HomeMy WebLinkAboutDAQ-2025-000878
1
DAQC-163-25
Site ID 10237 (B5)
MEMORANDUM
TO: FILE – HUNTER POWER PLANT
THROUGH: Harold Burge, Major Source Compliance Section Manager
FROM: Rob Leishman, Environmental Scientist
DATE: February 10, 2025
SUBJECT: Hunter Power Plant (Hunter), Major, NSPS, Emery County,
FRS # UT0000004901500101
INSPECTION TYPE: State Electronic Data Report (SEDR) Review
REVIEW DATE: February 10, 2025
SOURCE LOCATION: Castle Dale/Emery County
SOURCE CONTACT: Terry Guthrie – 435-748-6059
Jay Howard – 435-748-6519
APPLICABLE
REGULATIONS: Title V Operating Permit
Permit Number: 1500101004
Date of Permit: September 4, 2020
Date of Last Revision: November 19, 2021
SOURCE REVIEW EVALUATION:
SOURCE INSPECTION
EVALUATION: With the exception of sources that only monitor for opacity, quarterly
report memoranda will only address the findings of the quarterly report.
Approval Order and Title V permit conditions addressing continuous
emission monitoring requirements will be addressed in Hunter’s relative
accuracy performance specification test review memorandum.
1 8 2
2
SEDR Review
Fourth Quarter 2024
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During
Point Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
1 2207 SO2 100% 10/22/24 10/22/24 1 SO2 0.00
1.2
lb/MMBtu - 3
hr ra
1 2207 NOx 100% 10/22/24 10/22/24 1 SO2 0.00
0.12
lb/MMBtu -
30 DRA
1 2207 CO2 100% 10/22/24 10/22/24 1 SO2 0.00
0.2
lb/MMBtu -
30 DRA
1 2207 Opacity 99% 1 NOx 0.00
0.7
lb/MMBtu - 3
hr ra
1 2207 CO 100% 10/22/24 10/22/24 1 NOx 0.00
0.26
lb/MMBtu -
30 DRA
2 2179 SO2 100% 10/22/24 10/16/24 1 Opacity 0.00 20 Percent - 6
min
2 2179 NOx 100% 10/22/24 10/16/24 1 CO 0.00 3990 lb/hr - 8
hr Block Ave
2 2179 CO2 100% 10/22/24 10/16/24 1 CO 0.00
0.34
lb/MMBtu -
30 DRA
2 2179 Opacity 99% 2 SO2 0.00
1.2
lb/MMBtu - 3
hr ra
2 2179 CO 100% 10/22/24 10/16/24 2 SO2 0.00
0.12
lb/MMBtu -
30 DRA
3 2175 SO2 100% 10/23/24 11/20/24 2 SO2 0.00
0.2
lb/MMBtu -
30 DRA
3 2175 NOx 99% 10/23/24 11/20/24 2 NOx 0.00
0.7
lb/MMBtu - 3
hr ra
3 2175 CO2 100% 10/23/24 11/20/24 2 NOx 0.00
0.26
lb/MMBtu -
30 DRA
3 2175 Opacity 99% 2 Opacity 0.00 20 Percent - 6
min
3 2175 CO 97% 10/23/24 11/20/24 2 CO 0.00 3990 lb/hr - 8
hr Block Ave
2 CO 0.00
0.34
lb/MMBtu -
30 DRA
3 SO2 0.00
0.12
lb/MMBtu -
30 DRA
3
Fourth Quarter 2024
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During
Point Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
3 SO2 0.00
0.2
lb/MMBtu -
30 DRA
3 NOx 0.00
0.34
lb/MMBtu -
30 DRA
3 Opacity 0.00 20 Percent - 6
min
3 CO 0.00
0.2
lb/MMBtu -
30 DRA
3 CO 0.00 2406 lb/hr - 8
hr Block Ave
Summary of SO2 Emission Reduction
Percent Removal Required
% Reduction
Point
Source Channel Min Max Days in violation Status
1 SO2 94% 95% 80% 0 In compliance
2 SO2 94% 95% 80% 0 In compliance
3 SO2 94% 94% 90% 0 In compliance
Excess Emission Report - Hourly Summary
Point
Source Channel
Startup
&
Shutdown
Control
Equipment
Problems
Process
Problems
Other
Known
Causes
Unknown
Causes
Emission
Limit
1 SO2 0 0 0 0 0 1.2 lb/MMBtu - 3 hr ra
1 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA
1 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA
1 NOx 0 0 0 0 0 0.7 lb/MMBtu - 3 hr ra
1 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA
1 Opacity 0 0 0 0 0 20 Percent - 6 min
1 CO 0 0 0 0 0 3990 lb/hr - 8 hr Block Ave
1 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA
2 SO2 0 0 0 0 0 1.2 lb/MMBtu - 3 hr ra
2 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA
2 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA
2 NOx 0 0 0 0 0 0.7 lb/MMBtu - 3 hr ra
2 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA
2 Opacity 0 0 0 0 0 20 Percent - 6 min
4
Excess Emission Report - Hourly Summary
Point
Source Channel
Startup
&
Shutdown
Control
Equipment
Problems
Process
Problems
Other
Known
Causes
Unknown
Causes
Emission
Limit
2 CO 0 0 0 0 0 3990 lb/hr - 8 hr Block Ave
2 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA
3 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA
3 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA
3 NOx 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA
3 Opacity 0 0 0 0 0 20 Percent - 6 min
3 CO 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA
3 CO 0 0 0 0 0 2406 lb/hr - 8 hr Block Ave
CMS Performance Summary - Hourly Summary
Point
Source Channel Monitor
Malfunction
Non-monitor
Malfunction
QA
Calibrations
Other
Known
Causes
Unknown
Causes
1 SO2 0 0 0 2 0
1 NOx 0 0 0 2 0
1 CO2 0 0 0 2 0
1 Opacity 1 0 9 4 0
1 CO 0 0 0 2 0
2 SO2 3 0 3 0 0
2 NOx 3 0 2 1 0
2 CO2 3 0 2 1 0
2 Opacity 0 0 10 1 0
2 CO 3 0 2 1 0
3 SO2 0 0 0 8 0
3 NOx 23 0 0 2 0
3 CO2 0 0 0 8 0
3 Opacity 0 0 11 5 0
3 CO 56 0 0 6 0
5
Type Code 280 (COMS Attenuator Filters) Procedure 3
Point Source
& Location
Attenuator
I.D.
Attenuator
Certification
Date
Certified
Attenuator
Opacity
OPLR,
SECR,
or
PLCF,
Corrected
Opacity
Value
Range
Low,
Mid, &
High
Certification
1-year or 5-
year
Unit 1 - 1A S13263 6/28/24 17.40 1.00 17.4 Low 1
Unit 1 - 1A S13268 6/28/24 26.60 1.00 26.6 Mid 1
Unit 1 - 1A S13249 6/28/24 46.90 1.00 46.9 High 1
Unit 1 - 1B S13263 6/28/24 17.40 1.00 17.4 Low 1
Unit 1 - 1B S13268 6/28/24 26.60 1.00 26.6 Mid 1
Unit 1 - 1B S13249 6/28/24 46.90 1.00 46.9 High 1
Unit 2 - 2A S13263 6/28/24 17.40 1.00 17.4 Low 1
Unit 2 - 2A S13268 6/28/24 26.60 1.00 26.6 Mid 1
Unit 2 - 2A S13249 6/28/24 46.90 1.00 46.9 High 1
Unit 2 - 2B S13263 6/28/24 17.40 1.00 17.4 Low 1
Unit 2 - 2B S13268 6/28/24 26.60 1.00 26.6 Mid 1
Unit 2 - 2B S13249 6/28/24 46.90 1.00 46.9 High 1
Unit 3 - 3 S13263 6/28/24 17.40 1.00 17.4 Low 1
Unit 3 - 3 S13268 6/28/24 26.60 1.00 26.6 Mid 1
Unit 3 - 3 S13249 6/28/24 46.90 1.00 46.9 High 1
Unit 3 - 3 S13263 6/28/24 17.40 1.00 17.4 Low 1
Unit 3 - 3 S13268 6/28/24 26.60 1.00 26.6 Mid 1
Unit 3 - 3 S13249 6/28/24 46.90 1.00 46.9 High 1
Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error)
Point
Source Location Audit Date
Opacity Monitor Response
(Average of 5) Mean Difference Calibration
Error (≤ 3%) Low Mid High
Unit 1 1A 10/1/24 17
Unit 1 1A 10/1/24 26 -0.640 0.007
Unit 1 1A 10/1/24 48 0.700 0.015
Unit 1 1B 10/1/24 17 0.020 0.001
Unit 1 1B 10/1/24 26 -0.630 0.007
Unit 1 1B 10/1/24 48 0.680 0.007
Unit 2 2A 10/7/24 18 0.180 0.005
Unit 2 2A 10/7/24 26 -0.490 0.007
Unit 2 2A 10/7/24 47 0.380 0.007
Unit 2 2B 10/7/24 18 0.200 0.002
Unit 2 2B 10/7/24 26 -0.320 0.003
Unit 2 2B 10/7/24 48 0.880 0.009
6
Unit 3 3 10/8/24 17 -0.120 0.002
Unit 3 3 10/8/24 26 -0.470 0.010
Unit 3 3 10/8/24 47 0.370 0.014
Unit 3 3 10/8/24 17 -0.060 0.001
Unit 3 3 10/8/24 26 -0.700 0.008
Unit 3 3 10/8/24 48 0.910 0.010
Type Code 282 (Annual Zero Alignment Audit) Procedure 3
Point
Source Location Audit
Date
Alternative
Zero Alignment
(Yes or No)
COM Clear
Condition
Zero
Response
(CCZR)
COM
Simulated
Zero
Response
(CSZR)
Zero
Alignment
Error
Difference
(CCZR)-
(CSZR)
Adjustment to
COM
Simulated Zero
Response
(CSZR)
(Yes or No)
1 1A 2/12/24 no 0.25 0.03 0 yes
1 1B 2/12/24 no -2.35 -0.03 -2 yes
2 2A 2/6/24 no 100.00 -0.02 100 yes
2 2B 2/6/24 no 0.83 -0.15 1 yes
3 3A 3/6/24 no 0.49 0.04 0 yes
3 3B 3/5/24 no 0.35 -0.07 0 yes
Summary of SO2 Emission Reduction
Percent Removal Required Percent
Reduction
Point
Source Channel Min Max Days in violation
1 SO2 94% 95% 80% 0
2 SO2 94% 95% 80% 0
3 SO2 94% 94% 90% 0
Pollutant Concentration
Exceeded Span of CEM
Monitor Outage During
Point Source Operation
Alternate
Sampling CEM Modifications
0 Hours 177 Hours 0 Hours 0 Events
SOURCE INSPECTION
SUMMARY EVALUATION: Hunter maintains its CEMS as required in R307-170 and 40 CFR 60.13.
7
CURRENT
RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related
problems that do not warrant issuing a violation. Periods of excess
emissions that were recorded by the CMS in service on each point source
during this reporting period are summarized in the SEDR and described
in Pivot Table 400 “Excess Emissions Review.”
Hunter was in compliance during this reporting period. No further
enforcement actions should be taken.
Hunter’s NSPS monitoring system meets the performance standards of
40 CFR 60, Appendix B Performance Specifications.
Hunter’s acid rain monitoring system meets the performance standards of
40 CFR 75 Acid Rain Performance Specifications.
HIGH PRIORITY
VIOLATOR (HPV): No
RECOMMENDATION
FOR NEXT INSPECTION: Check DAS for daily zero and span drift.
Check the QC program to ensure that monitor drift is being tracked and
that the source can identify excessive drift.
ATTACHMENTS: Excel spreadsheet review
Pacificorp Hunter EER 4Q2024
Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No
1 Type Code 100
(Company Information)Type Code Company Manager Company Name AIRS # Phone Number
Environmental
Contact
1 100 Laren Huntsman 01500101 435-748-6519 Jay Howard
1 100 0 0 0 0
1 Type Code 110
(Point Source Identification)Type Code Point Source
Quarter
1 - 4 Year
Point Source
Operating Hrs. in
Quarter
1 110 4 2024 2207.97
1 110 4 2024 2179.85
1 110 4 2024 2175.27
1 110 0 0 0
1 Type Code 200
(Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date
Monitor
Location
1 200 CO Thermo Scientific 48iQ 12111711815 0 2000 7/12/2021 Stack
1 200 CO2 Thermo Scientific 410iQ 12111711827 0 20 7/12/2021 Stack
1 200 NOx Thermo Scientific 42iQ 12111711830 0 400 7/12/2021 Stack
1 200 OpacityA Teledyne Lighthawk 560 ES 5603357 0 100 9/17/2021 1-1 BH
1 200 OpacityB Teledyne Lighthawk 560 ES 5603356 0 100 9/17/2021 1-2 BH
1 200 SO2 Thermo Scientific 43iQ 12111711833 60 600 7/12/2021 Stack
1 200 CO Thermo Scientific 48iQ 12111711816 0 2000 7/13/2021 Stack
1 200 CO2 Thermo Scientific 410iQ 12111711828 0 20 7/13/2021 Stack
1 200 NOx Thermo Scientific 42iQ 12111711831 0 400 7/13/2021 Stack
1 200 OpacityA Teledyne Lighthawk 560 ES 5603359 0 100 9/16/2021 2-1 BH
1 200 OpacityB Teledyne Lighthawk 560 ES 5603358 0 100 9/16/2021 2-2 BH
1 200 SO2 Thermo Scientific 43iQ 12111711834 60 600 7/12/2022 Stack
1 200 CO Thermo Scientific 48iQ 12111711817 0 2000 7/13/2021 Stack
1 200 CO2 Thermo Scientific 410iQ 12111711829 0 20 7/13/2021 Stack
1 200 NOx Thermo Scientific 42iQ 12111711832 0 400 7/13/2021 Stack
1 200 OpacityA Teledyne Lighthawk 560 ES 5603360 0 100 9/15/2021 3-1 BH Duct
1 200 OpacityB Teledyne Lighthawk 560 ES 5603361 0 100 9/15/2021 3-2 BH Duct
1 200 SO2 Thermo Scientific 43iQ 12111711835 60 600 7/13/2021 Stack
1 200 0 0 0 0 0 0 1/0/1900 0
1
Type Code310
(Excess Emissions)
SUMMARY REPORT
Type Code Channel
Total Hours of Excess
Emissions
Excess Emissions -
% of Total
Operating Hours
RC 701 Hours -
start
up/Shutdown
RC 702 Hours-
Control Equipment
Problems
RC 703 Hours -
Process Problems
RC 704, 706, 707
Hours -Other Known
Causes
RC 705 Hours -
Unknown
Causes
Emission
Limitation
Emission
Limitation
Units
Emission
Limitation
Averaging
Period
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 1.2 lb/MMBtu 3 hr ra
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.7 lb/MMBtu 3 hr ra
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA
1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3990 lb/hr 8 hr Block Ave
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 1.2 lb/MMBtu 3 hr ra
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.7 lb/MMBtu 3 hr ra
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA
1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3990 lb/hr 8 hr Block Ave
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA
1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 2406 lb/hr 8 hr Block Ave
1 310 0 0 0 0 0 0 0 0 0
Point Source
0
3
1
2
3
0
3
1
1
1
2
2
2
3
3
3
3
Pacificorp Hunter
0
1
1
1
1
1
1
2
2
2
2
2
1
1
1
2
2
1
1
2
2
2
2
3
3
3
3
3
3
0
Pacificorp Hunter EER 4Q2024
1 Type Code 300 (CMS
Performance Summary) Type Code Channel
Point Source Operating
Hours
Downtime - % of
Total Operating
Hours
Total CMS
Downtime
RC 721 Hours -
Monitor
Malfunction
RC 722 Hours -
Non-monitor
Malfunction
RC 723 Hours -
QA Calibrations
RC 724 Hours -
Other Known
Causes
RC 725
Hours -
Unknown
Causes
1 TRUE 300 SO2 2207.97 0.09% 1.98 0 0 0 1.98 0
1 TRUE 300 NOx 2207.97 0.09% 1.98 0 0 0 1.98 0
1 TRUE 300 CO2 2207.97 0.09% 1.97 0 0 0 1.97 0
1 TRUE 300 Opacity 2207.97 0.67% 14.79 0.83 0.17 9.47 4.32 0
1 TRUE 300 CO 2207.97 0.09% 1.98 0 0 0 1.98 0
1 TRUE 300 SO2 2179.85 0.27% 5.9 3 0 2.9 0 0
1 TRUE 300 NOx 2179.85 0.28% 6 3 0 2 1 0
1 TRUE 300 CO2 2179.85 0.28% 6 3 0 2 1 0
1 TRUE 300 Opacity 2179.85 0.52% 11.4 0.2 0.1 9.7 1.4 0
1 TRUE 300 CO 2179.85 0.28% 6 3 0 2 1 0
1 TRUE 300 SO2 2175.27 0.36% 7.9 0 0 0 7.9 0
1 TRUE 300 NOx 2175.27 1.15% 25 23 0 0 2 0
1 TRUE 300 CO2 2175.27 0.36% 7.9 0 0 0 7.9 0
1 TRUE 300 Opacity 2175.27 0.75% 16.4 0.2 0.2 11 5 0
1 TRUE 300 CO 2175.27 2.85% 62 56 0 0 6 0
1 300 0 0 0 0 0 0
1 Type Code 250
(Performance Specification
RATA Results)
Type Code Channel
Date of Most Current
RATA
Date of Preceding
RATA
Months Between
RATA's
Units of
Measurement CEM Value Reference Method
Value
Relative
accuracy Pass/ Fail
1 64 Days 250 CO 10/22/24 08/19/24 2.1 lb/mmBtu 0.1 0.1 5.00% pass
1 64 Days 250 CO 10/22/24 08/19/24 2.1 lb/hr 146.5 118.3 0.90% pass
1 64 Days 250 CO2 10/22/24 08/19/24 2.1 Percent 8.7 8.7 1.20% pass
1 64 Days 250 NOx 10/22/24 08/19/24 2.1 #/MMBtu 0.2 0.2 2.20% pass
1 64 Days 250 SO2 10/22/24 08/19/24 2.1 ppm 22.5 22.8 1.60% pass
1 167 Days 250 CO 10/16/24 05/02/24 5.5 lb/mmBtu 0.03 0.02 3.90% pass
1 167 Days 250 CO 10/16/24 05/02/24 5.5 lb/hr 55 31 0.60% pass
1 167 Days 250 CO2 10/16/24 05/02/24 5.5 Percent 8.9 8.9 0.60% pass
1 167 Days 250 NOx 10/16/24 05/02/24 5.5 #/MMBtu 0.1 0.1 2.30% pass
1 167 Days 250 SO2 10/16/24 05/02/24 5.5 ppm 19.5 19.3 1.60% pass
1 392 Days 250 CO 11/20/24 10/25/23 12.9 lb/mmBtu 0.023 0.01 6.80% pass
1 392 Days 250 CO 11/20/24 10/25/23 12.9 lb/hr 42.1 18.9 1.00% pass
1 392 Days 250 CO2 11/20/24 10/25/23 12.9 Percent 8.8 8.6 2.70% pass
1 392 Days 250 NOx 11/20/24 10/25/23 12.9 #/MMBtu 0.2 0.2 3.20% pass
1 392 Days 250 SO2 11/20/24 10/25/23 12.9 ppm 25.3 23.7 7.20% pass
1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0
Point Source
Point Source
0
2
2
2
2
3
1
1
2
2
2
1
1
1
3
2
2
3
3
3
3
0
1
1
1
1
2
1
3
3
3
3
Pacificorp Hunter EER 4Q2024
1 Type Code 260
(CGA Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder
Expiration Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 260 CO 10/22/24 low CC437416 09/23/32 p1 ppm 492.6 501 -1.70% PASS 0
1 Valid Cal. Gas 260 CO 10/22/24 mid DT0027442 12/20/27 p1 ppm 1145.2 1118 2.40% PASS 0
1 Valid Cal. Gas 260 CO 10/22/24 low CC280314 09/23/32 p1 ppm 506.2 501.3 1.00% PASS 0
1 Valid Cal. Gas 260 CO 10/22/24 mid DT0011509 12/20/27 p1 ppm 1116.1 1117 -0.10% PASS 0
1 Valid Cal. Gas 260 CO 10/23/24 low SA7143 08/23/27 p1 ppm 537 520 3.30% PASS 0
1 Valid Cal. Gas 260 CO 10/23/24 mid AAL073426 06/28/28 p1 ppm 1105.3 1095 0.90% PASS 0
1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1 Type Code 270
(Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder
Expiration Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 270 CO2 10/22/24 low CC437416 09/23/32 P1 percent 4.87 5 2.70% PASS 0
1 Valid Cal. Gas 270 CO2 10/20/24 mid EB0105186 09/03/32 P1 percent 10.9 10.9 0.00% PASS 0
1 Valid Cal. Gas 270 CO2 10/22/24 high EB0086622 10/14/32 P1 percent 18.17 18 0.90% PASS 0
1 Valid Cal. Gas 270 NOx 10/22/24 low CC437416 09/23/32 P1 ppm 50.53 50.4 0% PASS 0
1 Valid Cal. Gas 270 NOx 10/22/24 mid EB0105186 09/03/32 P1 ppm 109.27 110.9 2% PASS 0
1 Valid Cal. Gas 270 NOx 10/22/24 high EB0086622 10/14/32 P1 ppm 179.5 181.8 1% PASS 0
1 Valid Cal. Gas 270 SO2 10/22/24 low CC437416 09/23/32 P1 ppm 149.3 154.1 3.20% PASS 0
1 Valid Cal. Gas 270 SO2 10/22/24 mid EB0105186 09/23/32 P1 ppm 329.43 328.1 0.40% PASS 0
1 Valid Cal. Gas 270 SO2 10/22/24 high EB0086622 10/14/32 P1 ppm 526.07 536 1.90% PASS 0
1 Valid Cal. Gas 270 CO2 10/22/24 low CC280314 09/23/32 P1 percent 4.87 5 2.70% PASS 0
1 Valid Cal. Gas 270 CO2 10/22/24 mid CC480573 09/03/32 P1 percent 10.8 10.9 0.90% PASS 0
1 Valid Cal. Gas 270 CO2 10/22/24 high EB0067529 10/07/32 P1 percent 17.9 18 0.60% PASS 0
1 Valid Cal. Gas 270 NOx 10/22/24 low CC280314 09/23/32 P1 ppm 49.53 50.5 1.90% PASS 0
1 Valid Cal. Gas 270 NOx 10/22/24 mid CC480573 09/03/32 P1 ppm 107.17 110.1 2.70% PASS 0
1 Valid Cal. Gas 270 NOx 10/22/24 high EB0067529 10/07/32 P1 ppm 177.2 183.2 3.30% PASS 0
1 Valid Cal. Gas 270 SO2 10/22/24 low CC280314 09/23/32 P1 ppm 155.9 149.3 4% PASS 0
1 Valid Cal. Gas 270 SO2 10/22/24 mid CC480573 09/03/32 P1 ppm 337.97 334.2 1% PASS 0
1 Valid Cal. Gas 270 SO2 10/22/24 high EB0067529 10/07/32 P1 ppm 523.63 531.2 1% PASS 0
1 Valid Cal. Gas 270 CO2 10/23/24 low SA7143 08/23/27 P1 percent 5 4.9 2.00% PASS 0
1 Valid Cal. Gas 270 CO2 10/23/24 mid CC498041 07/01/32 P1 percent 11.03 11 0.30% PASS 0
1 Valid Cal. Gas 270 CO2 10/23/24 high CC155742 08/26/27 P1 percent 17.7 17.6 0.60% PASS 0
1 Valid Cal. Gas 270 NOx 10/23/24 low SA7143 08/23/27 P1 ppm 110.57 110 0.50% PASS 0
1 Valid Cal. Gas 270 NOx 10/23/24 mid CC498041 07/01/32 P1 ppm 216.07 215.3 0.40% PASS 0
1 Valid Cal. Gas 270 NOx 10/23/24 high CC155742 08/26/27 P1 ppm 350.97 358 2.00% PASS 0
1 Valid Cal. Gas 270 SO2 10/23/24 low SA7143 08/23/27 P1 ppm 151.93 146.2 3.90% PASS 0
1 Valid Cal. Gas 270 SO2 10/23/24 mid CC498041 07/01/32 P1 ppm 334.43 330 1.30% PASS 0
1 Valid Cal. Gas 270 SO2 10/23/24 high CC155742 08/26/27 P1 ppm 535.73 539 0.60% PASS 0
1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code Channel Start Date Start Time End Date End Time Hours
1 0 0 0 1/0/00 0:00 1/0/00 0:00
1
1 None Reported
1 0 TC 220 Hours 176.63 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00
1 177.20 TC 300 Hours 0.57 FALSE
None Reported None Reported Yes Yes None Reported None Reported
2
2
2
3
3
3
3
3
3
3
0
Point Source
Point Source
Point Source
Yes
1
1
Type Code 550
(Changes in Operation in
Control Equipment When
CEM Data Not Available)
Type Code 500
(Boiler Operating Days
w/o 18 Hours of Data)
Type Code 450
(Data Excluded)
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code 220
(Monitor Outage
During Point Source Operation)
Type Code 230
(Manual Sample - Alternate
Sampling During Monitor
Outage)
Type Code 240
(CEM Modifications)
Type Code 530
(Excess Emissions During
Emergency Conditions)
2
2
3
3
0
2
3
3
1
1
1
1
2
1
1
1
1
1
2
2
2
2
0
Pacificorp Hunter EER 4Q2024
Relative Accuracy Overview
Point Source Channel
Date of Most
Current
RATA
Date of
Preceding
RATA
Months Between
RATA's
Units
Measured CEM Value Reference Method
Value
Relative
Accuracy Pass/ Fail 2024
1 CO 10/22/24 08/19/24 2.1 lb/mmBtu 0.1 0.10 5.00% pass
1 CO 10/22/24 08/19/24 2.1 lb/hr 146.5 118.30 0.90% pass
1 CO2 10/22/24 08/19/24 2.1 Percent 8.7 8.70 1.20% pass
1 NOx 10/22/24 08/19/24 2.1 #/MMBtu 0.2 0.20 2.20% pass
1 SO2 10/22/24 08/19/24 2.1 ppm 22.5 22.80 1.60% pass
2 CO 10/16/24 05/02/24 5.5 lb/mmBtu 0.03 0.02 3.90% pass
2 CO 10/16/24 05/02/24 5.5 lb/hr 55 31.00 0.60% pass
2 CO2 10/16/24 05/02/24 5.5 Percent 8.9 8.90 0.60% pass
2 NOx 10/16/24 05/02/24 5.5 #/MMBtu 0.1 0.10 2.30% pass
2 SO2 10/16/24 05/02/24 5.5 ppm 19.5 19.30 1.60% pass
3 CO 11/20/24 10/25/23 12.9 lb/mmBtu 0.023 0.01 6.80% pass
3 CO 11/20/24 10/25/23 12.9 lb/hr 42.1 18.90 1.00% pass
3 CO2 11/20/24 10/25/23 12.9 Percent 8.8 8.60 2.70% pass
3 NOx 11/20/24 10/25/23 12.9 #/MMBtu 0.2 0.20 3.20% pass
3 SO2 11/20/24 10/25/23 12.9 ppm 25.3 23.70 7.20% pass
*
NSPS CGA Fourth 2024
Audit Gas Ranges Audit Gas Ranges
AP1 Low AP2 Low AP1 High AP2 High
1 CO 10/22/24 2000 501 400 to 600
1 CO 10/22/24 2000 1118 1000 to 1200
2 CO 10/22/24 2000 501.3 400 to 600
2 CO 10/22/24 2000 1117 1000 to 1200
3 CO 10/23/24 2000 520 400 to 600
3 CO 10/23/24 2000 1095 1000 to 1200
*
Acid Rain Audit Linearity Fourth 2024
Low Span Gas Ranges High Span Gas Ranges
Low Mid High Low Mid High
1 CO2 10/22/24 20 5 4 to 6
1 CO2 10/20/24 20 10.9 10 to 12
1 CO2 10/22/24 20 18 16 to 20
1 NOx 10/22/24 400 50.4 80 to 120
1 NOx 10/22/24 400 110.9 200 to 240
1 NOx 10/22/24 400 181.8 320 to 400
1 SO2 10/22/24 600 154.1 120 to 180
1 SO2 10/22/24 600 328.1 300 to 360
1 SO2 10/22/24 600 536 480 to 600
2 CO2 10/22/24 20 5 4 to 6
2 CO2 10/22/24 20 10.9 10 to 12
2 CO2 10/22/24 20 18 16 to 20
2 NOx 10/22/24 400 50.5 80 to 120
2 NOx 10/22/24 400 110.1 200 to 240
2 NOx 10/22/24 400 183.2 320 to 400
2 SO2 10/22/24 600 149.3 120 to 180
2 SO2 10/22/24 600 334.2 300 to 360
2 SO2 10/22/24 600 531.2 480 to 600
3 CO2 10/23/24 20 4.9 4 to 6
3 CO2 10/23/24 20 11 10 to 12
3 CO2 10/23/24 20 17.6 16 to 20
3 NOx 10/23/24 400 110 80 to 120
3 NOx 10/23/24 400 215.3 200 to 240
3 NOx 10/23/24 400 358 320 to 400
3 SO2 10/23/24 600 146.2 120 to 180
3 SO2 10/23/24 600 330 300 to 360
3 SO2 10/23/24 600 539 480 to 600
*
Audit Gas Used
Point Source Channel Audit Date Low Span
Point Source Channel Audit Date Low Span
Audit Gas Used High Span Audit Gas Used
High SpanAudit Gas Used
Pacificorp Hunter EER 4Q2024
Type Code 280 (COMS Attenuator Filters) Procedure 3
Point Source Location
Attenuator
I.D.
Attenuator
Certification Date
Certified Attenuator
Opacity
OPLR,
SECR, or
PLCF,
Corrected Opacity
Value
Range
Low, Mid, & High
Certification
1-year or 5-year
Unit 1 1A S13263 6/28/24 17 1 17.4 Low 1
Unit 1 1A S13268 6/28/24 27 1 26.6 Mid 1
Unit 1 1A S13249 6/28/24 47 1 46.9 High 1
Unit 1 1B S13263 6/28/24 17.4 1 17.4 Low 1
Unit 1 1B S13268 6/28/24 26.6 1 26.6 Mid 1
Unit 1 1B S13249 6/28/24 46.9 1 46.9 High 1
Unit 2 2A S13263 6/28/24 17.4 1 17.4 Low 1
Unit 2 2A S13268 6/28/24 26.6 1 26.6 Mid 1
Unit 2 2A S13249 6/28/24 46.9 1 46.9 High 1
Unit 2 2B S13263 6/28/24 17.4 1 17.4 Low 1
Unit 2 2B S13268 6/28/24 26.6 1 26.6 Mid 1
Unit 2 2B S13249 6/28/24 46.9 1 46.9 High 1
Unit 3 3 S13263 6/28/24 17.4 1 17.4 Low 1
Unit 3 3 S13268 6/28/24 26.6 1 26.6 Mid 1
Unit 3 3 S13249 6/28/24 46.9 1 46.9 High 1
Unit 3 3 S13263 6/28/24 17.4 1 17.4 Low 1
Unit 3 3 S13268 6/28/24 26.6 1 26.6 Mid 1
Unit 3 3 S13249 6/28/24 46.9 1 46.9 High 1
*
Opacity Monitor Response (Average of 5)
Low Range Mid Range High Range
Unit 1 1A 10/1/24 17 0.000 0.000 0.000 0.000
Unit 1 1A 10/1/24 26 -0.640 0.045 0.056 0.007
Unit 1 1A 10/1/24 48 0.700 0.626 0.777 0.015
Unit 1 1B 10/1/24 17 0.020 0.045 0.056 0.001
Unit 1 1B 10/1/24 26 -0.630 0.022 0.028 0.007
Unit 1 1B 10/1/24 48 0.680 0.000 0.000 0.007
Unit 2 2A 10/7/24 18 0.180 0.249 0.309 0.005
Unit 2 2A 10/7/24 26 -0.490 0.157 0.194 0.007
Unit 2 2A 10/7/24 47 0.380 0.235 0.291 0.007
Unit 2 2B 10/7/24 18 0.200 0.000 0.000 0.002
Unit 2 2B 10/7/24 26 -0.320 0.000 0.000 0.003
Unit 2 2B 10/7/24 48 0.880 0.000 0.000 0.009
Unit 3 3 10/8/24 17 -0.120 0.084 0.104 0.002
Unit 3 3 10/8/24 26 -0.470 0.450 0.559 0.010
Unit 3 3 10/8/24 47 0.370 0.818 1.016 0.014
Unit 3 3 10/8/24 17 -0.060 0.055 0.068 0.001
Unit 3 3 10/8/24 26 -0.700 0.045 0.056 0.008
Unit 3 3 10/8/24 48 0.910 0.045 0.056 0.010
*
Point Source Location Audit Date
Alternitive Zero
Alignment
(Yes or No)
COM Clear
Condition Zero
Response
(CCZR)
COM Simulated
Zero Response
(CSZR)
Zero Alignment
Error Difference
(CCZR)-(CSZR)
Adjustment to COM
Simulated Zero
Response
(CSZR)
(Yes or No)
1 1A 2/12/24 no 0.250 0.030 0.220 yes
1 1B 2/12/24 no -2.350 -0.030 -2.320 yes
2 2A 2/6/24 no 100.000 -0.020 100.020 yes
2 2B 2/6/24 no 0.830 -0.150 0.980 yes
3 3A 3/6/24 no 0.490 0.040 0.450 yes
3 3B 3/5/24 no 0.350 -0.070 0.420 yes
Type Code 282 (Procedure 3 - Annual Zero Alignment Audit)
Point
Source Location Audit Date Mean Difference Standard Deviation
Confidence
Coefficient
Calibration
Error (≤ 3%)
Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error)
Pacificorp Hunter EER 4Q2024
Monitoring Information TC 210, 230, & 240
Type Code 210
(Pollutant Concentration Exceeded Span of CEM) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 230
(Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 240
(CEM Modifications) - 100 (All)
*
Count of Channel Column Labels
Row Labels (blank) Grand Total
(blank)
(blank)
Grand Total
Pacificorp Hunter EER 4Q2024
Type Code 220
(Monitor Outage During Point Source Operation) - 600 (All)
*
Sum of Hours Column Labels
Row Labels 723 722 724 721 Grand Total
1
Opacity
The monitor was unavailable during the daily monitor calibration as
required by 40 CFR parts 60 and 75.4.67 4.67
Quarterly filter audit performed followed by auto calibration.4.02 4.02
An instantaneous power loss to the remote unit caused the remote to
initiate a startup sequence during which valid data was not available.
0.08 0.08
Following maintenance, a daily calibration reference gas cylinder was not
valved in, resulting in a calibration fail out of control indication. The
cylinder was valved in and a second calibration was initiated.
2.17 2.17
Trouble shooting the 8864. Reset the 8864 due to 24 hr averages being
stuck in the DCS. The reset did not fix the issue due to 8864 not being the
problem. The data was correct in stackvision. The last update from ESC
altered some points that didn't allow DCS to read the data.
2.15 2.15
The sample system became plugged resulting in insufficient sample flow
to the analyzers. The sample system was cleaned and the analyzer(s)
were returned to service.
0.83 0.83
A loss of power to the stack and or UPS system resulted in a loss of valid
data. Stack power and or UPS power was restored and the monitor was
returned to service.
0.08 0.08
Opacity monitor purge air filters were changed, optical surfaces were
inspected and cleaned and electrical connections checked. The monitor
was then returned to service
0.78 0.78
CO2
Trouble shooting the 8864. Reset the 8864 due to 24 hr averages being
stuck in the DCS. The reset did not fix the issue due to 8864 not being the
problem. The data was correct in stackvision. The last update from ESC
altered some points that didn't allow DCS to read the data.
1.97 1.97
CO
Trouble shooting the 8864. Reset the 8864 due to 24 hr averages being
stuck in the DCS. The reset did not fix the issue due to 8864 not being the
problem. The data was correct in stackvision. The last update from ESC
altered some points that didn't allow DCS to read the data.
1.98 1.98
NOx
Trouble shooting the 8864. Reset the 8864 due to 24 hr averages being
stuck in the DCS. The reset did not fix the issue due to 8864 not being the
problem. The data was correct in stackvision. The last update from ESC
altered some points that didn't allow DCS to read the data.
1.98 1.98
SO2
Trouble shooting the 8864. Reset the 8864 due to 24 hr averages being
stuck in the DCS. The reset did not fix the issue due to 8864 not being the
problem. The data was correct in stackvision. The last update from ESC
altered some points that didn't allow DCS to read the data.
1.98 1.98
2
Opacity
The monitor was unavailable during the daily monitor calibration as
required by 40 CFR parts 60 and 75.6.25 6.25
Quarterly filter audit performed followed by auto calibration.2.72 2.72
Pacificorp Hunter EER 4Q2024
Sum of Hours Column Labels
Row Labels 723 722 724 721 Grand Total
An instantaneous power loss to the remote unit caused the remote to
initiate a startup sequence during which valid data was not available.
0.08 0.08
Following maintenance, a daily calibration reference gas cylinder was not
valved in, resulting in a calibration fail out of control indication. The
cylinder was valved in and a second calibration was initiated.
1.00 1.00
The sample system became plugged resulting in insufficient sample flow
to the analyzers. The sample system was cleaned and the analyzer(s)
were returned to service.
0.25 0.25
Opacity monitor purge air filters were changed, optical surfaces were
inspected and cleaned and electrical connections checked. The monitor
was then returned to service
0.48 0.48
Invalid 6 minute due to process off time and/ or calibration during hour 0.43 0.43
A calibration drift test was performed on one or more analyzers in order
to verify system accuracy.0.27 0.27
CO2
Quarterly linearity testing performed.0.98 0.98
A calibration drift test was performed on one or more analyzers in order
to verify system accuracy.0.98 0.98
Purge air solenoid valve stuck open caused purge air to continue to flow
into the sample system, resulting in invalid data. The solenoid valve was
repaired or replaced. An auto calibration was initiated and the monitors
returned to service.
2.95 2.95
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
0.98 0.98
CO
Quarterly linearity testing performed.0.98 0.98
A calibration drift test was performed on one or more analyzers in order
to verify system accuracy.0.98 0.98
Purge air solenoid valve stuck open caused purge air to continue to flow
into the sample system, resulting in invalid data. The solenoid valve was
repaired or replaced. An auto calibration was initiated and the monitors
returned to service.
2.95 2.95
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
0.98 0.98
NOx
Quarterly linearity testing performed.0.98 0.98
A calibration drift test was performed on one or more analyzers in order
to verify system accuracy.0.98 0.98
Purge air solenoid valve stuck open caused purge air to continue to flow
into the sample system, resulting in invalid data. The solenoid valve was
repaired or replaced. An auto calibration was initiated and the monitors
returned to service.
2.95 2.95
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
0.98 0.98
SO2
Quarterly linearity testing performed.0.98 0.98
A calibration drift test was performed on one or more analyzers in order
to verify system accuracy.1.97 1.97
Purge air solenoid valve stuck open caused purge air to continue to flow
into the sample system, resulting in invalid data. The solenoid valve was
repaired or replaced. An auto calibration was initiated and the monitors
returned to service.
2.95 2.95
3
Opacity
Pacificorp Hunter EER 4Q2024
Sum of Hours Column Labels
Row Labels 723 722 724 721 Grand Total
The monitor was unavailable during the daily monitor calibration as
required by 40 CFR parts 60 and 75.7.85 7.85
Quarterly filter audit performed followed by auto calibration.2.95 2.95
An instantaneous power loss to the remote unit caused the remote to
initiate a startup sequence during which valid data was not available.
0.08 0.08
A loss of power to the stack and or UPS system resulted in a loss of valid
data. Stack power and or UPS power was restored and the monitor was
returned to service.
0.08 0.08
Invalid 6 minute due to process off time and/ or calibration during hour 0.17 0.17
Opacity monitor retro reflector lenses were cleaned and inspected. No
adjustments were made to the analyzer. Followed by an auto cal.
4.87 4.87
Opacity Monitor calibration arm failed causing the monitor to fail
calibration. Causing data to be out of control. Hands free calibration
completed and passed.
0.18 0.18
CO2
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
7.92 7.92
CO
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
5.95 5.95
IR source on the analyzer failed. Source was replaced followed by an
auto cal.27.98 27.98
The monitor failed its daily/startup calibration. The monitor was
recalibrated and returned to service.27.98 27.98
NOx
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
1.97 1.97
The monitor failed calibration out of control. The circuit board, and or
the UV source were replaced or adjusted. Adjust factors were reset.
Monitor was calibrated and returned to service.
15.98 15.98
The NOx, CO wheel chopper motor failed. The motor was replaced and
the monitor was returned to service.3.98 3.98
Analyzer was in fault do to a board. Power was cycled and the fault
cleared. Initiated auto calibration 2.98 2.98
SO2
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
7.92 7.92
Grand Total 38.83 0.42 45.40 91.98 176.63
Pacificorp Hunter EER 4Q2024
Opy *
Opy Count of Magnitude of Emissions Column Labels
Opy Row Labels Grand Total
Opy Grand Total
SO2 *
SO2 Type Code 410 (SO2) - 6000 (All)
SO2 *
SO2 Count of Magnitude of Emissions Column Labels
SO2 Row Labels Grand Total
SO2 Grand Total
NOx d *
NOx d Type Code 421 (Daily NOx Emissions) - 500 (All)
NOx d *
NOx d Count of Reason Code Column Labels
NOx d Row Labels (blank)q Grand Total
NOx d 3
NOx d #N/A 1 1
NOx d Grand Total 1 1
CO *
CO Type Code 440
(CO) - 6000 (All)
CO *
CO Count of Magnitude of Emissions Column Labels
CO Row Labels Grand Total
CO Grand Total
Dat Ex *
Dat Ex Type Code 450
(Data Excluded) - 6000 (All)
Dat Ex *
Dat Ex Count of Channel Column Labels
Dat Ex Row Labels 724 721 Grand Total
Dat Ex 3
Dat Ex CO 1 2 3
Dat Ex
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
1 1
Dat Ex IR source on the analyzer failed. Source was replaced followed by
an auto cal.1 1
Dat Ex The monitor failed its daily/startup calibration. The monitor was
recalibrated and returned to service.1 1
Dat Ex NOx 2 1 3
Dat Ex
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
2 2
Dat Ex Analyzer was in fault do to a board. Power was cycled and the fault
cleared. Initiated auto calibration 1 1
Dat Ex SO2 3 3
Dat Ex
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
3 3
Dat Ex Grand Total 6 3 9
Pacificorp Hunter EER 4Q2024
Type Code 500
Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of
Data) After February 28, 2005 (90% Operating Hours For each 30 BOD)
- 500
(All)
*
Count of Channel Column Labels
Row Labels (blank)701 Grand Total
(blank)
(blank)
(blank)
3
SO2 1 1
The unit was removed from service in a controlled fashion in order
to repair leaks in the startup boiler feed pump. The leak was
repaired and the unit returned to service.
1 1
NOx 1 1
The unit was removed from service in a controlled fashion in order
to repair leaks in the startup boiler feed pump. The leak was
repaired and the unit returned to service.
1 1
Grand Total 2 2
*
Type Code 510
(F-factor, Equations & Conversion Factors) - 500 (All)
Count of F-factor Column Labels
Row Labels SO2 NOx Grand Total
1
1800 1 1 2
2
1800 1 1 2
3
1800 1 1 2
Grand Total 3 3 6
*
Type Code 520
(Minimum Data Not
Obtained <22/30 BODs) - 500
(All)
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 530
(Excess Emissions During Emergency Conditions) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 540
(Fuel Pre-treatment Credit SO2) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
TypeCode 550
(Changes in Operation in Control Equipment When CEM Data Not
Available) - 500
(All)
Column Labels
Row Labels Grand Total
Grand Total