HomeMy WebLinkAboutDDW-2025-002047Sanitary Survey - Deficiency Report PWS Number:UTAH18177 Deficiency Points:50 Survey Date:02/21/2025 Survey Name:UTAH DATA CENTER Surveyor:Tom McOmie Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | PUMP STATION 59. There are no unprotected cross-connections in the pump station. Rule: R309-105-12(1)Cross connections are not allowed unless controlled by an approved and properly operating backflow prevention assembly or device. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:There is an air-vac line connected to one of the PRVs, where the discharge line is routed below the rim of the drain without the required air gap. They are working to get this corrected as soon as possible. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS15 PUMP STATION HAS CROSS CONNECTION OR IS SUBJECT TO CONTAMINATION