Loading...
HomeMy WebLinkAboutDDW-2025-001797J. Paul Wright <pwright@utah.gov> RE: [EXTERNAL]: Re: Design of Gas Chlorination System at Cedar City's Enoch Well #3 Jonathan Stathis <jstathis@cedarcity.org>Mon, Jan 20, 2025 at 12:11 PM To: "J. Paul Wright" <pwright@utah.gov> Cc: Sarah Page <sepage@utah.gov>, Bill Maxwell <mbill@cedarcityut.gov>, Matt Baker <mbaker@cedarcityut.gov> Paul – I’ve attached a revised set of drawings for the design of the proposed Gas Chlorination System at Cedar City’s Enoch Well #3. See below in red for my responses to your comments. Please review and let me know if you have any comments or questions. Thank you. Thanks, Jonathan Stathis, P.E. Cedar City Corporaon Cell Phone: (435) 463-0412 jstathis@cedarcityut.gov From: J. Paul Wright <pwright@utah.gov> Sent: Tuesday, November 19, 2024 2:55 PM To: Jonathan Stathis <jstathis@cedarcity.org> Cc: Sarah Page <sepage@utah.gov>; Robbie Mitchell <mrobbie@cedarcityut.gov>; Bill Maxwell <mbill@cedarcityut.gov>; Kent Fugal <kentf@cedarcityut.gov>; Ryan Marshall <mryan@cedarcityut.gov> Subject: [EXTERNAL]: Re: Design of Gas Chlorinaon System at Cedar City's Enoch Well #3 Jonathan, I opened this to see if it was complete. I just want to point out a couple of things that the design is not clear about. 1) The exhaust fan needs to draw from near the floor in the chlorine room. (iii) Chlorine room exhaust fan(s) shall take suction inside the chlorine room near the floor, as far as practical from the door and air inlet, and discharge air outside of the building away from air inlets 2/3/25, 4:11 PM State of Utah Mail - RE: [EXTERNAL]: Re: Design of Gas Chlorination System at Cedar City's Enoch Well #3 https://mail.google.com/mail/u/0/?ik=f3bcb897f8&view=pt&search=all&permmsgid=msg-f:1821796269858883018&simpl=msg-f:1821796269858883018 1/2 A note regarding the installation of an exhaust fan has been added to the drawing. The exhaust fan will be located on the opposite side of the room from the door and air inlet. 2) The air intake needs to draw from near the ceiling, opposite side of the room from the exhaust fan near the floor. (iv) Chlorine room air inlets shall be through wall louvers near the ceiling. Louvers are already located in the door. A note has been added on Sheet 1 regarding the location of the louvers. If you need more information regarding the louvers, I can get a photo and send it to you. 3) The chlorine vent pipe needs to have a #14 screen on the end of it. A note regarding the #14 screen on the end of the vent pipes has been added to Sheet 1. Rule R309-520 is here for your reference: https://adminrules.utah.gov/public/rule/R309-520/Current%20Rules With chlorinators, we need to have information about the chlorinator as well as your Point of Entry sample location, where you will be required to sample daily (or continuously) prior to your first customer. I have attached a Word file that includes the items I will need more information about to complete my review and include in the plan approval letter. Information is now provided on Sheet 2 regarding the Point of Entry sample location where the chlorine analyzer will be installed. Also, the responses to the items in the Word file are included on Sheet 2. Let me know if you have any questions. Paul [Quoted text hidden] 2 attachments ENOCH WELL #3 CHLORINATOR 1-16-25.pdf 6852K DDW-Project Notification Form - Chlorine Disinfection at Cedar City's Enoch Well #3.xlsm 29K 2/3/25, 4:11 PM State of Utah Mail - RE: [EXTERNAL]: Re: Design of Gas Chlorination System at Cedar City's Enoch Well #3 https://mail.google.com/mail/u/0/?ik=f3bcb897f8&view=pt&search=all&permmsgid=msg-f:1821796269858883018&simpl=msg-f:1821796269858883018 2/2