HomeMy WebLinkAboutDERR-2025-001628Leak Detector
Facility Information
Name:Fast Stop 1107 Certification/Inspection #:58164
Address:75 S STONE RD, Snowville, UT, 84336 State ID:0100596
Phone Number:Form Completed By:Larry Vasquez Date:01/15/2025
Tank Information
Tank #:T1 RUL T3 PUL T4 DSL
Capacity:15248 15246 7983
Product:Unleaded Premium Diesel
Line #:RUL PUL DSL
Line Type:Pressure Pressure Pressure
LD Brand:VMI Red Jacket Red Jacket
LD Model:LD-2000 FX1V FX1DV
Serial #:0 0 0
Associated Tank:T1 RUL T3 PUL T4 DSL
Resiliency (ml):250 100 50
Check Valve Holding PSI:29 10 17
Opening Time:2 0 2
Result:Pass Inconclusive Pass
Test Equip. Mfg.:Vaporless, LDT-890 Vaporless, LDT-890 Vaporless, LDT-890
Notes:
Tested per manufacturer specifications.
Contractor Signature:Printed Name:Larry Vasquez
Leak Detector
Facility Information
Name:Fast Stop 1107 Certification/Inspection #:58512
Address:75 S STONE RD, Snowville, UT, 84336 State ID:0100596
Phone Number:Form Completed By:Ray Simms Date:01/28/2025
Tank Information
Tank #:T1 RUL T3 PUL T4 DSL
Capacity:15248 15246 7983
Product:Unleaded Premium Diesel
Line #:PUL
Line Type:Pressure
LD Brand:Red Jacket
LD Model:FX1V
Serial #:301206009
Associated Tank:T3 PUL
Resiliency (ml):180
Check Valve Holding PSI:22
Opening Time:2
Result:Pass
Test Equip. Mfg.:Vaporless, LDT-890
Notes:
Tested per manufacturer specifications.
Contractor Signature:Printed Name:Ray Simms
Line Test
Facility Information
Name:Fast Stop 1107 Certification/Inspection #:58167
Address:75 S STONE RD State ID:0100596
Phone Number:Form Completed By:Larry Vasquez Date:01/15/2025
Tank Test Information
Tank #:T1 RUL T3 PUL T4 DSL
Capacity:15248 15246 7983
Product:Unleaded Premium Diesel
Line Test Information
Line #:RUL PUL DSL
LineType:Pressure Pressure Pressure
Line Material:DW Flex DW Flex DW Flex
Line ID Size (in):2 2 2
Line Length (ft):300 300 300
Pump Type:Red Jacket Red Jacket Red Jacket
Associated Tank:T1 RUL T3 PUL T4 DSL
Test Equip. Mfg.:Triangle Triangle Triangle
Test Pressure (PSI):50 50 50
Initial Cyl. Level:0 300 310
Final Cyl. Level:0 270 300
Change in Time (mins):50 15 15
Change in Vol:0.0000 -30.0000 -10.0000
Change in Temp (F):0 0 0
Coeff. Of Thermal Expansion (g/F):0.00070 0.00070 0.00045
Line Vol (gal):48.94 48.94 48.94
Leak Rate (GPH):0.0000 -0.0317 -0.0106
Result:Inconclusive Pass Pass
Notes
TIGHTNESS TESTING CERTIFICATION
CGRS certifies that the systems in the above table have been tested utilizing leak detection methods which meet the prescribed leak rate testing standard of 0.10
gph with a minimum probability of detection of 95% and a 5% probability of a false alarm. CGRS further certifies that the protocol for each test method was strictly
adhered to, and that all precision tightness testing performed by CGRS was conducted in accordance with EPA 40 CFR parts 280.43(c) and 280.44(b) and the
National Fire Protection Association, Bulletin NFPA 329 criteria.
Contractor Printed Name:Larry Vasquez Contractor Signature:
Certification Number:TMI-301
Line Test
Facility Information
Name:Fast Stop 1107 Certification/Inspection #:58511
Address:75 S STONE RD State ID:0100596
Phone Number:Form Completed By:Ray Simms Date:01/28/2025
Tank Test Information
Tank #:T1 RUL T3 PUL T4 DSL
Capacity:15248 15246 7983
Product:Unleaded Premium Diesel
Line Test Information
Line #:RUL
LineType:Pressure
Line Material:DW Flex
Line ID Size (in):2
Line Length (ft):300
Pump Type:Red Jacket
Associated Tank:T1 RUL
Test Equip. Mfg.:Triangle
Test Pressure (PSI):55
Initial Cyl. Level:230
Final Cyl. Level:200
Change in Time (mins):15
Change in Vol:-30.0000
Change in Temp (F):0
Coeff. Of Thermal Expansion (g/F):0.00070
Line Vol (gal):48.94
Leak Rate (GPH):-0.0317
Result:Pass
Notes
TIGHTNESS TESTING CERTIFICATION
CGRS certifies that the systems in the above table have been tested utilizing leak detection methods which meet the prescribed leak rate testing standard of 0.10
gph with a minimum probability of detection of 95% and a 5% probability of a false alarm. CGRS further certifies that the protocol for each test method was strictly
adhered to, and that all precision tightness testing performed by CGRS was conducted in accordance with EPA 40 CFR parts 280.43(c) and 280.44(b) and the
National Fire Protection Association, Bulletin NFPA 329 criteria.
Contractor Printed Name:Ray Simms Contractor Signature:
Certification Number:1651,UT 407
Automatic Tank Gauge Inspection
ATG 1
ATG 1665
Facility Information
Name:Fast Stop 1107 Certification/Inspection #:58169
Address:75 S STONE RD, Snowville, UT, 84336 State ID:0100596
Phone Number:Form Completed By:Larry Vasquez Date:01/15/2025
ATG Console Inspection
Tank Level Monitor Brand :Veeder Root
1.Status upon Arrival:All Functions Normal
2.Status upon Departure:All Functions Normal
3.Is the display in good
condition and functioning?:
Yes
4.Is the keypad in good
condition?:
Yes
Tank Level Monitor Model :TLS-350
5.Are all indicator lights
functional?:
Yes
6.Is printer functional?:Yes
7.Back-up battery tested? (if
applicable)?:
Yes
8.Back-up battery voltage (if
applicable):
3.6
Tank Information
Probe and Programing Inspection:
9.Tank # T3 PUL T1 RUL T4 DSL
10.Tank Facility ID T3 PUL T1 RUL T4 DSL
11.Tank # per ATG T3 PUL T1 RUL T4 DSL
12.Product:Premium Unleaded Diesel
13.Tank Volume, gallons 15246 15248 7983
14.Tank Dia/depth, inches 119 119 119
In-Tank Setup Parameters:
15.Thermal coefficient .000700 .000700 .000450
16.ATG Programmed Diameter 119 119 119
17.Number of points on profile 4 4 4
18.Full volume on profile 15248 15248 7983
19.After removing the probe from the tank, it has been inspected and any damaged or missing parts replaced?Yes Yes Yes
20.Do floats move freely along the stem without binding?Yes Yes Yes
21.Does product level match console value?Yes Yes Yes
22.Does water level match console value?Yes Yes Yes
Pass/Fail Criteria: if any of questions 19, 20 ,21 & 22 are No, then the system has failed the test.
Comment
Operator Certification
Contractor Signature:Printed Name:Larry Vasquez
23.Water warning (inches)(1")1.5 1.5 1.5
24.High water limit (inches)(1.5")2 2 2
25.Does console water alarm trigger at programmed level?Yes Yes Yes
26.Programmed Overfill Limit (90%)90 90 90
27.Does console overfill alarm trigger at programmed level?Yes Yes Yes
28.Programmed High Product Limit (95%)95 95 95
29.Does console high product alarm trigger at programmed level?Yes Yes Yes
30.Low Product (15% of tank volume or 15" whichever is greater)15 15 15
31.Tank test program enabled?Yes Yes Yes
32.Tank Test Method?CSLD CSLD CSLD
33.Tank Test Rate 0.2 0.2 0.2
34.Test duration (hrs)CONT CONT CONT
35.12 months of tank test history present?Yes Yes Yes
Lines:
36.Electronic Line Leak Type NA NA NA
37.Line # and label in ATG (Q1, Unleaded)N/A N/A N/A
38.Line Test Rate N/A N/A N/A
39.12 months of line test history present?NA NA NA
40.Test Result Pass Pass Pass