HomeMy WebLinkAboutDAQ-2025-001762
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144820 • Salt Lake City, UT 84114-4820
Telephone (801) 536-4000 • Fax (801) 536-4099 • T.D.D. 800 346-3128
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
Department of
Environmental Quality
Tim Davis
Interim Executive Director
DIVISION OF AIR QUALITY
Bryce C. Bird
Director
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
DAQC-317-25
Site ID 10335 (B5)
Rheannon Schaefer, Environmental Specialist
Tesoro Refining and Marketing Company, LLC
474 West 900 North
Salt Lake City, UT 84103-1425
Dear Ms. Schaefer:
Re: Tesoro Refining and Marketing Company, LLC (Tesoro) – Pretest Protocol for Hydrogen
Sulfide (H2S) Relative Accuracy Test – Salt Lake County
The Utah Division of Air Quality (DAQ) reviewed Tesoro’s pretest protocol dated March 14,
2025. The proposed test shall be performed under the following conditions:
Tesoro’s monitoring system to be certified:
Point Source Channel Manufacturer Model # Monitor SN
V-917 H2S Siemens Maxum II TCD 30048853581060
North Flare H2S Siemens Maxum II TCD 30048895441610
South Flare H2S Siemens Maxum II TCD 30048895441060
Alliance Technical Group, LLC will conduct a relative accuracy/performance specification test on
Tesoro’s continuous monitoring system.
Relative accuracy must be determined in the units of the emission standard or equivalent units of
the emission standard, i.e., tons/year shall be tested in pounds/hour.
The DAQ understands that testing will conduct testing as follows:
Test Date Point Source Parameter EPA Reference
Method
August 5-7,
2025
V-917 fuel gas, North and South Flare
CEMS H2S Method 11
/ % Û à Û Ù Û Þ
DAQC-317-25
Page 2
• Reference Method 11 - Determination of Hydrogen Sulfide Emissions from
Stationary Point Sources – as outlined in 40 CFR 60 Appendix A.
• Deviations - The Director or the representative of the Director must be notified of
and approve deviations of the Reference Method test. Any deviation from these
conditions without approval from the DAQ may constitute rejection of these tests.
Acceptance of a protocol does not relieve the owner/operator and the testing
contractor from strict adherence to all applicable EPA methods, DAQ policies,
Utah Air Quality Rules (UAQR), and methods approved by the Director. Any
deviation from EPA methods, DAQ policies, UAQR, and methods approved by the
Director must be addressed separately and express written consent given prior to
commencement of testing.
• Field data (Point Source emission data and test data) shall be turned over to the
DAQ in a timely manner for review.
• The Director will determine the relative accuracy of each monitoring system based
on Point Source continuous emission monitoring data and test data acquired by the
staff member of the DAQ during the test.
• All test reports must be submitted to the Director not later than 60 days after
completion of the test.
• The test report shall include all raw calibration data and raw emission data with
date and time stamps.
Relative accuracy test reports must contain:
1. Point source continuous monitor, channel, manufacturer, and serial number.
2. Raw stack test data and continuous monitor data with date and time stamps.
3. Emission data reported in concentration (ppm or %) and units in the applicable
emission limit.
The DAQ requires that all test reports include a statement signed by a responsible official
certifying that:
1. Testing was conducted while the Point Source was operating at the rate and/or
conditions specified in the applicable approval order, operating permit, or federal
regulation.
2. During testing, the Point Source combusted fuels, used raw materials, and maintained
process conditions representative of normal operations, and operated under such other
relevant conditions specified by the Director.
DAQC-317-25
Page 3
3. Based on information and belief formed after reasonable inquiry, the statements and
information contained in the report are true, accurate, and complete.
Should you have any questions concerning this matter, contact me at (801) 536-4438 or by email
at rleishman@utah.gov.
Sincerely,
Rob Leishman, Environmental Scientist
Major Source Compliance Section
RL:jl
cc: Salt Lake County Health Department
Alliance Technical Group, LLC
* $ . # ( ) - — - A E v A ? A D @ ? w ? D ˜
Rob Leishman Jr