HomeMy WebLinkAboutDAQ-2025-001072 1 DAQC-171-25 Site ID 16015 (B5) MEMORANDUM TO: FILE – HOLLY ENERGY PARTNERS – Light Oil Dock THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Rob Leishman, Environmental Scientist DATE: February 12, 2025 SUBJECT: Holly Energy Partners, Light Oil Dock (Holly LOD), Major, MACT, SIP, Title V, Davis County, FRS # UT00000049001100013 INSPECTION TYPE: State Electronic Data Report (SEDR) Review REVIEW DATE: February 12, 2025 SOURCE LOCATION: West Bountiful/Davis County SOURCE CONTACT: Daria Underwood – 214-954-3935 APPLICABLE REGULATIONS: Title V operating permit – 1100458001 – dated February 8, 2021 SOURCE INSPECTION EVALUATION: With the exception of sources that only monitor for opacity, quarterly report memoranda will only address the findings of the quarterly report. Approval Order and Title V permit conditions addressing continuous emission monitoring requirements will be addressed in Holly LOD’s relative accuracy performance specification test review memorandum. SOURCE REVIEW EVALUATION: Fourth Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation LOD 2198 VOC 99% 12/05/24 11/19/24 LOD VOC 0.00 10000 ppm - 6 hour RA 1 8 2 2 Excess Emission Report - Hourly Summary Point Source Channel Startup & Shutdown Control Equipment Problems Process Problems Other Known Causes Unknown Causes Emission Limit LOD VOC 0 0 0 0 0 10000 ppm - 6 hour RA CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes LOD VOC 0 0 13 0 0 Pollutant Concentration Exceeded Span of CEM Monitor Outage During Point Source Operation Alternate Sampling CEM Modifications 0 Hours 0 Hours 0 Hours 0 Events SOURCE INSPECTION SUMMARY EVALUATION: Holly LOD maintains its CEMS as required in R307-170 and 40 CFR 60.13. CURRENT RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related problems that do not warrant issuing a violation. Holly LOD was in compliance during this reporting period. No further enforcement action is necessary. Holly LOD’s NSPS monitoring system meets the performance standards of 40 CFR 60, Appendix B, Performance Specifications. HIGH PRIORITY VIOLATOR (HPV): No RECOMMENDATION FOR NEXT INSPECTION: Check DAS for daily zero and span drift. Check the QC program to ensure that monitor drift is being tracked and that the source can identify excessive drift. ATTACHMENTS: Excel spreadsheet review ,.tttf $nctor i rrDsrREAM January 29,2025 Utah Division of Air Quality 195 North 1950 West Salt Lake City Utah 84116 Re:ll; _.-_ __-- __ ____---_ .,1 Dear SirlMadam: Enclosed please find the Q4-2024 Woods Cross Terminal Continuous Emission Monitoring System (CEMS) Report. Per Utah Administrative Code R307-170-9, the electronic ASCII report file will be sent to Rob Leishman, UDAQ, with this report, via e-mail. The following information is applicable to report contents: The continuous monitoring system calibration and drift checks were routinely performed, and a quarterly cylinder gas audit (CGA) was completed on 1215/2024 and found within the required performance specifications. The data used to show compliance with the standard were obtained in accordance with approved methods and procedures. The minimum data requirements have been met, with minimal missin8 data. Overall CEMS downtime was 0.57% including required QC (daily span/zero checks) and CGA during the 4'h quarter. Total CEMS QC and CGA downtime was 12.5 hours. VRU required approximately 10 hours 33 minutes of downtime during this quarter for routine maintenance. All activities were under planned preventative maintenance and operational needs in alignment with the permit. During VRU downtime, LOD effluent was diverted to the VCU or loading operations were discontinued. Compliance with the general requirements under Utah Administrative Code R307-170-5 has been achieved during the reporting period. I certify under penalties of law that, based upon inquiry of personnel involved, and to the best of my knowledge, the statements and information contained in this report are truthful and accurate, and are a complete record of all monitoring-related events that occurred during the reporting period. lf you have any questions or need additional information, please contact me at John.Paris@hfsinclair.com. Attachment:trlLl HEP CEMS EER Worksheet, 4th Quarter 2024 Ll ir\i ' [)r-r,,r,F.i i,,:5i,1 6i. -- i! Vi l-.'rl'Nll:1 ir ii I,1.i (i L IALITY-t i 4'h Quarter 2024 cEMs Report Woods Cross Terminal, Approval Order DAQE-AN0101200238{7 Holly Energy Partners 1. 2. 3. 4. 'esident - Operations Corporate Offlce: 0peraUons Offlce: 2828 N. Hanvood, Sulte 1il0o 1602 West Maln Street Dallas, TX 75201-1507 2!l-8713555 Artesla, NM 88210 57$7484000 Attachment: HEP CEMS EER Worksheet, 4th Quarter 2024 (Note: A copy of the attached EER worksheet, in CSV format, was submitted to Mr. Rob Leishman on January 30,2025, via email from Estee Lafrenz, ERM, on behalf of HEP) 1OO t&rkTCunnlnghanHoltyEnerP.O.Eo(1260Artesla,Newm01l-00013 (21,+)871-3555JohnParis 1r0 LoD 4 20?4 2198 200 LoD 220 LOo 230 LOD 250 LOD 28{' LOO 260 LOD s00 LoD 310 LOD 460 LoD 700 700 700 700 700 720 720 720 720 720 7g 730 730 730 730 730 730 7g 7g 730 730 730 730 730 o l7l79no24 tu5no21 7a5no21 ttnu20x 5000 20,@0 u8/2016 \,8U 12 ppm 1102.5 976,7 Zgrzxl2 Certltled Malter ptrcent 7llol2a32 C.nlfied Master percent 2.21+6 pess 0.51 0.511 .0.2ott Pass 1.007 1.096 0.(r(,t pass 0-m 0 10000 ppm 6hourRA voc voc , ?627795 2 RAIX,:rI low mld 12.5 voc 701 Startup/Shutdom 702 Controt Equipment Problems 703 Procsss Probtqns 704 OthGrXmwnCau*s 706 Unknown C€usc! 721 I'bnitor Equipment l&ltunction 722 NonmonltorEq!lpment Matlunctlon 723 QACatibrationt 724 Othu Xmwn Caucos 726 Unkn0vn Caura 703 A Pomrlailure. 703 B Contotwtvaraiture. 703 c PumplolluE 7u A olhcrhnMcsu3es. B€tlnaryproductproc€srchsngetorwlnlorErades 705 A Unknwn crwe. 721 A Dallycrtlbrallonchectexceedrnce. CaEsof dritlunknm' Rtrallb.atcdlmtrument. 72lg DstrrecordGrraltuE. 72lC Powertailurc.Notoadlngdurlnsout0ge. 721O Monildtailure 722 A VRU Equipmntlailule. VCU ussd rorconttot. 7 A {QA,/QC)-VCUusedtorcontrol. 724 A Meterproving. VCIJ Bedlorcontrcl. 7u g VRU maintananco. vCU usodlorcontrol. 7 c a.lonltormalntsnancq t-rinH orpnnrMrrui-5n- E NVIROI.!MENTAL QUALIT\ t---- -_-_-_-r II rrP, -3 )r)t l I Irl DIVISION OF AIR OUALITY FEB Holly EP LOD EER 4Q2024 Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No 1 Type Code 100 (Company Information)Type Code Company Manager Company Name AIRS # Phone Number Environmental Contact 1 100 Mark T Cunningham 01100013 (214)871-3555 John Paris0 1 100 0 0 0 0 1 Type Code 110 (Point Source Identification)Type Code Point Source Quarter 1 - 4 Year Point Source Operating Hrs. in Quarter 1 110 4 2024 2198 1 110 0 0 0 1 Type Code 200 (Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date Monitor Location 1 200 VOC IR 8400D 5086 5000 20000 8/8/2016 VRU 1 200 0 0 0 0 0 0 1/0/1900 0 1 Type Code310 (Excess Emissions) SUMMARY REPORT Type Code Channel Total Hours of Excess Emissions Excess Emissions - % of Total Operating Hours RC 701 Hours - start up/Shutdown RC 702 Hours- Control Equipment Problems RC 703 Hours - Process Problems RC 704, 706, 707 Hours -Other Known Causes RC 705 Hours - Unknown Causes Emission Limitation Emission Limitation Units Emission Limitation Averaging Period 1 TRUE 310 VOC 0 0.00% 0 0 0 0 0 10000 ppm 6 hour RA 1 310 0 0 0 0 0 0 0 0 0 1 Type Code 300 (CMS Performance Summary) Type Code Channel Point Source Operating Hours Downtime - % of Total Operating Hours Total CMS Downtime RC 721 Hours - Monitor Malfunction RC 722 Hours - Non-monitor Malfunction RC 723 Hours - QA Calibrations RC 724 Hours - Other Known Causes RC 725 Hours - Unknown Causes 1 TRUE 300 VOC 2198 0.57% 12.5 0 0 12.5 0 0 1 300 0 0 0 0 0 0 1 Type Code 250 (Performance Specification RATA Results) Type Code Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units of Measurement CEM Value Reference Method Value Relative accuracy Pass/ Fail 1 364 Days 250 VOC 11/19/24 11/21/23 12 ppm 1102.5 976.7 2.21% pass 1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0 1 Type Code 260 (CGA Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 260 VOC 12/05/24 1 P627795 07/09/32 Certified Master Gaspercent 5100 5110 -0.20% pass low 1 Valid Cal. Gas 260 VOC 12/05/24 2 R817032 07/10/32 Certified Master Gaspercent 10970 10960 0.06% pass mid 1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 270 (Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code Channel Start Date Start Time End Date End Time Hours 1 0 0 0 1/0/00 0:00 1/0/00 0:00 1 1 None Reported 1 0 TC 220 Hours 0.00 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00 1 12.50 TC 300 Hours 12.50 FALSE Yes None Reported None Reported None Reported None Reported None Reported Point Source Point Source Point Source Point Source Point Source Point Source Yes LOD 0 LOD LOD LOD 0 Type Code 550 (Changes in Operation in Control Equipment When CEM Data Not Available) Type Code 500 (Boiler Operating Days w/o 18 Hours of Data) Holly Energy Partners Operating, L.P. 0 Type Code 450 (Data Excluded) LOD 0 LOD 0 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code 220 (Monitor Outage During Point Source Operation) Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) Type Code 240 (CEM Modifications) Type Code 530 (Excess Emissions During Emergency Conditions) 0 LOD 0 0 0 Holly EP LOD EER 4Q2024 Relative Accuracy Overview Point Source Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units Measured CEM Value Reference Method Value Relative Accuracy Pass/ Fail LOD VOC 11/19/24 11/21/23 12 ppm 1102.5 976.70 2.21% pass * NSPS CGA Fourth 2024 Audit Gas Ranges Audit Gas Ranges AP1 Low AP2 Low AP1 High AP2 High LOD VOC 12/5/24 20000 5110 4000 to 6000 LOD VOC 12/5/24 20000 10960 10000 to 12000 Point Source Channel Audit Date Low Span Audit Gas Used High Span Audit Gas Used Holly EP LOD EER 4Q2024 Monitoring Information TC 210, 230, & 240 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) VOC Grand Total (blank)0 0 LOD 0 0 Grand Total 0 0 0 * Type Code 240 (CEM Modifications) - 100 (All) * Count of Channel Column Labels Row Labels (blank) Grand Total (blank) (blank) Grand Total Holly EP LOD EER 4Q2024 Type Code 220 (Monitor Outage During Point Source Operation) - 600 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank) (blank) 0 0 LOD VOC 0 0 0 Grand Total 0 0 Holly EP LOD EER 4Q2024 VOC/THC * VOC/THC Type Code 460 (VOC/THC) - 6000 (All) VOC/THC * VOC/THC Count of Magnitude of Emissions Column Labels VOC/THC Row Labels (blank)0 Grand Total VOC/THC LOD VOC/THC #N/A 1 1 VOC/THC Grand Total 1 1 Holly EP LOD EER 4Q2024 Type Code 500 Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of Data) After February 28, 2005 (90% Operating Hours For each 30 BOD) - 500 (All) * Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 510 (F-factor, Equations & Conversion Factors) - 500 (All) Count of F-factor Column Labels Row Labels Grand Total Grand Total * Type Code 520 (Minimum Data Not Obtained <22/30 BODs) - 500 (All) Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 530 (Excess Emissions During Emergency Conditions) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * Type Code 540 (Fuel Pre-treatment Credit SO2) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * TypeCode 550 (Changes in Operation in Control Equipment When CEM Data Not Available) - 500 (All) Column Labels Row Labels Grand Total Grand Total