HomeMy WebLinkAboutDDW-2025-002055Sanitary Survey - Deficiency Report
PWS Number:UTAH18021 Deficiency Points:175 Survey Date:02/18/2025
Survey Name:TAYLORSVILLE-BENNION
ID
Surveyor:Chris Bowles
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS006 | HIGH ZONE WEST WELL
132. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:The conduit is in need of repair and a mouse or something could get into the well head.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS006 | HIGH ZONE WEST WELL
134B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:The line is disconnected so the piping is exposed. I let them know they need to screen it or
connect it.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST004 | LOW ZONE NORTH #4
513. Roof or wall penetrations sealed
Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control
apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have
additional proper shielding to prevent vandalism. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:The SCADA junction box on the west side of the roof is broken and needs to be replaced. A
mouse could possible access the opening and get into the tank.
Deficiency Points: 100
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS
ON TANK ROOF OR SIDEWALLS