HomeMy WebLinkAboutDAQ-2025-000837.rAf
COMPASS
MINERALS
\-/
Compass Minerals
755 N 10500 W
Ogden, UT 84404
www.compassminerals.com
T (801) 731-3100
January 23,2025
Mr. Bryce Bird
Utah Division of Air Quality
195 North 1950 West
Salt Lake City, Utah 84174
i',i\/i5|oN oF AIR (lllnLlTY
RE:40 CFR 63 Subpart DDDDD Compliance Certification (Operating Permit No. 5700001004)
Mr. Bird,
ln accordance with Operating Permit provision ll.B.20.e and Utah Administrative Code (UAC)
R307-415-5c(5), the following compliance certification is submitted for Compass Minerals Ogden lnc.
(Compass Minerals). This compliance certification covers the period from 07/03/2019 to 7213U2O24
and includes identification of each term or condition of the permit that is the basis for this certification,
the compliance status of each identified term or condition, and the methods used to determine
compliance status.
On July 26rh,2024 Zeeco performed a tune up on Boilers #1 and #2 per the requirements listed
in 40 CFR 63.7540(a)(10)(i)through (vi). A detailed description of the requirements, as well as the work
performed by Zeeco is listed below.
Per 40 CFR 63.7540 (aX10)(i): Zeeco inspected the burners and cleaned and replaced as
needed components ofthe burners.
Per 40 CFR 53.7540 (aX10Xii): Zeeco inspected the flame pattern and adjusted the
burner as necessary to optimize the flame pattern consistent with manufacturer's
specifications.
Per 40 CFR 63.7540 (aX1OXiii): Zeeco inspected the system controlling the air-to-fuel
ratio and ensured that they were calibrated and functioning properly.
Per 40 CFR 63.7540 (aX10Xiv): Zeeco optimized the total emissions of CO and NOx
consistent with the manufacturer's specifications.
Per 40 CFR 63.7540 (aX10Xv): Zeeco measured concentrations in the effluent stream,
please see attached report.
Per 40 CFR 53.7540 (aX10)(vi): Compass maintains these reports on-site.
Please contact lan Wright (wrishti@compassminerals.com, (801) 732-3011) if you have any
questions regarding the information provided.
REVIEWED
Initials JBR Date 1/12/2025
Comp Status Meets
File # 10917 Blue 2
both boilers tune up
.zAr
COMPASS
MINERALS
\-/
Respectfully,
Compass Mlnerals
765 N 10500 W
Ogden, UT 84404
T (801) 731-3100
Ken Potts
Plant Manager
Compass Minerals Ogden lnc.
Cc: EPA Region 8
. Boiler Burners
. Duct Burners
. Burner Monogement Systems
80 Spring Lane
Plainville, CT 06062 USA
Phone: 918-893-8598
Fax: 918-251-5519
CUSTOMER: Compass Minerals
PO#:
ZEECO S.O.:
DATE: 7126124
PROJECT NAME: Compass Minerals
PERSONNEL CONTACTED: Aaron Ried
SERVICE TECHNICIAN: Scott Flatt
ATTACHMENTS: N/A
, , ', . l',1 ;6 ii 1'171 ' 1
-1
1:
i', ,' ::'rr.'NlAi- O' IAL ITY-l
I
i
1. Safety checks were performed by site personnel on boilers 1 and 2.
2. Site installed new Pitot tubes for the Air flow in Boiler #1.
3. Zeroed and checked air flow transmitter on boiler ff1 and set upper range value.
4. Tuned Boiler # 1 combustion. Tuned airflow to match Gas flow for the best efficiency, Nox was
under 9 ppm throughout the firing range.
5.
6.
7.
Site installed new Pitot tubes for the Air flow in Boiler #2.
Zeroed and checked air flow transmitter on boiler #2 and set upper range value.
Tuned Boiler # 2 combustion. Tuned airflow to match Gas flow for the best efficiency, Nox was
under 9 ppm throughout the firing range.