HomeMy WebLinkAboutDDW-2025-002847
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Nathan Lunstad, Ph.D., P.E.
Director, Division of Drinking Water
January 14, 2025
Scott Hansen
Austin SSD
P.O. Box 408
Elsinore, UT 84724
Subject: Corrective Action Plan Extension for Austin SSD, UTAH21003 (2025-01)
Dear Scott Hansen:
The Division of Drinking Water, (the Division) has received your request for an extension to the
Corrective Action Plan granted to Austin SSD on October 20, 2022. Please review the extension
agreement and sign the attached agreement. Once the extension agreement has been signed by the
water system and the Division, then a copy of the fully executed document will be returned to you.
Please contact Brandi Smith at (385) 515-1650 or brandismith@utah.gov if you have any questions
regarding this letter or the enclosed copy of Corrective Action Plan.
Sincerely,
Helen Lau
Compliance and Operations Manager
Division of Drinking Water
Enclosures –Austin SSD Corrective Action Plan Extension 2025-01
cc: Eric Larsen, Central Utah Health Department, elarsen@centralutahhealth.org
John Chartier, P.E. District Engineer, Division of Drinking Water, jchartier@utah.gov
Scott Hansen, Austin SSD, 6333212@gmail.com
' ) 0 — ) A @ v A ? A D @ E w C @ ˜
Corrective Action Plan Extension (2025-01)
Austin SSD – UTAH21003
The purpose of this Corrective Action Plan (“CAP”) is to establish terms and conditions of
compliance for Austin SSD (“System”), system number UTAH21003, to take actions and correct
significant deficiencies identified in Exhibit A.
The Corrective Action Plan terms and conditions are described in detail in Exhibit A. As long as
the System complies with every one of the requirements in Exhibit A, the Division will:
• Temporarily allow the extended deadlines for correcting the identified significant
deficiencies,
• Temporarily hold off assessing additional points for failure to fix violations, and
• Temporarily silence the significant deficiencies and hold off reporting those to US EPA.
Nothing in this Corrective Action Plan prohibits the Division from taking further enforcement
actions if the System fails to comply with any of the requirements in Exhibit A or if an imminent
public risk exists in the System.
We, the undersigned parties, agree to the terms, conditions and deadlines set forth in the
Corrective Action Plan (see Exhibit A).
___________________________________ ___________________________________
Helen Lau Scott Hansen
Compliance & Operations Manager Austin SSD
_______________________, 2025 _______________________, 2025
* / / ) . ) — ) A C v A ? A D ? E w B G ˜
Scott Hansen
Helen Lau (Jan 24, 2025 16:02 MST)
CAP Page 1
Exhibit A
Corrective Action Plan Extension Agreement UTAH21003, 2025-01
System Name: Austin SSD
System Number: UTAH21003
Administrative Contact: Scott Hansen
Email: 6333212@gmail.com
Phone Number: 435-633-3212
Reason for Extension: Water system called and said that they have made the corrections but
because of the snow they will not be able to get up there to take photos until the springtime which
management agreed to.
Corrective Action Plan Requirements and Due Dates
Norton Spring (WS001)
Item #1 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
SS14 WS001 Spring box overflow or drain lacks a free fall
of 12-24 inches
R309-515-7(7)(d), R309-545
Corrective Action to be Taken Completion Due Date
Ensure that the spring box overflow or drain has an free fall of 12-24
inches
06/01/2025
Item #2 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
SS07 WS001 Deep rooted vegetation in the spring
collection area
R309-515-7(&)(f)
Corrective Action to be Taken Completion Due Date
Ensure that all the deep-rooted vegetation is removed from the spring
collection area
06/01/2025
Item #3 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
SS08 WS001 Deep Rooted vegetation in the Spring
collection pipes
R309-105-10(4)(a), R309-
515-8(1)(a)
Corrective Action to be Taken Completion Due Date
Ensure that all the deep-rooted vegetation is the Spring Collection pipes
has been removed
06/01/2025
Item #2 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
SS10 WS001 Spring Box lid lacks a gasket R309515-7(7)(d), R309-545-
14(2)
Corrective Action to be Taken Completion Due Date
Ensure that all the spring box lid has an appropriate gasket 06/01/2025