and Testing Dates..................................... 3
2.7 Testing Limits and Parameters (Federal)................................. 4
2.2 TestingLimitsandParameters(State)..................................... 4
2.3 Additional Parameters... ..............4
4.2 Test Specific Target Analytes and Data Quality Objectives.. S
s.0 aA/ac........... ..........7
5.1 Measurement System Capabilities.. .................. 7
Figure(s)
3.1 Sample Port Location ...................5
3.2 Sample locations inside the stack..................................,.......... 5
9.0 Sampling Schematic Diagram........ .....................9
Protocol Attachment(s)
Engine Parameter Data Sheet Diagram................................. 10
Velocity Field Data Diagram........ .....................10
10.0
11.0
Great Plains Analytical Seruices, lnc.
fable 1.1
Contact ADDlication Teleohone EmallAddltss Phvsical Addrcs
Macie Holsapple GAS 580-225-0403 mholsapple@gasinc. us 303 W 3rd St. Elk city, OK 73644
Kaitlin Meszaros Crusoe Energy
Systeru, lnc.720-614-5598 Meszaros@pinyon-env.com
1.0 lntroduction
GAS has been cmtracted by Crus@ Energy Systems, lnc. to conduct source testing seruices at Duchesne Data Center Power Station located in ouchesne County, Utah. The purpose of
engines fueled by Natural Gas.
1.1 Contact lnfomation
2.0 Test lnfomation (contlnuedl
Thetestwillbeconductedusin8amulticomponentBasanalyzerthatincorporatesaFourierTransformlnfrared(FTIR)spectrometer. FTlRisstateofthearttechnoloty. ltis
designed to military specifications and allws simple calibration using only single component calibration Bases.
Tests will consist of (3) 60 minute test runs.
2.0 Test lnfomation
Gre.l PIeiN An.lSir.l 5edlce5, lnr
Oxysen (O2)%vd ]A
Moisture % H20 06348-03
Sample Ication ln(hes (")t/1A
Footnote
cO2, H2O, NOr, cO, voc, and cH2o will be
measured uslnt a Gasmet multigas FTIR analyze.ln
..cordance wlth ASTM Method D6348 when:n.ll..hl. ,n,lvr.<.t. h.ln, t.<ted Int
3.0 Method Synopsis
EPA Method 1/1A
The purpose of the method is to provide guidance for the selection of sampling ports and traverse points at which sampling for air pollutants will be
performedpursuanttoregulationssetforthinthispart. MethodlmaybemodifiedasallowedinSubpartJJJJ &TTTT.Alternafively,forNOx,CO,
VOC, 02, and moisture measurement, ducts s6 inches in diameter may be sampled at a single point located at the duct centroid and ducts >6 and
s12 inches in diameter may be sampled at 3 traverse points located at 16.7,50.0, and 83.3% of the measurement line ('3-point long line'). lf the
duct is >12 inches in diameter and the sampling port location meets the two and half-diameter criterion of Section 11.1.1of Method 1of 40 CFR
part 50, Appendix A, the duct may be sampled at'3-point long line'; othenivise, conduct the stratification testing and select sampling points
accordingto Section 8.1.2 of Method 7E of40 CFR part 60, Appendix A."
Figure 3.1
For all stacks greater than 6" in diameter, GAS will use a sampling port that is located at a minimum of 2 stack diameters downstream from any
disturbance, and U2 stack diameter upstream from any disturbance.
1/2 diameter upstream
2 diameters downstream
Actualdiameter
SAMPLE PORT LOCATION DETERMINED
BY DISTANCE FROM DISTURBANCE
Figure 3.1. Sample Port Location
Figure 3.2
For all stacks greater than 5" in diameter, GAS will sample at 3 points within the stack. These points will be located at 83.3%, 50%, and 16.7% of the
stack diameter.
TRI-PROBE SAMPLE POINT LOCATIONS
AS PERCENTAGE OF STACK DIAMETER
eU
U23oYo
Eo
Great Plains AElyti6l SeRic6, lnc.
EPA Method 2/2C
This method is applicable for the determination of the average velocity and the volumetric flow rate of a gas stream. Method
2 will be used for stacks greater than 12 inches. Method 2C will be used for stacks with a diameter ol L2 inches or less.
Section 12.5 of this method will be utilized to determine the molecular weight of the stack on a wet basis. The formula found
in Method 3 section 12.3 will be utilized to determine the molecular weight of the stack gas on a dry basis.
EPA Method 3A
This is a procedure for measuring oxygen (O2) and carbon dioxide (CO2) in stationary source emissions using a continuous
instrumental analyzer. Quality assurance and quality control requirements are included to assure that the tester collects data
of known quality. Documentation to these specific requirements for equipment, supplies, sample collection and analysis,
calculations, and data analysis will be included.
ASTM D63rr8-03
This extractive FTIR based field test method is used to quantify gas phase concentrations of multiple target analytes from
stationarysourceeffiuent. BecauseanFTlRanalyzerispotentiallycapableofanalyzinghundredsofcompounds,thistest
method is not analyte or source specific. The analytes' detection levels, and data quality objectives are expected to change
for a ny pa rticu la r testing situation. lt is the responsibility of the teste r to define the ta rget a na lytes, the associated detection
limits for those analytes in the particular source effluent, and the required data quality objectives for each specific test
program. Provisionsareincludedinthistestmethodthatrequirethetestertodeterminecriticalsamplingsystemand
instrument operational parameters, and for the conduct of QA,/QC procedures. Testers following this test method will
generate data that will allow an independent observer to verify the valid collection, identification, and quantification of the
subject target analytes. A heated sample line is used to collect the sample on a wet basis per ASTM D6348. Effluent
Moisture content is determined to within a 2Yo accuracy using the FTIR analytical algorithm.
4.0 Emissions Point lnformation
4.1 Target Analytes
Exhaust emission testing will be conducted for the following compounds: carbon monoxide (CO), oxides of nitrogen (NOx),
volatile organic compounds (VOCs), and oxygen (O2%).
4.2 Test Quality Objectives
Table 4.2 summarizes the test quality objectives specific that will be used to evaluate test data to a known degree of
accuracy.
Concentration
Measurement
System Achievable
Concentrations
Required
Measurement
System Accuracy
and Precision for
Test Application
VOC as defined in 40 CFR Part 60
subpart JJJJ
*. Measured flue gas conditions at the sampling location including temperature, moisture content, and volumetric flow rate
will be included in test results.
6reat Plains Analytical Seryices, lnc
5.0 Quality Control lnformation
The following is a list of the QAy'QC procedures performed. lt is listed as to the process and method it pertains
to. Calibrationsheets,calibrationgasesandanyothertestingequipmentwill bemadeavailablepriortothe
start of testing. Upon completion of the assembled sampling system, a leak check will be conducted under
pressure or partial vacuum conditions to ensure the integrity ofthe sample collection system.
5.0 quality Control lnformation (continued)
Datageneratedduringthebenchscalepre-testprocedureswillbepresentedinTable5.l. PleasenotethatTableS.lwill
be presented in the final report with data collected from the actual field-testing source.
All informationrequiredperASTMD6348,Annexesl-7will beprovidedinthefinal report. Thisinformationshall cover:
Test Plan Requirements
Determination of FTIR Measurement System Minimum Detectable Concentration
FTIR Reference Spectra
Required Pre-Test Procedures
AnalVte Spikinx Technique
Determination ofSystem Performance Parameters - Noise Equivalent Absorbance, Line Position, Resolution, and
Preparation of Analytical Quantification Algorithm
A1)
A2)
A3)
A4)
As)
A6)
47)
rable 5.0 QA/QC
Process or Hement
I rraohall QA/QC Element Acceptance Criteria Frequency
Calibration Gas TraceabiliW protocol 2% Certaintv Everv Test
SamDle Extraction ILAI Probe material Pass svstem bias check Everv test run
SamDle Ertraction (D6348)Particulate filter Placed after heated orobe :hanced weeklv
Samole Extraction (D6348)Probe Box Heated to 180'C, introduces calibration
into sampling system at the probe outlet Every test
Sample Extraction (3A,/D6348)Heated line Sample kept above dew point at all
times.
emp kept to 1E0-c at
all times. Visible
/idir.l d.,,da
SamDle Extraction ( 1/1A)Manifold material Stainless Steel Everv Test
Sample Point Selection (1/1A)Measurement from disturbances 1/2 stack diameter downstream and 2
stack diameters upstream.Every test
Multiple Sample Points
Simultaneouslv (1/14)Distance from stack walls 83.3"A, 50"A, L6.6oA f tom stack walls All stack under 6"
Velocity Flow Measurement
12)
M anometer
System is back purged after last sample.
Another sample is taken and must be
within 5% of the last sample
Every test
Velocity Flow Measurement
(2)Manometer Manometer is leveled and visual
in<nprfcd Every test run
Svstem Performance (3A)Ca libration within 10% of the Sample collected Every test
System Performance (3A)System bias check Within 5%6erore Ttrsr resr ano
-k^. l-.r
System Pertormance
I 1 A /nAirA\System response time Determines minimum samplin8 time During bias check
System Performance (3A)Draft Within 3%During bias check
System Performance D6348)System Zero Less than 2 % of permat limit Pre test
System Performance 05348)CTS Check direct to analyzer Within Tolerance Pre and post test
System Performance D6348)CTS Check entire system Within Tolerance Pre Test
System Performance D6348)System Recovery (Spike)Within 30% of effluent concentration Every test run
System Performance (D5348)Line position
Verify line positions have not shifted by
more than 15% of the resolution, and the
resolution has not chan8ed by more than
1 q% ^f ihii .ioiarhi^o.l hri^r t^ io<tiho
Post Test
Parameter Measured Gas Concentration Path
Lensth Equilibration Time Dilution
Factor
%
Recovelv
Path Leneth Ethvlene to7.2 4.93
Mechanical Response Time Ethvlene 101.2 42
Svstem Resoonse Time Prooane 101.9 37
AnalWe Spike Recovery Propane 101.9 50 10 92
Svstem Zero Nitrogen 5S
Greal Plains Analyti(al Serurces, lft
6.0 Additional lnformation and Reporting
Additional parameters and atmospheric information will also be provided in the final report and will include:
* Elevation, Barometric pressure ("HG), Ambient temperature'F, Humidity Yo,Dew Point "F* Catalyst lnlet Temp'F, Catalyst Outlet Temp "F, Manifold Temp "F* Exhaust Gas Temp'C* RPM, Manifold Pressure ("HG)* Horsepower (BHP) and Fuel Flow Rate (dscfh)* Stack Diameter (")* Sample location (" Downstream from Disturbance & " Upstream from Disturbance)* Catalyst Pressure Drop ( lnches H20)* Moisture Percentage* Volumetric Flow Rate* AFR setpoints and reading* CatalystManufacturer* N umber of elements* Date of installation* Date of last reconditioning or cleaning
The final report will contain all field test data including all pre and post calibration information. Final
concentrations will be reported in the permitted units of measure.
7.0 Example Calculations
1. Exhaust Volumetric flow Rate Determination by EPA Method 2
Qsd= 3500* (1-B(ws))*V(s)*A* (T(std)/T(s))* P(s)/P(std)
V(s)= 45to1r," Stack Gas Velocity
A= Cross Sectional Area of Stack
T(std)= standard Absolute Temperature
T(s)= 66to1r," Stack Temperature
P(s)= 46to;r," Stack Pressure
P(std)= 513 n6. rd Absolute Pressure
2. Absolute Stack Gas velocity v(s)
(When Method 2 is used)
V(s)= K*c*v(AP)*v(T(s(avg))+450)/v(M*P)
K=Pitot tube velocity Constant (85.49)
C=Velocity Pressure Coefficient
VAP= Square Root of differential Pressure of stack gas (inH2O)
T(s(avg))= Average Stack temp'R
M=Molecular Weight of stack gas, wet basis
P= Absolute stack gas Pressure
3. Mass Emission Rates (tBS./HR.)3. Mass Emission Rates (G./HP.-HR.)
lblhr =(385*105)4wttP-ttt - Engine Horsepower
lt R/HRl*4qa
3. Mass Emission Rates (TPY)
rDV - (LB/HR)t24(HRS/DAY)t365(DaysAR)..'-
Great Plains Analytical Services, lnc
8.0 Health and Safety Concerns
ln accordance with 40 CFR Part 60.8, the client must provide safe access to the unit for testing and observance.
Due to the nature of the source and the exposure to high temperatures, extreme caution will be observed in
ordertoavoidcontactwiththeunitwhichmayresultinburnsandorinhalationofexhaustemissions. GAS
personnel will sign in and out at all facilities, as well as undergo site specific safety training.
ln addition, GAS will use the following safety equipment:* Hardhat* Steel-Toed Bootsi Safety Glasses* Hearing Protection* Fire-RetardantClothing* 4-SafetyGloves* 4 Gas Monitor
Due to the remote location of the source unit, additional health & safety precautions will be observed such as
avoidance of slips, trips, falls, and heat exhaustion.
Figure 9.0 Schematic Diagram ,TlF
*#-l
U
PANEI
[\r e
IGNT I #
Figure 9.0 Sampling Schematic Diagram
Breakdown Of Schematic Diagram:* Gas: Required calibration gases per ASTM D6348 and Method 3A.
ControlPanel: AllowsthecontrolofflowthroughoutthesystemasrequiredbyASTMD6348and
Method 3A. Allows for introduction of calibration standards into the sampling system at the probe
outlet, upstream of the primary particulate filter.
Probe: Heated probe assembly required by ASTM D5348.
Heated Line: Used for "Hot/Wet" sample to keep line above any dew point that would cause
moisture to drop out.
PSS: Allows precise heating of the samplinB system.
02 Sensor: Zirconium Dioxide sensor to measure Oxygen per method 3A.
Gasmet FTIR: FTIR Analyzer for use with ASTM D5348
Flow Meter: Allows proper measurement of flow.
Data: Dataacquisitionsystemthatallowsfortheacquisitionoftheinfrareddata,Oxygendataand
analysis ofthe resulting spectra.
Great Plains Analytical SeMces, lnc
Attachment 10.0 Engine Parameter Data Sheet Diagram
#as
**Note: Actual note parameters may differ due to the availability of such parameters at specific locations.
Attachment 11.0 Velocity Field Data
Pitot readlngs.re taken for Method 2 calculatlons usln8 me.surlng goints outlincd ln Method 1
Ap*a- Vclaity hcod mcasurcd by
s.mDle aftcr Back Purtc:
Withln 5X of l.st Apstd readlna:
Stack Dlemeter (inches)
lnches upstream from disturbance
Great Plains Analytical seryices, lnr
Great Plains Analytical Services, Inc.
Facility Unit # Serial # Location
Duchesne Data Center Power
Station
1663358 Duchesne County,
Utah
Duchesne Data Center Power
Station
3221509 Duchesne County,
Utah
Our testing protocol is included, for information regarding our protocol or the performance
test, you can contact me by email at mholsapple@gasinc.us or by phone at 580-225-0403.
For information regarding engine or location information, please contact Kaitlin Meszaros
by email at meszaros@pinyon-env.com or by phone at (631)-245-0308.
Regards,
Macie Holsapple
Client Services Supervisor
GAS Inc.
P.O. Box 682 ● 303 West 3rd Street ● Elk City, Oklahoma 73644 ● 580-225-0403
March 25, 2025
Utah Department of Environmental Quality
State Office Building – Air Quality Division
195 North 1950 West
Salt Lake City, Utah 84114
RE: Crusoe Energy Systems, Inc.
40 CFR Part 60 Subpart JJJJ – Test Notification
To Whom It May Concern,
We are notifying you of performance testing dates for 40 CFR Part 60, Subpart JJJJ on behalf
of Crusoe Energy Systems, Inc. Please see below for the information pertinent to the
testing. The testing will take place the week of April 14, 2025.
Great Plains Analytical Services, Inc.
Performance Test Protocol40 CFR Part 60 Subpart JJJJ
Facility: Duchesne Data Center Power Station
State of Utah
Permit ID: #DAQE-AN161210002-23
Prepared by
303 West 3rd StreetElk City, OK 73644
TypeAnnual
Prepared on behalf ofCrusoe Energy Systems, Inc.
Unit IDs
Great Plains Analytical Services, Inc.
1.0 Introduction………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….3
1.1 Contact Information………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….3
2.0 Test Information………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….3
3.0 Method Synopsis………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….5
4.0 Emission Point Information………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….6
4.1 Target Analytes………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….6
4.2 Test Quality Objectives………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….6
5.0 Quality Control Information………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….7
6.0 Additional Information and Reporting………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….8
7.0 Example Calculations………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….8
8.0 Health and Safety Concerns………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….9
1.1 Contact Information………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….3
2.0 Source Information and Testing Dates………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….3
2.1 Testing Limits and Parameters (Federal)………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….4
2.2 Testing Limits and Parameters (State)………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….4
2.3 Additional Parameters………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….4
4.2 Test Specific Target Analytes and Data Quality Objectives………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….6
5.0 QA/QC………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….7
5.1 Measurement System Capabilities………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….7
3.1 Sample Port Location………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….5
3.2 Sample locations inside the stack………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….5
9.0 Sampling Schematic Diagram………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….9
10.0 Engine Parameter Data Sheet Diagram………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….10
11.0 Velocity Field Data Diagram………………………………………………………………………………………………………………………………………………………………………………………………….…………………………………………………………………………………………………….10
Table of Contents
Table(s)
Figure(s)
Protocol Attachment(s)
3
Great Plains Analytical Services, Inc.
2.0 Test Information (continued)
1.0 Introduction
Tests will consist of (3) 60 minute test runs.
The test will be conducted using a multi component gas analyzer that incorporates a Fourier Transform Infrared (FTIR) spectrometer. FTIR is state of the art technology. It is
designed to military specifications and allows simple calibration using only single component calibration gases.
1.1 Contact Information
2.0 Test Information
Waukesha H24 530
Test Dates
mholsapple@gasinc.us
Crusoe Energy
Systems, Inc.720-614-5598 Meszaros@pinyon-env.com
Table 2.0 Test Information and Testing Dates
GAS has been contracted by Crusoe Energy Systems, Inc. to conduct source testing services at Duchesne Data Center Power Station located in Duchesne County, Utah. The purpose of
this test plan is to document the test methods and procedures that will be employed to collect and analyze exhaust gas emissions during performance testing of the internal combustion
engines fueled by Natural Gas.
Contact
Macie Holsapple
Physical Address
303 W 3rd St. Elk City, OK 73644GAS580-225-0403
Table 1.1 Contact Information
Kaitlin Meszaros
Serial Number Location/Facility
Name Make and Model Site Rated
Horsepower
Application Telephone Email Address
Source ID
1663358
Duchesne Data
Center Power
Station
3221509
Duchesne Data
Center Power
Station
Waukesha H24 530
Week of
04/14/2025
Week of
04/14/2025
4
Great Plains Analytical Services, Inc.
g/hp-hr lb/hr TPY ppm
@15% O2 g/hp-hr lb/hr TPY ppm
@15% O2 g/hp-hr lb/hr TPY ppm
@15% O2
1.00 2.00 0.70
1.00 2.00 0.70
g/hp-hr lb/hr TPY ppm
@15% O2 g/hp-hr lb/hr TPY ppm
@15% O2 g/hp-hr lb/hr TPY ppm
@15% O2
0.15 0.18 0.30 0.35 0.02 0.020
0.15 0.18 0.30 0.35 0.02 0.020
3A
D6348-03
1/1A
% H2O
Sample Location Inches (")
CO2, H2O, NOx, CO, VOC, and CH2O will be
measured using a Gasmet multigas FTIR analyzer in
accordance with ASTM Method D6348 when
applicable analytes are being tested for.
Footnote
Table 2.3 Additional Parameters
Reduction %
Reference Method 10/2
COOxygen (O2)%vd
Moisture
CH2O
320
Reduction %
Table 2.4 Testing Limits and Parameters (Reduction)
Source ID
Table 2.2 Testing Limits and Parameters (State)
Source ID
NOx CO VOC (NMNEHC)
Reference Method ASTM D6348-03 Reference Method ASTM D6348-03 Reference Method ASTM D6348-03
Reference Method ASTM D6348-03Reference Method ASTM D6348-03
Table 2.1 Testing Limits and Parameters (Federal)
Reference Method ASTM D6348-03Source ID
VOC (NMNEHC)NOx CO
5
Great Plains Analytical Services, Inc.
3.0 Method Synopsis
EPA Method 1/1A
Figure 3.1
Figure 3.2
The purpose of the method is to provide guidance for the selection of sampling ports and traverse points at which sampling for air pollutants will be
performed pursuant to regulations set forth in this part. Method 1 may be modified as allowed in Subpart JJJJ & ZZZZ. Alternatively, for NOx, CO,
VOC, O2, and moisture measurement, ducts ≤6 inches in diameter may be sampled at a single point located at the duct centroid and ducts >6 and
≤12 inches in diameter may be sampled at 3 traverse points located at 16.7, 50.0, and 83.3% of the measurement line ('3-point long line'). If the
duct is >12 inches in diameter and the sampling port location meets the two and half-diameter criterion of Section 11.1.1 of Method 1 of 40 CFR
part 60, Appendix A, the duct may be sampled at '3-point long line'; otherwise, conduct the stratification testing and select sampling points
according to Section 8.1.2 of Method 7E of 40 CFR part 60, Appendix A."
For all stacks greater than 6" in diameter, GAS will use a sampling port that is located at a minimum of 2 stack diameters downstream from any
disturbance, and 1/2 stack diameter upstream from any disturbance.
For all stacks greater than 6" in diameter, GAS will sample at 3 points within the stack. These points will be located at 83.3%, 50%, and 16.7% of the
stack diameter.
1/2 diameter upstream
2 diameters downstream
Figure 3.2. Sample locations inside the stack
Actual diameter
Figure 3.1. Sample Port Location
6
Great Plains Analytical Services, Inc.
4.1 Target Analytes
4.2 Test Quality Objectives
Section 12.5 of this method will be utilized to determine the molecular weight of the stack on a wet basis. The formula found
in Method 3 section 12.3 will be utilized to determine the molecular weight of the stack gas on a dry basis.
CO
Target Analytes
Exhaust emission testing will be conducted for the following compounds: carbon monoxide (CO), oxides of nitrogen (NOx),
volatile organic compounds (VOCs), and oxygen (O2%).
Table 4.2 summarizes the test quality objectives specific that will be used to evaluate test data to a known degree of
accuracy.
Compounds
Table 4.2. Test Specific Target Analytes and Data Quality Objectives
Infrared Analysis
Expected
Concentration Range
Measurement
System Achievable
Minimum Detectable
Concentrations
Required
Measurement
System Accuracy
and Precision for
Test Application
(cm-1)
VOC as defined in 40 CFR Part 60
subpart JJJJ
2600-3200
0-100 ppm 0.9 ppm 1 ppm910-11502550-2950
*. Measured flue gas conditions at the sampling location including temperature, moisture content, and volumetric flow rate
will be included in test results.
Interfering CompoundsCO2 926-1150 0-10%0%n/aWater Vapor 3200-3401 0-22%0.2%n/a
2700-2950 0-100 ppm 0.03 ppm 2 ppmNO2
EPA Method 2/2C
EPA Method 3A
This method is applicable for the determination of the average velocity and the volumetric flow rate of a gas stream. Method
2 will be used for stacks greater than 12 inches. Method 2C will be used for stacks with a diameter of 12 inches or less.
This is a procedure for measuring oxygen (O2) and carbon dioxide (CO2) in stationary source emissions using a continuous
instrumental analyzer. Quality assurance and quality control requirements are included to assure that the tester collects data
of known quality. Documentation to these specific requirements for equipment, supplies, sample collection and analysis,
calculations, and data analysis will be included.
NO 1875-2138 0-1000 ppm 0.20 ppm 2 ppm
ASTM D6348-03
This extractive FTIR based field test method is used to quantify gas phase concentrations of multiple target analytes from
stationary source effluent. Because an FTIR analyzer is potentially capable of analyzing hundreds of compounds, this test
method is not analyte or source specific. The analytes’ detection levels, and data quality objectives are expected to change
for any particular testing situation. It is the responsibility of the tester to define the target analytes, the associated detection
limits for those analytes in the particular source effluent, and the required data quality objectives for each specific test
program. Provisions are included in this test method that require the tester to determine critical sampling system and
instrument operational parameters, and for the conduct of QA/QC procedures. Testers following this test method will
generate data that will allow an independent observer to verify the valid collection, identification, and quantification of the
subject target analytes. A heated sample line is used to collect the sample on a wet basis per ASTM D6348. Effluent
Moisture content is determined to within a 2% accuracy using the FTIR analytical algorithm.
4.0 Emissions Point Information
4 ppm1 ppm0-1200 ppm2000-2200
7
Great Plains Analytical Services, Inc.
Path
Length
Dilution
Factor
%
Recovery
4.93
10 92
A1)
A2)A3)A4)A5)A6)A7)Determination of System Performance Parameters - Noise Equivalent Absorbance, Line Position, Resolution, and Analyte Spiking TechniqueRequired Pre-Test ProceduresFTIR Reference Spectra
Preparation of Analytical Quantification Algorithm
Determination of FTIR Measurement System Minimum Detectable ConcentrationTest Plan Requirements
All information required per ASTM D6348, Annexes 1-7 will be provided in the final report. This information shall cover:
System Zero Nitrogen 65
Analyte Spike Recovery Propane 101.9 50
CTS Check entire system
System Recovery (Spike)
Data generated during the bench scale pre-test procedures will be presented in Table 5.1. Please note that Table 5.1 will
be presented in the final report with data collected from the actual field-testing source.
System Performance
(3A/D6348)Determines minimum sampling time During bias check
System Performance (3A)Within 3%During bias check
System response time
Drift
System Performance (D6348)Less than 2 % of permit limit Pre test
5.0 Quality Control Information (continued)
Mechanical Response Time Ethylene 101.2 42
System Response Time Propane 101.9 37
Table 5.1. Measurement System Capabilities
Parameter Measured Gas Concentration Equilibration Time
Path Length Ethylene 101.2
5.0 Quality Control Information
The following is a list of the QA/QC procedures performed. It is listed as to the process and method it pertains
to. Calibration sheets, calibration gases and any other testing equipment will be made available prior to the
start of testing. Upon completion of the assembled sampling system, a leak check will be conducted under
pressure or partial vacuum conditions to ensure the integrity of the sample collection system.
QA/QC Element
Traceability protocol
Probe material
Particulate filter
Table 5.0 QA/QC
Multiple Sample Points
Simultaneously (1/1A)83.3%, 50%, 16.6% from stack walls All stacks under 6"
Measurement from disturbances
Distance from stack walls
Sample Extraction (D6348)
Heated line
Manifold material
Process or Element
(Method)Acceptance Criteria Frequency
Calibration Gas 2% Certainty Every Test
Sample Extraction (1/1A)Pass system bias check Every test run
System Performance (D6348)
Verify line positions have not shifted by
more than 15% of the resolution, and the
resolution has not changed by more than
15% of that determined prior to testing.
Post TestLine position
System Performance (3A)Within 5%Before first test and
after last
Calibration
System bias check
System Performance (D6348)Within Tolerance Pre and post test
System Zero
CTS Check direct to analyzer
System Performance (D6348)Within Tolerance Pre Test
System Performance (D6348)Within 30% of effluent concentration Every test run
System Performance (3A)Within 10% of the Sample collected Every test
Stainless Steel Every Test
Velocity Flow Measurement
(2)
Manometer is leveled and visual
inspected
Sample Point Selection (1/1A)1/2 stack diameter downstream and 2
stack diameters upstream.Every test
Sample Extraction (D6348)Placed after heated probe Changed weekly
Heated to 180°C, introduces calibration
into sampling system at the probe outlet Every testProbe Box
Sample Extraction (3A/D6348)Sample kept above dew point at all
times.
Temp kept to 180°C at
all times. Visible
digital gaugeSample Extraction (1/1A)
Every test run
Manometer
Manometer
Velocity Flow Measurement
(2)
System is back purged after last sample.
Another sample is taken and must be
within 5% of the last sample
Every test
8
Great Plains Analytical Services, Inc.
* Elevation, Barometric pressure ("HG), Ambient temperature °F, Humidity %, Dew Point °F
* Catalyst Inlet Temp °F, Catalyst Outlet Temp °F, Manifold Temp °F
* Exhaust Gas Temp °C
* RPM, Manifold Pressure ("HG)
* Horsepower (BHP) and Fuel Flow Rate (dscfh)
* Stack Diameter (")
* Sample location (" Downstream from Disturbance & " Upstream from Disturbance)
* Catalyst Pressure Drop ( Inches H2O)
* Moisture Percentage
* Volumetric Flow Rate
* AFR setpoints and reading
* Catalyst Manufacturer
* Number of elements
* Date of installation
* Date of last reconditioning or cleaning
1. Exhaust Volumetric flow Rate Determination by EPA Method 2
Qsd=3600*(1-B(ws))*V(s)*A*(T(std)/T(s))*P(s)/P(std)
V(s)= Absolute Stack Gas Velocity
A= Cross Sectional Area of Stack
T(std)= Standard Absolute Temperature
T(s)= Absolute Stack Temperature
P(s)= Absolute Stack Pressure
P(std)= Standard Absolute Pressure
(When Method 2 is used)
K=Pitot tube velocity Constant (85.49)
C=Velocity Pressure Coefficient
√ΔP= Square Root of differential Pressure of stack gas (inH2O)
T(s(avg))= Average Stack temp °R
M=Molecular Weight of stack gas, wet basis
P= Absolute stack gas Pressure
(LB/HR)*454Engine Horsepower
(LB/HR)*24(HRS/DAY)*365(Days/YR)2000(LB/TON)
3. Mass Emission Rates (TPY)
TPY =
g/hp-hr = lb/hr =
K*C*√(ΔP)*√(T(s(avg))+460)/√(M*P)V(s)=
6.0 Additional Information and Reporting
Additional parameters and atmospheric information will also be provided in the final report and will include:
The final report will contain all field test data including all pre and post calibration information. Final
concentrations will be reported in the permitted units of measure.
7.0 Example Calculations
2. Absolute Stack Gas Velocity V(s)
3. Mass Emission Rates (LBS./HR.)
((Mol Wgt)*(Qd dscfh)*(concentration (385*106)
3. Mass Emission Rates (G./HP.-HR.)
9
Great Plains Analytical Services, Inc.
* Hardhat* Steel-Toed Boots* Safety Glasses* Hearing Protection* Fire-Retardant Clothing* 4 - Safety Gloves* 4 Gas Monitor
*
*
*
*
*
*
*
*
*
8.0 Health and Safety Concerns
In accordance with 40 CFR Part 60.8, the client must provide safe access to the unit for testing and observance.
Due to the nature of the source and the exposure to high temperatures, extreme caution will be observed in
order to avoid contact with the unit which may result in burns and or inhalation of exhaust emissions. GAS
personnel will sign in and out at all facilities, as well as undergo site specific safety training.
Probe: Heated probe assembly required by ASTM D6348.
Heated Line: Used for "Hot/Wet" sample to keep line above any dew point that would cause
moisture to drop out.PSS: Allows precise heating of the sampling system.
Breakdown Of Schematic Diagram:
O2 Sensor: Zirconium Dioxide sensor to measure Oxygen per method 3A.
Gasmet FTIR: FTIR Analyzer for use with ASTM D6348
Flow Meter: Allows proper measurement of flow.
Data: Data acquisition system that allows for the acquisition of the infrared data, Oxygen data and
analysis of the resulting spectra.
Gas: Required calibration gases per ASTM D6348 and Method 3A.
Control Panel: Allows the control of flow throughout the system as required by ASTM D6348 and
Method 3A. Allows for introduction of calibration standards into the sampling system at the probe
outlet, upstream of the primary particulate filter.
Due to the remote location of the source unit, additional health & safety precautions will be observed such as
avoidance of slips, trips, falls, and heat exhaustion.
Figure 9.0 Sampling Schematic Diagram
Figure 9.0 Schematic Diagram
In addition, GAS will use the following safety equipment:
!
10
Great Plains Analytical Services, Inc.
**Note: Actual note parameters may differ due to the availability of such parameters at specific locations.
Attachment 11.0 Velocity Field Data
Attachment 10.0 Engine Parameter Data Sheet Diagram 1/53
Great Plains Analytical Services, Inc.
10.0 Engine Parameter Data Sheet
Company
Facility
Date
Elevation (ft)
Unit ID
Make
Model
Serial Number
Technician
Run 1 Run 2 Run 3 AverageTime:9:06 AM 10:17 AM 11:28 AM N/A
Engine Speed (RPM)1601 1600 1603 1601Engine Hours 10568 10569 10570 10571Catalyst (Yes or No)Yes Yes Yes YesCatalyst Manufacturer Murphy Murphy Murphy Murphy# of Catalyst installed 1 1 1 1Catalyst Element Installation date 7/22/16 7/22/16 7/22/16 7/22/16Catalyst Inlet Temp °F 847 845 846 846Catalyst Outlet Temp °F 878 879 780 846Catalyst Pressure Drop H2O 1.50 1.50 1.50 1.50Catalyst reconditioning or cleaning date New New New NewAFR Manufacturer/Type Murphy Murphy Murphy MurphyAFR Setting (Targets Right Bank)17.00 17.00 17.00 17.00AFR Readings NA NA NA NA
Intake Manifold Pressure (psi)4.40 4.50 4.50 4.47Ambient Temp °F 76.00 79.00 83.00 79.33Exhaust Gas Temp °F (From Probe)785.00 784.00 783.00 784.00Intake Manifold Temp °F 85.00 85.00 85.00 85.00Barometric Press ("HG)30.13 30.13 30.11 30.12Fuel Flow Rate (dscf)587.00 586.63 587.73 587.12Engine Load (BHP)72.05 72.00 72.14 72.06
Cottonwood 08E
Cummins
4,724
Whiting Oil & Gas Company
7/26/2016
73697207
ENG-01
5.9
Noel Arnim