Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
DAQ-2025-001320
1 DAQC-182-25 Site ID 11977 (B4) MEMORANDUM TO: STACK TEST FILE – TRANS-JORDAN CITIES – Landfill Generation THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Robert Sirrine, Environmental Scientist DATE: February 13, 2025 SUBJECT: Location: 1047 South Bacchus Highway, South Jordan, Salt Lake County, Utah Contact: Summer Hitchens, 515-604-1784 Tester: Montrose Air Quality Services, Cheyney Guymon, 801-794-2950 Source: Landfill Gas Generator Engines #1-#3 FRS ID#: UT0000004903500535 Permit# Title V operating permit 3500535004 dated July 21, 2020, last revised January 12, 2023 Action Code: Tr Subject: Review of Stack Test Report received January 29, 2025 On January 29, 2025, the Utah Division of Air Quality (DAQ) received a stack test report for emissions testing of the Trans-Jordan Landfill Generator Engines #1-#3, located in South Jordan, Salt Lake County, Utah. Stack emissions testing was performed on January 14-15, 2025, to determine compliance with Title V operating permit Conditions, II.B.3.a, and II.B.3.c for VOC, CO, and NOX emissions. The DAQ-calculated test results are: Source Test Date RM/Pollutant DAQ Result Test Result Limit Engine #1 1/14/25 7/NOX 0.3 g/bhp-hr 0.29 g/bhp-hr 2.0 lb/bhp-hr 1.31 lb/hr 1.31 g/bhp-hr 1.97 lb/hr 10/CO 2.6 g/bhp-hr 2.64 g/bhp-hr 5.0 g/bhp-hr 25A/VOC 0.0 g/bhp-hr 0.002 g/bhp-hr 1.0 g/bhp-hr Engine #2 1/15/25 7/NOX 0.3 g/bhp-hr 0.32 g/bhp-hr 2.0 g/bhp-hr 1.46 lb/hr 1.46 g/bhp-hr 1.97 lb/hr 10/CO 2.7 g/bhp-hr 2.73 g/bhp-hr 5.0 g/bhp-hr 25A/VOC 0.2 g/bhp-hr 0.19 g/bhp-hr 1.0 g/bhp-hr Engine #3 1/15/25 7/NOX 0.3 g/bhp-hr 0.30 g/bhp-hr 2.0 g/bhp-hr 1.34 lb/hr 1.34 g/bhp-hr 1.97 lb/hr 10/CO 2.7 g/bhp-hr 2.67 g/bhp-hr 5.0 g/bhp-hr 25A/VOC 0.2 g/bhp-hr 0.21 g/bhp-hr 1.0 g/bhp-hr * - / $ - - $ ) 2 DEVIATIONS: No deviations were noted. CONCLUSION: The stack test report appears to be acceptable. RECOMMENDATION: Trans-Jordan Landfill gas powered engines #1-#3 should be considered to have been in compliance with the VOC, CO, and NOX emission limits at the time of testing. No further action is recommended. HPV: No. ATTACHMENTS: Stack test report received January 29, 2025 DAQ generated excel spreadsheets Trans Jordan E 1 CO VOC and NOx 2025 rev Reference Methods 2, 3A, 6C, 7E, 10, & 19 Source Information Company Name Trans-Jordan Cities Ladfill Generation Company Contact:Summer Hitchen Contact Phone No.517-604-1784 Stack Designation:Landfil Gas Engine #1 Test & Review Dates Test Date:1/14/2025 Review Date: 2/10/2025 Observer:none Reviewer:Robert Sirrine Emission Limits Emission Rates VOC NOX CO VOC NOX CO g/bhp-hr 1.0 2.0 5.0 0.002 0.3 2.6 lbs./hr. 1.0 2.0 1.0 0.01 1.31 11.75 ppm Percent %O2 Correction as a whole # Test Information Stack I.D. inches As ft^2 Y Dl H @ Cp Pbar Pq (static) Ps Stack Pressure 12.75 0.887 1.0130 1.732 0.84 25.14 10 Contractor Information Contact:Austin Keough Contracting Company: Alliance Source Testing Address: 2855S 500 W Sutie A, Salt Lake City, Utah 84115 Phone No.: (385) 722-6712 Project No.: 8710 Division of Air Quality Instrumental Reference Methods - Gaseous Measurements Round Method 19 - F factors for Coal, Oil, and Gas Fd Fw Fc dscf/MMBtu wscf/MMBtu scf/MMBtu Diluent F factor used O2 CO2 Anthracite 2 Bituminous 2 Lignite Natural Propane Butane 10100 COAL OIL GAS 9780 9860 9190 8710 8710 8710 10540 10640 11950 320 10610 10200 10390 1970 1800 1910 1420 1040 1190 1250 Wet CEM Correct For O2 CO2 Interference w/CO Yes Yes Yes Trans Jordan E 1 CO VOC and NOx 2025 rev Division of Air Quality NSPS Relative Accuracy Performance Specification Test - CEMS Certification Trans-Jordan Cities Ladfill Generation Landfil Gas Engine #1 Average Emission Dry VOC NOX CO g/HP-hr 0.0022 0.29 2.61 Average % concentration lbs./hr.0.010 1.31 11.75 CO2 O2 ppm or % 0.36 44.44 662.53 10.82 8.61 Run 1 Enter O2 or CO2 Dry VOC NOX CO CO2 O2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)5.57E-04 7.73E-02 7.08E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 3.779E-08 5.244E-06 4.804E-05 lbs./hr.0.009 1.27 11.64 10.97 8.55 ppm or %0.33 43.90 660.67 10.60 8.48 Run 2 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)6.03E-04 7.92E-02 7.34E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 4.065E-08 5.341E-06 4.946E-05 lbs./hr.0.010 1.31 12.100 10.80 8.63 ppm or %0.36 44.72 680.29 10.60 8.50 Raw Value Run 3 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)6.84E-04 7.95E-02 7.00E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 4.592E-08 5.339E-06 4.702E-05 lbs./hr.0.011 1.31 11.50 10.70 8.67 ppm or %0.40 44.70 646.62 10.30 8.50 Raw Value Run 4 Dry VOC NOX CO CO2 O2 Atomic Weight 64 46 28 lbs./MMBtu (O2)E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft lbs./hr. ppm or %Raw Value Corrected For Cal. Drift Raw Value Corrected For Cal. Drift Corrected For Cal. Drift Corrected For Cal. Drift O2 CO2 Clear lbs./MMBTU Trans Jordan E 1 CO VOC and NOx 2025 rev Calibration Error Test Test Date January 14, 2025 O2 CS - Cal. Span 19.66 Units % Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.51% Passed Cal. Mid-level 10.09 10.00 0.09 0.46% Passed Cal. High-level 19.66 19.60 0.06 0.31% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of CS - Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 51.32% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 CO2 CS - Cal. Span 11.70 Units % Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.00 0.00 0.000% Passed Cal. Mid-level 5.99 6.00 0.01 0.085% Passed Cal. High-level 11.70 11.70 0.00 0.000% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 51.20% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 VOC CS - Cal. Span 51.69Unitsppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.30 0.30 0.580% Passed Cal. Mid-level 30.20 29.70 0.50 0.967% Passed Cal. High-level 51.69 51.10 0.59 1.141% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 58.43% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 NOx CS - Cal. Span 95.60 Units ppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.105% Passed Cal. Mid-level 51.00 50.10 0.90 0.941% Passed Cal. High-level 95.60 95.70 0.10 0.105% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 53.35% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 CO 1 CS - Cal. Span 1,238.00 Units ppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.00 0.00 0.000% Passed Cal. Mid-level 512.00 511.20 0.80 0.065% Passed Cal. High-level 1,238.00 1,239.30 1.30 0.105% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 41.36% 100% of Cal. Span High-level 100.00% Trans Jordan E 1 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #1 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % Unprotected CV - Cylinder Value: VOC NOX CO CO2 O2 Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3%100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CDir CMA 30.20 51.00 512.00 5.99 10.09 Calibration Error Test Cs - Measured Concentration VOC NOX CO CO2 O2Low-Level 0.30 0.10 0.00 0.00 0.10 Mid-Level 29.70 50.10 511.20 6.00 10.00 High-Level 51.10 95.70 1239.30 11.70 19.60 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 29.70 50.10 511.20 6.00 10.00 Low-Level 0.58% 0.10% 0.00% 0.00% 0.51% ppmdv Difference 0.3 0.1 0 0 0.1StatusPassed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.97% 0.94% 0.06% 0.09% 0.46% ppmdv Difference 0.5 0.9 0.8 0.01 0.09 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.10% 0.11% 0.00% 0.31% ppmdv Difference 0.59 0.1 1.3 0 0.06 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.30 0.30 0.20 0.20 0.20 System Bias. SBi - Zero Bias 0.00% 0.21% 0.02% 1.71% 0.51%± 5% of Span Difference 0 0.2 0.2 0.2 0.1 Pass or Failed Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 29.70 49.50 502.70 5.90 10.00 SBi - Up-Scale Bias 0.00% 0.63% 0.69% 0.85% 0.00% Difference 0.00 0.60 8.50 0.10 0.00 Pass or Failed Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/14/2025 SO2 VOC NOX CO CO2 O2 NOX 0.3 42.60 654.90 10.60 8.48 CO 0.6% 44.6% 52.9% 90.6% 43.1% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.10 0.10 0.00 0.30 0.10 System Bias. SBi - Zero Bias 0.39% 0.00% 0.00% 2.56% 0.00%± 5% of Span Difference 0.2 0.0 0.0 0.3 0.0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 29.60 49.50 512.40 5.90 10.00 SBi - Up-Scale Bias 0.19% 0.63% 0.10% 0.85% 0.00% Difference 0.1 0.6 1.2 0.1 0.0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.39% 0.21% 0.02% 0.85% 0.51% Drift Difference 0.2 0.2 0.2 0.1 0.1 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 0.19% 0.00% 0.59% 0.00% 0.00% Difference 0.1 0.0 9.7 0.0 0.0Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #1 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.887 25.14 10.00 25.88 899.33 10.97 8.55 80.48 30.10 28.77 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 694.4304 1.0130 0.84 41.240 91.60 70.87 34.898 4.312 0.1100 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs (ft./sec.)Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6150 253.76 272,197 268 242,265.19 17.75904 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.88 2.620 898 60 61 739.70 705.90 33.80 2 6.81 2.610 899 64 60 744.00 707.60 36.40 3 900 69 61 620.80 609.80 11.00 4 901 72 62 865.50 855.10 10.40 5 899 75 63 6 900 79 64 2970.00 2878.40 Sum 7 899 81 65 8 899 83 66 9 900 84 67 10 899 85 68 11 898 86 69 12 900 87 70 13 14 15 16 17 18 19 2021 22 23 24 NOTEThese cells scans for the appropriate Cir. gas after the Cm If this scan is incorrect change the Cdir to the correct gas value. Failed Bias Dialog Failed Drift Dialog Failed Cal Error Dialog CO Calibration Gas Failed Bias Dialog Trans Jordan E 1 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #1 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % CV - Cylinder Value: VOC NOX CO CO2 O2Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3% 100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CMA 30.20 51.00 512.00 5.99 10.09 Calibration Error Test Measured Concentration VOC NOX CO CO2 O2Low-Level 0.30 0.10 0.00 0.00 0.10 Mid-Level 29.70 50.10 511.20 6.00 10.00 High-Level 51.10 95.70 1239.30 11.70 19.60 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 29.70 50.10 511.20 6.00 10.00 Low-Level 0.58% 0.10% 0.00% 0.00% 0.51% ppmdv Difference 0.3 0.1 0 0 0.1 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.97% 0.94% 0.06% 0.09% 0.46% ppmdv Difference 0.5 0.9 0.8 0.01 0.09 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.10% 0.11% 0.00% 0.31% ppmdv Difference 0.59 0.1 1.3 0 0.06 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.10 0.10 0.00 0.30 0.10 System Bias. SBi - Zero Bias 0.39% 0.00% 0.00% 2.56% 0.00%± 5% of Span Difference 0.2 0 0 0.3 0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 29.60 49.50 512.40 5.90 10.00 SBi - Up-Scale Bias 0.19% 0.63% 0.10% 0.85% 0.00% Difference 0.1 0.6 1.2 0.1 0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/14/2025 SO2 VOC NOX CO CO2 O2 NOX0.4 43.20 668.40 10.40 8.50 CO 0.8% 45.2% 54.0% 88.9% 43.2% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.00 0.20 0.00 0.30 0.00 System Bias. SBi - Zero Bias 0.58% 0.10% 0.00% 2.56% 0.51%± 5% of Span Difference 0.3 0.1 0.0 0.3 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 30.10 49.00 493.70 5.90 9.90 SBi - Up-Scale Bias 0.77% 1.15% 1.41% 0.85% 0.51% Difference 0.4 1.1 17.5 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.19% 0.10% 0.00% 0.00% 0.51% Response Spec. Difference 0.1 0.1 0.0 0.0 0.1 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 0.58% 0.52% 1.32% 0.00% 0.51% Difference 0.5 0.5 18.7 0.0 0.1Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #1 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.89 25.62 10.00 26.36 899 10.80 8.63 80.57 30.07 28.68 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 679.3253 1.0130 0.84 41.720 97.60 79 35.416 4.594 0.1148 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6260 252.79 276,355 272 244,623.51 17.9088 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.81 2.610 896 70 69 750.40 708.80 41.60 2 6.98 2.642 897 75 69 716.60 681.30 35.30 3 898 81 70 618.30 607.60 10.70 4 898 85 70 873.70 863.70 10.00 5 899 87 71 6 899 88 72 2959.00 2861.40 Sum 7 898 89 73 8 899 91 73 9 899 91 74 10 901 92 75 11 900 93 76 12 898 93 77 1314 15 16 17 18 19 20 2122 23 24 Failed Bias Dialog Failed Drift Dialog Failed Cal Error Dialog Failed Bias Dialog Trans Jordan E 1 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #1 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % CV - Cylinder Value: VOC NOX CO CO2 O2Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3% 100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CMA 30.20 51.00 512.00 5.99 10.09 Calibration Error Test Measured Concentration VOC NOX CO CO2 O2Low-Level 0.30 0.10 0.00 0.00 0.10 Mid-Level 29.70 50.10 511.20 6.00 10.00 High-Level 51.10 95.70 1239.30 11.70 19.60 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 29.70 50.10 511.20 6.00 10.00 Low-Level 0.58% 0.10% 0.00% 0.00% 0.51% ppmv Difference 0.3 0.1 0 0 0.1 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.97% 0.94% 0.06% 0.09% 0.46% ppmv Difference 0.5 0.9 0.8 0.01 0.09 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.10% 0.11% 0.00% 0.31% ppmv Difference 0.59 0.1 1.3 0 0.06 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.00 0.20 0.00 0.30 0.00 System Bias. SBi - Zero Bias 0.58% 0.10% 0.00% 2.56% 0.51%± 5% of Span Difference 0.3 0.1 0 0.3 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 30.10 49.00 493.70 5.90 9.90 SBi - Up-Scale Bias 0.77% 1.15% 1.41% 0.85% 0.51% Difference 0.4 1.1 17.5 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/14/2025 SO2 VOC NOX CO CO2 O2 NOX0.4 43.40 635.70 10.30 8.50 CO 0.8% 45.4% 51.3% 88.0% 43.2% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.00 0.00 0.00 0.30 0.10 System Bias. SBi - Zero Bias 0.58% 0.10% 0.00% 2.56% 0.00%± 5% of Span Difference 0.3 0.1 0.0 0.3 0.0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 30.20 50.10 513.00 5.90 9.90 SBi - Up-Scale Bias 0.97% 0.00% 0.15% 0.85% 0.51% Difference 0.5 0.0 1.8 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.00% 0.00% 0.00% 0.00% 0.51% Response Spec. Difference 0.0 0.2 0.0 0.0 0.1 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 0.19% 1.15% 1.27% 0.00% 0.00% Difference 0.1 1.1 19.3 0.0 0.0Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #1 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.89 25.14 10.00 25.88 898 10.70 8.67 80.63 30.06 28.74 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 690.4220 1.0130 0.84 41.920 90.30 83 34.656 4.250 0.1092 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6355 255.74 274,589 270 244,591.19 17.85888 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.98 2.642 899 76 75 775.20 739.70 35.50 2 6.91 2.629 897 80 75 777.60 744.00 33.60 3 896 86 76 632.60 620.80 11.80 4 897 89 76 874.90 865.50 9.40 5 898 91 76 6 898 92 77 3060.30 2970.00 Sum 7 898 93 77 8 899 93 78 9 898 94 78 10 898 94 79 11 899 94 79 12 899 95 79 1314 15 16 17 18 19 20 2122 23 24 Failed Bias Dialog Failed Cal Error Dialog Failed Drift Dialog Failed Bias Dialog Trans Jordan E 2 CO VOC and NOx 2025 rev Reference Methods 2, 3A, 6C, 7E, 10, & 19 Source Information Company Name Trans-Jordan Cities Ladfill Generation Company Contact:Summer Hitchen Contact Phone No.517-604-1784 Stack Designation:Landfil Gas Engine #2 Test & Review Dates Test Date:1/14/2025 Review Date: 2/12/2025 Observer:none Reviewer:Robert Sirrine Emission Limits Emission Rates VOC NOX CO VOC NOX CO g/bhp-hr 1.0 2.0 5.0 0.19 0.32 2.70 lbs./hr. 1.0 2.0 1.0 0.85 1.46 12.16 ppm Percent %O2 Correction as a whole # Test Information Stack I.D. inches As ft^2 Y Dl H @ Cp Pbar Pq (static) Ps Stack Pressure 12.75 0.887 1.0130 1.732 0.84 25.14 12 Contractor Information Contact:Austin Keough Contracting Company: Alliance Source Testing Address: 2855S 500 W Sutie A, Salt Lake City, Utah 84115 Phone No.: (385) 722-6712 Project No.: 8710 Division of Air Quality Instrumental Reference Methods - Gaseous Measurements Round Method 19 - F factors for Coal, Oil, and Gas Fd Fw Fc dscf/MMBtu wscf/MMBtu scf/MMBtu Diluent F factor used O2 CO2 Anthracite 2 Bituminous 2 Lignite Natural Propane Butane 10100 COAL OIL GAS 9780 9860 9190 8710 8710 8710 10540 10640 11950 320 10610 10200 10390 1970 1800 1910 1420 1040 1190 1250 Wet CEM Correct For O2 CO2 Interference w/CO Yes Yes Yes Trans Jordan E 2 CO VOC and NOx 2025 rev Division of Air Quality NSPS Relative Accuracy Performance Specification Test - CEMS Certification Trans-Jordan Cities Ladfill Generation Landfil Gas Engine #2 Average Emission Dry VOC NOX CO g/HP-hr 0.19 0.32 2.70 Average % concentration lbs./hr.0.85 1.46 12.16 CO2 O2 ppm or % 26.93 49.39 683.17 10.91 8.67 Run 1 Enter O2 or CO2 Dry VOC NOX CO CO2 O2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)4.45E-02 8.94E-02 7.71E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 2.977E-06 5.988E-06 5.161E-05 lbs./hr.0.81 1.46 12.56 10.91 8.71 ppm or %26.00 50.13 709.88 10.50 8.50 Run 2 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)4.58E-02 8.87E-02 7.29E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 3.080E-06 5.963E-06 4.903E-05 lbs./hr.0.85 1.47 12.10 11.01 8.66 ppm or %26.90 49.92 674.27 10.50 8.50 Raw Value Run 3 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)4.75E-02 8.55E-02 7.19E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 3.195E-06 5.749E-06 4.838E-05 lbs./hr.0.88 1.41 11.83 10.80 8.66 ppm or %27.90 48.13 665.35 10.40 8.50 Raw Value Run 4 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft lbs./hr. ppm or %Raw Value Corrected For Cal. Drift Raw Value Corrected For Cal. Drift Corrected For Cal. Drift Corrected For Cal. Drift O2 CO2 Clear lbs./MMBTU Trans Jordan E 2 CO VOC and NOx 2025 rev Calibration Error Test Test Date January 14, 2025 O2 CS - Cal. Span 19.66 Units % Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.51% Passed Cal. Mid-level 10.09 10.00 0.09 0.46% Passed Cal. High-level 19.66 19.60 0.06 0.31% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of CS - Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 51.32% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 CO2 CS - Cal. Span 11.70 Units % Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.00 0.00 0.000% Passed Cal. Mid-level 5.99 6.00 0.01 0.085% Passed Cal. High-level 11.70 11.70 0.00 0.000% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 51.20% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 VOC CS - Cal. Span 51.69Unitsppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.30 0.30 0.580% Passed Cal. Mid-level 30.20 29.70 0.50 0.967% Passed Cal. High-level 51.69 51.10 0.59 1.141% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 58.43% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 NOx CS - Cal. Span 95.60 Units ppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.105% Passed Cal. Mid-level 51.00 50.10 0.90 0.941% Passed Cal. High-level 95.60 95.70 0.10 0.105% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 53.35% 100% of Cal. Span High-level 100.00% Test Date January 14, 2025 CO 1 CS - Cal. Span 1,238.00 Units ppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.00 0.00 0.000% Passed Cal. Mid-level 512.00 511.20 0.80 0.065% Passed Cal. High-level 1,238.00 1,239.30 1.30 0.105% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 41.36% 100% of Cal. Span High-level 100.00% Trans Jordan E 2 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #2 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % Unprotected CV - Cylinder Value: VOC NOX CO CO2 O2 Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3%100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CDir CMA 51.69 51.00 512.00 5.99 10.09 Calibration Error Test Cs - Measured Concentration VOC NOX CO CO2 O2Low-Level 0.30 0.10 0.00 0.00 0.10 Mid-Level 29.70 50.10 511.20 6.00 10.00 High-Level 51.10 95.70 1239.30 11.70 19.60 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 51.10 50.10 511.20 6.00 10.00 Low-Level 0.58% 0.10% 0.00% 0.00% 0.51% ppmdv Difference 0.3 0.1 0 0 0.1StatusPassed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.97% 0.94% 0.06% 0.09% 0.46% ppmdv Difference 0.5 0.9 0.8 0.01 0.09 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.10% 0.11% 0.00% 0.31% ppmdv Difference 0.59 0.1 1.3 0 0.06 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.00 0.00 0.00 0.30 0.10 System Bias. SBi - Zero Bias 0.58% 0.10% 0.00% 2.56% 0.00%± 5% of Span Difference 0.3 0.1 0 0.3 0 Pass or Failed Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 51.10 50.10 513.00 5.90 9.80 SBi - Up-Scale Bias 0.00% 0.00% 0.15% 0.85% 1.02% Difference 0.00 0.00 1.80 0.10 0.20 Pass or Failed Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/14/2025 SO2 VOC NOX CO CO2 O2 NOX 26.0 49.10 710.40 10.50 8.50 CO 50.3% 51.4% 57.4% 89.7% 43.2% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.10 0.20 0.30 0.10 System Bias. SBi - Zero Bias 0.19% 0.00% 0.02% 2.56% 0.00%± 5% of Span Difference 0.1 0.0 0.2 0.3 0.0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 49.30 49.80 511.80 5.90 9.90 SBi - Up-Scale Bias 3.48% 0.31% 0.05% 0.85% 0.51% Difference 1.8 0.3 0.6 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.39% 0.10% 0.02% 0.00% 0.00% Drift Difference 0.2 0.1 0.2 0.0 0.0 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 3.48% 0.31% 0.10% 0.00% 0.51% Difference 1.8 0.3 1.2 0.0 0.1Pass or Re-Calibrate Re-Cal. Pass Pass Pass Pass Landfil Gas Engine #2 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.887 25.14 12.00 26.02 894 10.91 8.71 80.38 30.09 28.76 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 673.1447 1.0130 0.84 42.620 93.60 76.29 35.702 4.406 0.1098 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs (ft./sec.)Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6130 252.34 273,384 269 243,353.78 17.75904 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.83 2.613 899 70 70 818.00 750.40 67.60 2 896 70 68 733.10 716.60 16.50 3 894 77 68 620.50 618.30 2.20 4 891 80 69 881.00 873.70 7.30 5 891 82 69 6 890 84 70 3052.60 2959.00 Sum 7 85 70 8 87 71 9 87 71 10 88 72 11 89 72 12 89 73 13 14 15 16 17 18 19 2021 22 23 24 NOTEThese cells scans for the appropriate Cir. gas after the Cm If this scan is incorrect change the Cdir to the correct gas value. Failed Bias Dialog Failed Drift Dialog Failed Cal Error Dialog CO Calibration Gas Failed Bias Dialog Trans Jordan E 2 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #2 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % CV - Cylinder Value: VOC NOX CO CO2 O2Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3% 100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CMA 51.69 51.00 512.00 5.99 10.09 Calibration Error Test Measured Concentration VOC NOX CO CO2 O2Low-Level 0.30 0.10 0.00 0.00 0.10 Mid-Level 29.70 50.10 511.20 6.00 10.00 High-Level 51.10 95.70 1239.30 11.70 19.60 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 51.10 50.10 511.20 6.00 10.00 Low-Level 0.58% 0.10% 0.00% 0.00% 0.51% ppmdv Difference 0.3 0.1 0 0 0.1 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.97% 0.94% 0.06% 0.09% 0.46% ppmdv Difference 0.5 0.9 0.8 0.01 0.09 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.10% 0.11% 0.00% 0.31% ppmdv Difference 0.59 0.1 1.3 0 0.06 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.10 0.20 0.30 0.10 System Bias. SBi - Zero Bias 0.19% 0.00% 0.02% 2.56% 0.00%± 5% of Span Difference 0.1 0 0.2 0.3 0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 49.30 49.80 511.80 5.90 9.90 SBi - Up-Scale Bias 3.48% 0.31% 0.05% 0.85% 0.51% Difference 1.8 0.3 0.6 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/14/2025 SO2 VOC NOX CO CO2 O2 NOX26.9 48.80 675.00 10.50 8.50 CO 52.0% 51.0% 54.5% 89.7% 43.2% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.30 0.20 0.30 0.20 System Bias. SBi - Zero Bias 0.19% 0.21% 0.02% 2.56% 0.51%± 5% of Span Difference 0.1 0.2 0.2 0.3 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 49.70 49.90 513.40 5.80 9.90 SBi - Up-Scale Bias 2.71% 0.21% 0.18% 1.71% 0.51% Difference 1.4 0.2 2.2 0.2 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.00% 0.21% 0.00% 0.00% 0.51% Response Spec. Difference 0.0 0.2 0.0 0.0 0.1 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 0.77% 0.10% 0.13% 0.85% 0.00% Difference 0.4 0.1 1.6 0.1 0.0Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #2 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.89 25.62 12.00 26.50 892 11.01 8.66 80.34 30.11 28.78 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 656.6122 1.0130 0.84 42.250 94.00 79 35.919 4.425 0.1097 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6245 250.92 277,168 273 246,769.96 17.9088 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.84 2.615 890 70 69 732.60 688.60 44.00 2 6.94 2.634 893 75 70 777.00 745.20 31.80 3 893 81 70 640.60 632.60 8.00 4 893 84 70 901.30 891.10 10.20 5 892 86 71 6 893 88 72 3051.50 2957.50 Sum 7 893 88 72 8 891 89 73 9 893 89 73 10 892 94 74 11 892 90 74 12 889 90 74 1314 15 16 17 18 19 20 2122 23 24 Failed Bias Dialog Failed Drift Dialog Failed Cal Error Dialog Failed Bias Dialog Trans Jordan E 2 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #2 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % CV - Cylinder Value: VOC NOX CO CO2 O2Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3% 100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CMA 51.69 51.00 512.00 5.99 10.09 Calibration Error Test Measured Concentration VOC NOX CO CO2 O2Low-Level 0.30 0.10 0.00 0.00 0.10 Mid-Level 29.70 50.10 511.20 6.00 10.00 High-Level 51.10 95.70 1239.30 11.70 19.60 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 51.10 50.10 511.20 6.00 10.00 Low-Level 0.58% 0.10% 0.00% 0.00% 0.51% ppmv Difference 0.3 0.1 0 0 0.1 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.97% 0.94% 0.06% 0.09% 0.46% ppmv Difference 0.5 0.9 0.8 0.01 0.09 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.10% 0.11% 0.00% 0.31% ppmv Difference 0.59 0.1 1.3 0 0.06 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.30 0.20 0.30 0.20 System Bias. SBi - Zero Bias 0.19% 0.21% 0.02% 2.56% 0.51%± 5% of Span Difference 0.1 0.2 0.2 0.3 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 49.70 49.90 513.40 5.80 9.90 SBi - Up-Scale Bias 2.71% 0.21% 0.18% 1.71% 0.51% Difference 1.4 0.2 2.2 0.2 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/14/2025 SO2 VOC NOX CO CO2 O2 NOX27.9 47.20 665.40 10.40 8.50 CO 54.0% 49.4% 53.7% 88.9% 43.2% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.30 0.30 0.30 0.10 System Bias. SBi - Zero Bias 0.19% 0.21% 0.02% 2.56% 0.00%± 5% of Span Difference 0.1 0.2 0.3 0.3 0.0 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 49.30 50.10 510.80 6.00 9.90 SBi - Up-Scale Bias 3.48% 0.00% 0.03% 0.00% 0.51% Difference 1.8 0.0 0.4 0.0 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.00% 0.00% 0.01% 0.00% 0.51% Response Spec. Difference 0.0 0.0 0.1 0.0 0.1 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 0.77% 0.21% 0.15% 1.71% 0.00% Difference 0.4 0.2 2.6 0.2 0.0Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #2 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.89 25.14 12.00 26.02 889 10.80 8.66 80.54 30.07 28.67 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 660.2301 1.0130 0.84 42.090 98.10 79 35.093 4.618 0.1163 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6360 254.57 276,700 272 244,525.14 17.85888 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.94 2.634 893 71 70 789.70 718.80 70.90 2 6.96 2.638 889 76 70 749.30 733.10 16.20 3 890 82 70 622.60 620.50 2.10 4 890 85 71 884.60 875.70 8.90 5 888 87 71 6 887 88 72 3046.20 2948.10 Sum 7 888 89 73 8 888 89 73 9 889 90 74 10 890 90 74 11 889 90 74 12 889 90 74 1314 15 16 17 18 19 20 2122 23 24 Failed Bias Dialog Failed Cal Error Dialog Failed Drift Dialog Failed Bias Dialog Trans Jordan E 3 CO VOC and NOx 2025 rev Reference Methods 2, 3A, 6C, 7E, 10, & 19 Source Information Company Name Trans-Jordan Cities Ladfill Generation Company Contact:Summer Hitchen Contact Phone No.517-604-1784 Stack Designation:Landfil Gas Engine #3 Test & Review Dates Test Date:1/15/2025 Review Date: 2/12/2025 Observer:none Reviewer:Robert Sirrine Emission Limits Emission Rates VOC NOX CO VOC NOX CO g/bhp-hr 1.0 2.0 5.0 0.21 0.30 2.65 lbs./hr. 1.0 2.0 1.0 0.96 1.33 11.92 ppm Percent %O2 Correction as a whole # Test Information Stack I.D. inches As ft^2 Y Dl H @ Cp Pbar Pq (static) Ps Stack Pressure 12.75 0.887 1.0130 1.732 0.84 25.21 9 Contractor Information Contact:Austin Keough Contracting Company: Alliance Source Testing Address: 2855S 500 W Sutie A, Salt Lake City, Utah 84115 Phone No.: (385) 722-6712 Project No.: 8710 Division of Air Quality Instrumental Reference Methods - Gaseous Measurements Round Method 19 - F factors for Coal, Oil, and Gas Fd Fw Fc dscf/MMBtu wscf/MMBtu scf/MMBtu Diluent F factor used O2 CO2 Anthracite 2 Bituminous 2 Lignite Natural Propane Butane 10100 COAL OIL GAS 9780 9860 9190 8710 8710 8710 10540 10640 11950 320 10610 10200 10390 1970 1800 1910 1420 1040 1190 1250 Wet CEM Correct For O2 CO2 Interference w/CO Yes Yes Yes Trans Jordan E 3 CO VOC and NOx 2025 rev Division of Air Quality NSPS Relative Accuracy Performance Specification Test - CEMS Certification Trans-Jordan Cities Ladfill Generation Landfil Gas Engine #3 Average Emission Dry VOC NOX CO g/HP-hr 0.21 0.30 2.7 Average % concentration lbs./hr.0.96 1.33 11.92 CO2 O2 ppm or % 29.83 44.50 655.39 10.67 8.62 Run 1 Enter O2 or CO2 Dry VOC NOX CO CO2 O2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)5.20E-02 7.75E-02 7.21E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 3.525E-06 5.248E-06 4.885E-05 lbs./hr.0.98 1.29 12.10 10.97 8.57 ppm or %30.78 43.93 671.79 10.50 8.40 Run 2 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)5.35E-02 7.81E-02 6.86E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 3.607E-06 5.270E-06 4.626E-05 lbs./hr.1.02 1.33 11.70 10.59 8.62 ppm or %31.50 44.12 636.25 10.50 8.40 Raw Value Run 3 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)4.63E-02 8.08E-02 7.12E-01 E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft 3.115E-06 5.429E-06 4.785E-05 lbs./hr.0.88 1.36 12.00 10.44 8.66 ppm or %27.20 45.45 658.14 10.00 8.40 Raw Value Run 4 Dry VOC NOX CO CO2 O2 Atomic Weight 44.1 46 28 lbs./MMBtu (O2)E=Cd x Fd x (20.9/(20.9-%O2d)) lbs./MMBtu (CO2)E=Cd x Fc x (100 / % CO2d) lbs./cu.ft lbs./hr. ppm or %Raw Value Corrected For Cal. Drift Raw Value Corrected For Cal. Drift Corrected For Cal. Drift Corrected For Cal. Drift O2 CO2 Clear lbs./MMBTU Trans Jordan E 3 CO VOC and NOx 2025 rev Calibration Error Test Test Date January 15, 2025 O2 CS - Cal. Span 19.66 Units % Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.51% Passed Cal. Mid-level 10.09 10.20 0.11 0.56% Passed Cal. High-level 19.66 19.70 0.04 0.20% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of CS - Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 51.32% 100% of Cal. Span High-level 100.00% Test Date January 15, 2025 CO2 CS - Cal. Span 11.70 Units % Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.855% Passed Cal. Mid-level 5.99 5.80 0.19 1.624% Passed Cal. High-level 11.70 11.80 0.10 0.855% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 51.20% 100% of Cal. Span High-level 100.00% Test Date January 15, 2025 VOC CS - Cal. Span 51.69Unitsppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.20 0.20 0.387% Passed Cal. Mid-level 30.20 30.20 0.00 0.000% Passed Cal. High-level 51.69 51.10 0.59 1.141% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 58.43% 100% of Cal. Span High-level 100.00% Test Date January 15, 2025 NOx CS - Cal. Span 95.60 Units ppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.10 0.10 0.105% Passed Cal. Mid-level 51.00 50.10 0.90 0.941% Passed Cal. High-level 95.60 95.60 0.00 0.000% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 53.35% 100% of Cal. Span High-level 100.00% Test Date January 15, 2025 CO 1 CS - Cal. Span 1,238.00 Units ppm Cylinder No. Expiration Date Cal. Gas CV- Certified Concentration CDir or CS - Measured Concentration Difference ACE Eq. 7E-1 Analyzer Cal. Error Status Low-level 0.00 0.00 0.00 0.000% Passed Cal. Mid-level 512.00 504.50 7.50 0.606% Passed Cal. High-level 1,238.00 1,241.90 3.90 0.315% Passed Cal. % of Span Sec. 8.2.1 Cal Gas Verification 0 to 20% of Cal. Span Low-Level 0.00% 40 to 60% of Cal. Span Mid-level 41.36% 100% of Cal. Span High-level 100.00% Trans Jordan E 3 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #3 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % Unprotected CV - Cylinder Value: VOC NOX CO CO2 O2 Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3%100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CDir CMA 51.69 51.00 512.00 5.99 10.09 Calibration Error Test Cs - Measured Concentration VOC NOX CO CO2 O2Low-Level 0.20 0.10 0.00 0.10 0.10 Mid-Level 30.20 50.10 504.50 5.80 10.20 High-Level 51.10 95.60 1241.90 11.80 19.70 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 51.10 50.10 504.50 5.80 10.20 Low-Level 0.39% 0.10% 0.00% 0.85% 0.51% ppmdv Difference 0.2 0.1 0 0.1 0.1StatusPassed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.00% 0.94% 0.61% 1.62% 0.56% ppmdv Difference 0 0.9 7.5 0.19 0.11 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.00% 0.32% 0.85% 0.20% ppmdv Difference 0.59 0 3.9 0.1 0.04 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.30 0.30 0.10 0.10 System Bias. SBi - Zero Bias 0.00% 0.21% 0.02% 0.00% 0.00%± 5% of Span Difference 0 0.2 0.3 0 0 Pass or Failed Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 51.10 50.00 504.10 5.80 9.90 SBi - Up-Scale Bias 0.00% 0.10% 0.03% 0.00% 1.53% Difference 0.00 0.10 0.40 0.00 0.30 Pass or Failed Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/15/2025 SO2 VOC NOX CO CO2 O2 NOX 30.8 42.67 653.79 10.50 8.40 CO 59.5% 44.6% 52.8% 89.7% 42.7% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.10 0.30 0.20 0.00 System Bias. SBi - Zero Bias 0.00% 0.00% 0.02% 0.85% 0.51%± 5% of Span Difference 0.0 0.0 0.3 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 51.40 49.00 492.60 5.80 9.90 SBi - Up-Scale Bias 0.58% 1.15% 0.96% 0.00% 1.53% Difference 0.3 1.1 11.9 0.0 0.3 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.00% 0.21% 0.00% 0.85% 0.51% Drift Difference 0.0 0.2 0.0 0.1 0.1 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 0.58% 1.05% 0.93% 0.00% 0.00% Difference 0.3 1.0 11.5 0.0 0.0Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #3 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.887 25.21 9.00 25.87 871 10.97 8.57 80.46 30.10 28.72 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 611.8636 1.0130 0.84 39.970 92.30 72.08 33.841 4.345 0.1138 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs (ft./sec.)Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6410 253.80 278,032 274 246,398.79 17.75904 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 7.04 2.653 872 69 55 772.40 716.50 55.90 2 6.91 2.629 870 72 57 756.60 732.00 24.60 3 871 75 58 619.10 614.20 4.90 4 872 77 59 891.00 884.10 6.90 5 872 79 61 6 871 81 63 3039.10 2946.80 Sum 7 870 83 64 8 871 84 66 9 870 86 67 10 869 87 68 11 871 89 70 12 871 90 70 13 14 15 16 17 18 19 2021 22 23 24 NOTEThese cells scans for the appropriate Cir. gas after the Cm If this scan is incorrect change the Cdir to the correct gas value. Failed Bias Dialog Failed Drift Dialog Failed Cal Error Dialog CO Calibration Gas Failed Bias Dialog Trans Jordan E 3 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #3 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % CV - Cylinder Value: VOC NOX CO CO2 O2Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3% 100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CMA 51.69 51.00 512.00 5.99 10.09 Calibration Error Test Measured Concentration VOC NOX CO CO2 O2Low-Level 0.20 0.10 0.00 0.10 0.10 Mid-Level 30.20 50.10 504.50 5.80 10.20 High-Level 51.10 95.60 1241.90 11.80 19.70 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 51.10 50.10 504.50 5.80 10.20 Low-Level 0.39% 0.10% 0.00% 0.85% 0.51% ppmdv Difference 0.2 0.1 0 0.1 0.1 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.00% 0.94% 0.61% 1.62% 0.56% ppmdv Difference 0 0.9 7.5 0.19 0.11 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.00% 0.32% 0.85% 0.20% ppmdv Difference 0.59 0 3.9 0.1 0.04 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.10 0.30 0.20 0.00 System Bias. SBi - Zero Bias 0.00% 0.00% 0.02% 0.85% 0.51%± 5% of Span Difference 0 0 0.3 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 51.40 49.00 492.60 5.80 9.90 SBi - Up-Scale Bias 0.58% 1.15% 0.96% 0.00% 1.53% Difference 0.3 1.1 11.9 0 0.3 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/15/2025 SO2 VOC NOX CO CO2 O2 NOX31.5 43.10 624.10 10.10 8.40 CO 60.9% 45.1% 50.4% 86.3% 42.7% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.00 0.20 0.00 0.20 0.00 System Bias. SBi - Zero Bias 0.39% 0.10% 0.00% 0.85% 0.51%± 5% of Span Difference 0.2 0.1 0.0 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 50.20 50.60 511.90 5.80 9.80 SBi - Up-Scale Bias 1.74% 0.52% 0.60% 0.00% 2.03% Difference 0.9 0.5 7.4 0.0 0.4 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.39% 0.10% 0.02% 0.00% 0.00% Response Spec. Difference 0.2 0.1 0.3 0.0 0.0 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 1.16% 0.63% 0.36% 0.00% 0.51% Difference 1.2 1.6 19.3 0.0 0.1Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #3 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.89 25.62 12.00 26.50 872 10.59 8.62 80.79 30.04 28.72 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 599.1265 1.0130 0.84 40.900 90.10 83 34.509 4.241 0.1094 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6570 252.35 283,039 279 252,061.56 17.9088 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 6.91 2.629 870 72 71 749.40 715.80 33.60 2 7.21 2.685 872 81 72 721.60 687.80 33.80 3 872 86 72 621.90 609.70 12.20 4 873 88 73 870.00 859.50 10.50 5 872 90 74 6 871 92 75 2962.90 2872.80 Sum 7 871 93 76 8 872 94 77 9 871 94 78 10 871 95 79 11 872 96 79 12 871 97 80 1314 15 16 17 18 19 20 2122 23 24 Failed Bias Dialog Failed Drift Dialog Failed Cal Error Dialog Failed Bias Dialog Trans Jordan E 3 CO VOC and NOx 2025 rev Division of Air Quality Stack Test Review of Trans-Jordan Cities Ladfill Generation VOC NOX CO CO2 O2 Landfil Gas Engine #3 CS Calibration Span 51.69 95.60 1238.00 11.70 19.66 Units ppm ppm ppm % % CV - Cylinder Value: VOC NOX CO CO2 O2Low-Level 0.00 0.00 0.00 0.00 0.00 Mid-Level 30.20 51.00 512.00 5.99 10.09High-Level 51.69 95.60 1238.00 11.70 19.66 0 to 20% of Cal. Span 0.00% 0.00% 0.00% 0.00% 0.00% 40 to 60% of Cal. Span 58.4% 53.3% 41.4% 51.2% 51.3% 100% of Cal. Span 100.0% 100.0% 100.0% 100.0% 100.0% Cdir - Enter Actual Up-scale Cylinder Value Used To Correct Emission Concentration. CMA 51.69 51.00 512.00 5.99 10.09 Calibration Error Test Measured Concentration VOC NOX CO CO2 O2Low-Level 0.20 0.10 0.00 0.10 0.10 Mid-Level 30.20 50.10 504.50 5.80 10.20 High-Level 51.10 95.60 1241.90 11.80 19.70 Enter Up-scale Analyzer Response to be used during testing. ACE Eq. 7E-1 51.10 50.10 504.50 5.80 10.20 Low-Level 0.39% 0.10% 0.00% 0.85% 0.51% ppmv Difference 0.2 0.1 0 0.1 0.1 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Mid-Level 0.00% 0.94% 0.61% 1.62% 0.56% ppmv Difference 0 0.9 7.5 0.19 0.11 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. High-Level 1.14% 0.00% 0.32% 0.85% 0.20% ppmv Difference 0.59 0 3.9 0.1 0.04 Status Passed Cal. Passed Cal. Passed Cal. Passed Cal.Passed Cal. Pre-Test Sampling System Bias Initial Values VOC NOX CO CO2 O2 CO - Low-Level 0.00 0.20 0.00 0.20 0.00 System Bias. SBi - Zero Bias 0.39% 0.10% 0.00% 0.85% 0.51%± 5% of Span Difference 0.2 0.1 0 0.1 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 50.20 50.60 511.90 5.80 9.80 SBi - Up-Scale Bias 1.74% 0.52% 0.60% 0.00% 2.03% Difference 0.9 0.5 7.4 0 0.4 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Raw Test Data Time Start Stop Test Date:1/15/2025 SO2 VOC NOX CO CO2 O2 NOX27.2 44.70 658.20 10.00 8.40 CO 52.6% 46.8% 53.2% 85.5% 42.7% CO2/O2 Post-Test System Bias 7E-2 SB=(Cs - Cdir)/CS x 100 Final Values VOC NOX CO CO2 O2 CO - Low-Level 0.20 0.00 0.00 0.10 0.00 System Bias. SBi - Zero Bias 0.00% 0.10% 0.00% 0.00% 0.51%± 5% of Span Difference 0.0 0.1 0.0 0.0 0.1 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. CM - Up-scale Gas 49.50 49.70 512.20 5.80 9.80 SBi - Up-Scale Bias 3.10% 0.42% 0.62% 0.00% 2.03% Difference 1.6 0.4 7.7 0.0 0.4 Pass or Invalid Run Passed Cal. Passed Cal. Passed Cal. Passed Cal. Passed Cal. Calibration Drift % of Span - D=ABS(SBf - SBi) Low-Level Drift 0.39% 0.00% 0.00% 0.85% 0.00% Response Spec. Difference 0.2 0.2 0.0 0.1 0.0 3% of Span Pass or Re-Calibrate Pass Pass Pass Pass Pass Up-scale Gas Drift 1.35% 0.10% 0.02% 0.00% 0.00% Difference 0.7 0.9 0.3 0.0 0.0Pass or Re-Calibrate Pass Pass Pass Pass Pass Landfil Gas Engine #3 Flow & Moisture As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms 0.89 25.21 12.00 26.09 872 10.44 8.66 80.89 30.02 28.67 Y Cp Vm cf Vlc AVG Tm F Vm std Vw std Bws S Bws 608.5408 1.0130 0.84 41.030 90.80 87 33.815 4.274 0.1122 0.9990 0.999 Load - Megawatts Avg. √∆P's Vs Qsw scfh wet Qa acfm Qsd dscfh Heat Input Btu/hr.Low Mid High 2.6680 255.61 282,260 278 250,587.67 17.85888 Enter >X 3D Pitot #1 - Times Date Point No.∆P √∆P ts F tm F (in) tm F (out) Final Vf Initial Vi 1 7.21 2.685 871 85 80 764.30 716.70 47.60 2 7.03 2.651 872 91 80 737.30 708.50 28.80 3 873 93 80 621.40 614.00 7.40 4 872 94 80 897.80 890.80 7.00 5 872 94 80 6 872 95 80 3020.80 2930.00 Sum 7 872 95 80 8 871 95 80 9 871 96 80 10 871 96 81 11 871 86 81 12 871 96 81 1314 15 16 17 18 19 20 2122 23 24 Failed Bias Dialog Failed Cal Error Dialog Failed Drift Dialog Failed Bias Dialog