HomeMy WebLinkAboutDERR-2025-001362 WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS Facility Name: SALT LAKE CITY AIRPORT AUTHORITY Owner: AIRPORT NORTH SUPPORT Address: PO BOX 145550 Address: 4000 WEST 1020 NORTH City, State, Zip: SALT LAKE CITY, UTAH 84114 City, State, Zip: SALT LAKE CITY, UTAH 84114 Facility I.D.#: 4001950 Phone #: 801-531-4571 Testing Company: Westech Phone #: 801-266-2545 DATE: 1/13/2025 This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures. Line Number 1 2 3 Product Stored DIESEL GAS DIESEL Leak Detector Manufacturer VEEDER ROOT VEEDER ROOT VEEDER ROOT Leak Detector Model FX2 FX1 FX2 Type Of leak Detector ☒MLLD ☐ELLD ☒MLLD ☐ELLD ☒MLLD ☐ELLD ☐MLLD ☐ELLD MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure 28 28 28 Check valve holding pressure 19 19 19 Line resiliency (ml) (line bleedback volume as measured from check valve holding pressure to 0 psig) 105 105 105 Step through time in seconds (time the MLLD hesitates at metering pressure before going to full operating pressure as measured from 0 sig with no leak induced on the line) 3 3 3 Metering pressure (STP pressure when simulated leak rate 3 gph at 10 psig) 15 15 15 Opening time in seconds (the time the MLLD opens to allow full pressure after simulated leak is stopped) 3 3 3 Does the STP pressure remain at or below the metering pressure for at least 60 seconds when the simulated leak is induced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No Does the leak detector reset (trip) when the line pressure is bled off to zero psig? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No Does STP properly clycle on/off under normal fuel system operating conditions? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No A "No" answer to any of the above questions indicates that the MLLD fails the test. ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure How many test cycles are observed before alarm/shutdown occurs? Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" answer to the above question indicates that the ELLD fails the test. Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail Comments: Tester’s Name Jon Sainsbury Tester’s Signature Jon Sainsbury WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054