Loading...
HomeMy WebLinkAboutDERR-2025-001580If any answers in Questions 3,4,5,6,7,11,13 or 14 are No, the system has failed the test. Overfill Alarm Inspection Facility Information Name:Fast Stop 1108 Certification/Inspection #: Address:2615 E BENGAL BLVD, Cottonwood Heights, UT, 84121 State ID:4001183 Phone Number:Form Completed By:Larry Vasquez Date:02/06/2025 Overfill Alarm Information This procedure is to determine wheather the high level alarm is operational and will trigger when the tank is no more than 90% full. See PEI/RP1200 Section 7.3 for inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place. Tank #T1 RUL T2 PUL T3 DSL Tank Facility ID T1 RUL T2 PUL T3 DSL Product Stored Unleaded Premium Diesel Tank Level Brand Veeder Root Veeder Root Veeder Root Tank Level Model TLS-350 TLS-350 TLS-350 1.Tank Diameter, in 92.000 92.000 92.000 2. Actual Tank Capacity, gal 11550 8086 4691 3.Overfill alarm activates in the test mode at the console? Y Y Y 4.When activated, overfill alarm can be heard or seen while delivering to the tank? Y Y Y 5.After removing the probe, it has been inspected and any damage or missing parts replaced? Y Y Y 6.Float moves freely on stem without binding?Y Y Y 7.Moving product level float up stem triggers alarm?Y Y Y 8.Inch level from bottom of stem when 90% alarm is triggered 90 90 90 9.Calculated tank volume from Question 8 10385 7263 4189 10.Tank % full 89.91 89.82 89.30 11.Is Question 10 less than 90%Y Y Y 12.Fuel float level on the console agrees with the gauge stick reading? Y Y Y 13. Overfill activates at 90% or less of tank capacity?Y Y Y 14.Fuel float level on the console agrees with the gauge stick reading Y Y Y Test Results Pass Pass Pass Comments Operator Certification Contractor Printed Name:Larry Vasquez Contractor Signature: