PWS Number:UTAH18177 Deficiency Points:50 Survey Date:02/21/2025
Survey Name:UTAH DATA CENTER Surveyor:Tom McOmie
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF001 | PUMP STATION
59. There are no unprotected cross-connections in the pump station.
Rule: R309-105-12(1)Cross connections are not allowed unless controlled by an approved and properly
operating backflow prevention assembly or device. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:There is an air-vac line connected to one of the PRVs, where the discharge line is routed
below the rim of the drain without the required air gap. They are working to get this
corrected as soon as possible.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS15 PUMP STATION HAS CROSS CONNECTION OR IS SUBJECT TO CONTAMINATION