HomeMy WebLinkAboutDERR-2024-005408Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name GRUMPS GENERAL STORE LLC
Address PO BOX 24
ECHO, UT 84024
Contact GRUMPS GENERAL STORE LLC
Phone
Email grumpsgeneralstore @gmail.com
TANK LOCATION
Name GRUMPS GENERAL STORE
Address 520 N MAIN ST
HENEFER, UT 84033
A Operator None
Phone None
B Operator SAME
Phone SAME
Facility ID: 7000021 Inspection Date: 03/28/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 -
Gasoline
Gasoline No Not Listed May 2,
1976
None No No None None
2 -
Diesel
Diesel No Not Listed May 2,
1976
None No No None None
TANK DETAILS
Tank ID/Alt ID 1 / 1
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc May 2, 1976 / 10000 / East
Substance
Stored Gasoline / Regular
Tank Material-
Mod
Impressed Current Cathodic
Protection-Lined Interior
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Galvanized Steel / Cathodically
Protected
Pipe type/STP
Cont Safe Suction / No
STP Flex
Connectors Not Listed
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type No / None
Tank/Pipe Rel Det TankSIR PipeLDDeferred
CP Tank Test July 23, 2018
CP Pipe Test July 23, 2018
Tank ID/Alt ID 2 / 2
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc May 2, 1976 / 4000 / West
Substance
Stored Diesel /
Tank Material-
Mod
Impressed Current Cathodic
Protection-Lined Interior
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Galvanized Steel / Cathodically
Protected
Pipe type/STP
Cont Safe Suction / No
STP Flex
Connectors Not Listed
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type No / None
Tank/Pipe Rel Det TankSIR PipeLDDeferred
CP Tank Test July 23, 2018
CP Pipe Test July 23, 2018
INSPECTION COMMENTS
None
2024-03-28 Page 1 of 6
FACILITY RESPONSES
The above accurately represents the
facility's release detection records No
Operator Training
A Operator current?No
B Operator current?No
Monthly checklist available and
complete?No
Is the site unmanned?Yes
Is a sign posted in a conspicuous area
giving the name and telephone number
of a person in case of an emergency
and if the station is manned part of the
time, are C operators trained?
Yes
Does the site have emergency shutoff
device?Yes
Cathodic Protection
Impressed current system is checked
for proper operations at least every 60
days and the results of the last three
checks are available?
No
The results of the last two cathodic
protection tests are available (within six
months of installation and every three
years thereafter)?
No
Financial Responsibility
Financial responsibility method is ok?No
TANK RESPONSES
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 1 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 1 Suction Piping Leak Detection
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
No
Does the overfill device have a valid 3-
year test or the tank is exempt?No
Tank 2 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
2024-03-28 Page 2 of 6
Tank 1 SIR/MTG
SIR - Dispensers have current
calibration stickers or proper calibration
documentation?
Yes
SIR - Drop tubes are present and
extend to within one foot of the tank
bottom?
Yes
SIR - Inventory readings for product
inputs, withdrawals, and the amount
remaining in the tank are recorded and
available for each operating day?
No
SIR - Product inputs are reconciled with
delivery receipts by measurement of
the tank inventory volume before and
after deliveries?
No
SIR - Records include the appropriate
number of water readings, and water
readings are used to adjust inventory
balances as necessary?
No
SIR/MTG - An appropriate calibration
chart is used to convert product level
readings to gallons, and is available for
review?
No
SIR/MTG - Inventory readings are
properly reconciled monthly (weekly
and monthly for MTG) to the
appropriate allowable amount?
No
SIR/MTG - Equipment used to take
readings (ATG, Gauge Stick, etc.) is
adequate, accessible, and operational?
No
SIR/MTG - Documentation of valid
testing or monitoring is available (must
have records for the two most recent
months and 10 of last 12 months)?
Show results in the RD tab.
No
Tank 2 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 2 Suction Piping Leak Detection
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
Tank 2 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
No
Does the overfill device have a valid 3-
year test or the tank is exempt?No
Tank 2 SIR/MTG
SIR - Dispensers have current
calibration stickers or proper calibration
documentation?
Yes
SIR - Drop tubes are present and
extend to within one foot of the tank
bottom?
No
SIR - Inventory readings for product
inputs, withdrawals, and the amount
remaining in the tank are recorded and
available for each operating day?
No
SIR - Product inputs are reconciled with
delivery receipts by measurement of
the tank inventory volume before and
after deliveries?
No
SIR - Records include the appropriate
number of water readings, and water
readings are used to adjust inventory
balances as necessary?
No
SIR/MTG - An appropriate calibration
chart is used to convert product level
readings to gallons, and is available for
review?
No
SIR/MTG - Inventory readings are
properly reconciled monthly (weekly
and monthly for MTG) to the
appropriate allowable amount?
No
SIR/MTG - Equipment used to take
readings (ATG, Gauge Stick, etc.) is
adequate, accessible, and operational?
No
SIR/MTG - Documentation of valid
testing or monitoring is available (must
have records for the two most recent
months and 10 of last 12 months)?
Show results in the RD tab.
No
DISPENSER RESPONSES
2024-03-28 Page 3 of 6
Dispenser Diesel
Flex connectors at the dispensers are
protected from corrosion?Yes
Dispenser Gasoline
Flex connectors at the dispensers are
protected from corrosion?Yes
MONTHLY LEAK DETECTION MONITORING
Mar '23 Apr '23 May '23 Jun '23 Jul '23 Aug '23 Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24
Tank 1 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 2 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
TANK 1
No Photos
Question:SIR - Inventory readings for product inputs, withdrawals, and the amount remaining in the tank are
recorded and available for each operating day?
Comments:None
TANK 1
No Photos
Question:SIR - Product inputs are reconciled with delivery receipts by measurement of the tank inventory
volume before and after deliveries?
Comments:None
TANK 1
No Photos
Question:SIR - Records include the appropriate number of water readings, and water readings are used to
adjust inventory balances as necessary?
Comments:None
TANK 1
No Photos
Question:SIR/MTG - An appropriate calibration chart is used to convert product level readings to gallons, and is
available for review?
Comments:None
TANK 1
No Photos
Question:SIR/MTG - Inventory readings are properly reconciled monthly (weekly and monthly for MTG) to the
appropriate allowable amount?
Comments:None
TANK 1
No Photos
Question:SIR/MTG - Equipment used to take readings (ATG, Gauge Stick, etc.) is adequate, accessible, and
operational?
Comments:None
TANK 1
No Photos
Question:SIR/MTG - Documentation of valid testing or monitoring is available (must have records for the two
most recent months and 10 of last 12 months)? Show results in the RD tab.
Comments:None
TANK 1
No Photos
Question:Does the spill bucket have a valid 3-year test, valid monthly monitoring for DW buckets, or the tank is
exempt?
Comments:None
TANK 1
No Photos
Question:Does the overfill device have a valid 3-year test or the tank is exempt?
Comments:None
TANK 2
No Photos
Question:SIR - Drop tubes are present and extend to within one foot of the tank bottom?
Comments:None
TANK 2
2024-03-28 Page 4 of 6
No Photos
Question:SIR - Inventory readings for product inputs, withdrawals, and the amount remaining in the tank are
recorded and available for each operating day?
Comments:None
TANK 2
No Photos
Question:SIR - Product inputs are reconciled with delivery receipts by measurement of the tank inventory
volume before and after deliveries?
Comments:None
TANK 2
No Photos
Question:SIR - Records include the appropriate number of water readings, and water readings are used to
adjust inventory balances as necessary?
Comments:None
TANK 2
No Photos
Question:SIR/MTG - An appropriate calibration chart is used to convert product level readings to gallons, and is
available for review?
Comments:None
TANK 2
No Photos
Question:SIR/MTG - Inventory readings are properly reconciled monthly (weekly and monthly for MTG) to the
appropriate allowable amount?
Comments:None
TANK 2
No Photos
Question:SIR/MTG - Equipment used to take readings (ATG, Gauge Stick, etc.) is adequate, accessible, and
operational?
Comments:None
TANK 2
No Photos
Question:SIR/MTG - Documentation of valid testing or monitoring is available (must have records for the two
most recent months and 10 of last 12 months)? Show results in the RD tab.
Comments:None
TANK 2
No Photos
Question:Does the spill bucket have a valid 3-year test, valid monthly monitoring for DW buckets, or the tank is
exempt?
Comments:None
TANK 2
No Photos
Question:Does the overfill device have a valid 3-year test or the tank is exempt?
Comments:None
FACILITY
No Photos
Question:Impressed current system is checked for proper operations at least every 60 days and the results of
the last three checks are available?
Comments:None
FACILITY
No Photos
Question:The results of the last two cathodic protection tests are available (within six months of installation
and every three years thereafter)?
Comments:None
FACILITY
No Photos
Question:Financial responsibility method is ok?
Comments:None
FACILITY
No Photos
Question:A Operator current?
Comments:None
FACILITY
No Photos
Question:B Operator current?
Comments:None
FACILITY
2024-03-28 Page 5 of 6
Prepared by fueloperator.com
No Photos
Question:Monthly checklist available and complete?
Comments:None
Inspection Information
Inspector:Harris, Gary
Record
Created:
March 28, 2024, 11:13
a.m.
Inspection
Date:March 28, 2024
2024-03-28 Page 6 of 6