FORM 1.2
PREVENTIVE MAINTENANCE TESTING
SITE OVERVIEW SIGN-OFF FORM
Site: Dugway Proving Ground Start Date: 03FEB2025
Location: Street: Bldg. 4038, Tucker Street, Dugway Complete Date: 06FEB2025
City, State/Country: Utah/USA Incident #: PM25SE5A2RA1
DoDAAC: SE5A2R BE#: 00000305
POC: Gary Morgan
POC Phone No.: Comm: 435-831-2679 DSN: 312-789-2679
Description: PM testing was performed on the systems listed below. Tanks monitored by each system are included
and detailed data sheets are attached, to include RPUID numbers in documents and drawings.
Tank Farm DSL Tank 5660 and DSL Tank 5661 (ATG: Ronan CTM) (IAS: Scully Multiple Liquid Level Panel).
Ditto SSTA UNL Tank 1 and DSL Tank 2 (ATG: Veeder Root TLS-450 Plus).
Main SSTA UNL Tank 1 DSL Tank 2 (ATG: Veeder Root TLS-450 Plus).
Flight Line Storage Jet-A Tank 1 and Jet-A Tank 2.
Tech Certs: Enraf Certified Technician. Veeder Root Certification B41310. ICC# 8761158. MS UST # THB5000.
Utah UST Technician TL482.
Associated Workorder(s):
ATG Verification for Inventory Control
Form 3.1.5 for each ATG monitor or probe replaced or installed within past two years collected from site and
attached to PM Deliverable. ☐ Yes ☒ N/A ☐ No
Section 3.1.5 and Form 3.1.5 for each ATG monitor or probe replaced or installed within past two years provided
Attachment (A) Automation Maintenance Program Energy Help Desk Guidance was provided to the site POC.
☒ Yes ☐ No Provide explanation if No.
Identified problems & Comments (e.g. required maintenance):
English Village SSTA ATG and overfill alarm share power circuit.
Organization: Print Name: Signature: Date:
Contractor Tyrone Davis 10FEB2025
Site Representative Gary Morgan
Site Representative email address: GARY.A.MORGAN14.CIV@ARMY.MIL
On-site expended time (minutes): 960 MINS
**Site representative signature acknowledges responsibility for input of ServiceNow/Helpdesk tickets for the
corrective action(s) listed above. Site shall contact their Service Control Point (SCP) for any assistance needed.
SENS-D-GEN-TEP-02-1.1
28
FORM 3.1.6.1
Validation of NIST Certified Working Tape
Site: Dugway Proving Ground Incident #: PM25SE5A2RA1
Site NIST Certified Tape serial # Date of NIST certification
N/A N/A
Visually inspect the site’s certified working tape-and-bob combination for damage which
includes kinks, worn snap catch, worn bob eye, worn bob tip, and illegible numbers. After the
validation check and the visual inspection, does the tape-and-bob combination meet all the
criteria required for continued use in the manual gauging of fuel tanks? If site personnel do not
have a NIST-certified working tape-and-bob, annotate as, “N/A” in the ‘Pass/Fail’ block and add
comment, accordingly.
Pass/Fail Comments
N/A Site does not have a NIST certified tape and bob.
Validation Check
Site Working Tape Certification points
from NIST-Traceable Certificate
Difference between Certified Tape
and Actual
(Pass =< 3/16'') Cert. Point Actual
15' N/A N/A
30' N/A N/A
45' N/A N/A
60' N/A N/A
75' N/A N/A
90' N/A N/A
100' N/A N/A
Maximum Length of Site’s Certified Tape-and-bob N/A
ATG Contractor NIST-Certified Tape serial # Date of NIST certification
CS17223 3/12/2019
Organization: Print Name: Signature: Date:
Contractor Tyrone Davis 10FEB2025
Site Representative Gary Morgan
SENS-D-GEN-TEP-02-1.1
29
FORM 3.1.6.2
Validation of Working Tapes by Comparison with
Reference Measurement
Site: Dugway Proving Ground Incident #: PM25SE5A2RA1
Site Working Tape serial # Working Tape date of validation
Tape 1 5210-00-526 Lufkin 50’ 2/3/2025
Tape 2 Non NIST Ditto Airfield 2/3/2025
Tape 3 N/A N/A
Tape 4 N/A N/A
Visually inspect the working tape-and-bob combination for damage which includes kinks, worn
snap catch, worn bob eye, worn bob tip, and illegible numbers. After the validation check and
the visual inspection, does the tape-and-bob combination meet all the criteria required for
continued use in the manual gauging of fuel tanks?
Validation Check
Reading on Working
Tape
Master Tape
Certification points
Difference between Working
Tape and Master
(Pass =< 3/16”)
Tape
1
Tape
2
Tape
3
Tape
4
Cert.
Point Actual Tape
1
Tape
2
Tape
3
Tape
4
15’ 15’ N/A N/A 15' 15.0012” <3/16” <3/16” N/A N/A
30’ 30’ N/A N/A 30' 30.0008” <3/16” <3/16” N/A N/A
45’ 45’ N/A N/A 45' 45.0012” <3/16” <3/16” N/A N/A
N/A N/A N/A N/A 60' 60.0021” N/A N/A N/A N/A
N/A N/A N/A N/A 75' 75.0017” N/A N/A N/A N/A
N/A N/A N/A N/A 90' 90.0008” N/A N/A N/A N/A
N/A N/A N/A N/A 100' 100.0000” N/A N/A N/A N/A
Maximum Length of Site’s Working Tape-and-bob 50’ 50’ N/A N/A
Serviceable (Pass/Fail) Pass Pass N/A N/A
Master Used ☐ Site ☒ Contractor
Organization: Print Name: Signature: Date:
Contractor Tyrone Davis 10FEB2025
Site Representative Gary Morgan
SENS-D-GEN-TEP-02-1.1
41
FORM 3.8.2
IAS Sensor Operational Verification Data
Site: Dugway Proving Ground Incident #: PM25SE5A2RA1
Fuel movement could not be performed to activate low level, low-low level, high level or high-high level sensors
Site POC Print Name: Gary Morgan Signature:
IAS Monitor: Scully ST-15-115-WX6 IAS Location: Tank Farm/Storage Building 5666
Checkout for Tank (Tank 5660) Sensor (High-High)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated.
Pass Sensor manually tested by filling
and draining sensor chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
Checkout for Tank (Tank 5660) Sensor (High)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated.
Pass Sensor manually tested by filling
and draining sensor chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
Checkout for Tank (Tank 5660) Sensor (Low)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated. Pass
Sensor manually tested by
draining and filling sensor
chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
SENS-D-GEN-TEP-02-1.1
42
FORM 3.8.2
IAS Sensor Operational Verification Data
Site: Dugway Proving Ground Incident #: PM25SE5A2RA1
Fuel movement could not be performed to activate low level, low-low level, high level or high-high level sensors
Site POC Print Name: Gary Morgan Signature:
IAS Monitor: Scully ST-15-115-WX6 IAS Location: Tank Farm/Storage Building 5666
Checkout for Tank (Tank 5660) Sensor (Low-Low)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated. Pass
Sensor manually tested by
draining and filling sensor
chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
Checkout for Tank (Tank 5661) Sensor (High-High)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated.
Pass Sensor manually tested by filling
and draining sensor chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
Checkout for Tank (Tank 5661) Sensor (High)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated.
Pass Sensor manually tested by filling
and draining sensor chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
SENS-D-GEN-TEP-02-1.1
43
FORM 3.8.2
IAS Sensor Operational Verification Data
Site: Dugway Proving Ground Incident #: PM25SE5A2RA1
Fuel movement could not be performed to activate low level, low-low level, high level or high-high level sensors
Site POC Print Name: Gary Morgan Signature:
IAS Monitor: Scully ST-15-115-WX6 IAS Location: Tank Farm/Storage Building 5666
Checkout for Tank (5661) Sensor (Low)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated. Pass
Sensor manually tested by
draining and filling sensor
chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
Checkout for Tank (5661) Sensor (Low-Low)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
Pass Site unable to move fuel to test.
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated. Pass
Sensor manually tested by
draining and filling sensor
chamber.
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
Pass N/A
4 Record activation setpoint. (Gallons or Level) N/A
Checkout for Tank (N/A) Sensor (N/A)
Item Inspection/Test Description Pass/
Fail
Comments/Test Method
1
Activate switch and note audible and visual alarm notification at
IAS monitor panel and/or local alarm panel. Verify proper
operation of pump and/or valve controllers.
N/A N/A
2
If applicable, press Reset at IAS monitor panel and/or local
alarm panel and confirm that audible alarm turns off, but visual
alarm remains activated.
N/A N/A
3
Restore sensor switch and confirm that alarm indications return
to normal on IAS monitor and/or the local alarm panel. Pump
and/or valve controllers return to normal mode.
N/A N/A
4 Record activation setpoint. (Gallons or Level) N/A