Loading...
HomeMy WebLinkAboutDAQ-2025-001206DEPARTMENT OF THE ARMY TOOELE ARMY DEPOT'HEADQUARTERS I TOOELE ARMY DEPOT, BUILDING 1 TOOELE, UT 8407+5003 May 23,2024 SUBJECT: Report of Deviation, Tooele Army Depot, Tooele, Utah - Permit 4500006004 Mr. Bryce Bird Department of Environmental Quality Division of Air Quality (DAO) ATTN: Compliance P.O. Box 144820 Salt Lake City, Utah 84114-4820 Dear Mr. Bird: I,TAH DEPARTMENT OF ENVIRONMENTAL OUAJTY MAY 2 B 2C24 H anrl detilers(l !',Vl$lON OF AtR eUALffy ln accordance with the Operating Permit provision l.S.2.c and Utah Administrative Code (UAC) R307-415-6a(3)9(c)(ii), the following deviation report is being submitted: a. The dates the deviation occurred: - 51612024 b. Permit condition for which the deviation occurred: - ll.B.l.e.1 condition, of the Title V Permit c. Describe the deviation that occurred: - On May 6,2024, after the first day of the Confirmatory Performance Test (CfPT), the stack testers compared the flow measurements from Tooele Army Depot's (TEAD's) stack gas velocity meter. TEAD's meter was reading significantly lower at 35 fps vs the stack testers of 50 fps causing an instrumentation failure. d. Was the deviation due to an "upset condition" as defined in of the permit? - No. e. Was the deviation due to an unavoidable breakdown as defined in UAC R307- 107? - No. REVIEWEDInitials:Date: Feb 4, 2025Compliance Status:OK File #: 11594 (B2)Comment: Report should have been received on or before May 20, 2024.(within 14 days of deviation). See inspection memo. SUBJECT: Report of Deviation, Tooele Army Depot, Tooele, Utah - Permit 4500006004 f. Describe the probable cause of the deviation: - This was due to instrumentation failure. g. Describe the conective action or preventive measures taken: - Personnel replaced the flow meter and continued the (CfPT) testing. The preliminary results show TEAD's stack flow meter had passed the RATA. ln accordance with Operating Permit provision l.K and UAC R307-415-5d, and based on information and belief formed after reasonable inquiry, I certify that the statements and information in this document are true, accurate and complete. Should you have any questions or require any additional information regarding this matter, please contact Mr. Lonnie Brown of my staff at 435-833-3257. Sincerely, Eric B. Dennis Colonel, U.S. Army Commanding cc: USEPA Region 8 2