Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
DAQ-2025-000499
1 DAQC-066-25 Site ID 12524 (B5) MEMORANDUM TO: FILE – PACIFICORP – Currant Creek Power Plant THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Rob Leishman, Environmental Scientist DATE: January 21, 2025 SUBJECT: PacifiCorp – Currant Creek Power Plant (Currant Creek), Major, NSPS, HAPs, Title IV, Juab County, FRS # UT00000049002300026 INSPECTION TYPE: State Electronic Data Report (SEDR) Review REVIEW DATE: January 21, 2025 SOURCE LOCATION: Near Mona Reservoir/Juab County SOURCE CONTACT: David Blackburn – 435-623-3816 APPLICABLE REGULATIONS: Approval Order DAQE-AN12524009-15 dated January 23, 2015 - New Source Performance Standards (NSPS) Subparts A, Da, Dc, and GG, applies to this source. SOURCE INSPECTION EVALUATION: With the exception of sources that only monitor for opacity, quarterly report memoranda will only address the findings of the quarterly report. Approval Order and Title V permit conditions addressing continuous emission monitoring requirements will be addressed in Currant Creek’s relative accuracy performance specification test review memorandum. SEDR Review Fourth Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation HRSG1A 1803 NOx 100% 07/07/21 01/30/24 HRSG1A NOx 0.00 2.25 ppmvd at 15%O2 - 3 hour HRSG1A 1803 CO 100% 12/11/24 01/30/24 HRSG1A CO 0.00 3 ppmvd at 15%O2 - 3 hour 1 8 2 2 Fourth Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation HRSG1A 1803 O2 100% 12/11/24 01/30/24 HRSG1B NOx 0.00 2.25 ppmvd at 15%O2 - 3 hour HRSG1B 2142 NOx 100% 12/04/24 01/31/24 HRSG1B CO 0.00 3 ppmvd at 15%O2 - 3 hour HRSG1B 2142 CO 99% 12/04/24 01/31/24 HRSG1B 2142 O2 99% 09/04/24 01/31/24 Excess Emission Report - Hourly Summary Point Source Channel Startup & Shutdown Control Equipment Problems Process Problems Other Known Causes Unknown Causes Emission Limit HRSG1A NOx 0 0 0 0 0 2.25 ppmvd at 15%O2 - 3 hour HRSG1A CO 0 0 0 0 0 3 ppmvd at 15%O2 - 3 hour HRSG1B NOx 0 0 0 0 0 2.25 ppmvd at 15%O2 - 3 hour HRSG1B CO 0 0 0 0 0 3 ppmvd at 15%O2 - 3 hour CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes HRSG1A NOx 4 0 0 0 0 HRSG1A CO 4 0 0 0 0 HRSG1A O2 4 0 0 0 0 HRSG1B NOx 0 0 0 6 0 HRSG1B CO 10 0 4 4 0 HRSG1B O2 10 0 0 5 0 Pollutant Concentration Exceeded Span of CEM Monitor Outage During Point Source Operation Alternate Sampling CEM Modifications 0 Hours 51 Hours 0 Hours 0 Events 3 SOURCE INSPECTION SUMMARY EVALUATION: Currant Creek maintains its CEMS as required in R307-170 and 40 CFR 60.13. CURRENT RECOMMENDATIONS: All other deviations appear to be a result of breakdown or process related problems that do not warrant issuing a violation. Periods of excess emissions that were recorded by the CMS in service on each point source during this reporting period are summarized in the SEDR and described in Pivot Table 400 “Excess Emissions Review.” Currant Creek was in compliance during this reporting period. No further enforcement action is recommended. Currant Creek’s NSPS monitoring system meets the performance standards of 40 CFR 60, Appendix B Performance Specifications. Currant Creek’s acid rain monitoring system meets the performance standards of 40 CFR 75 Acid Rain Performance Specifications. HPV: No RECOMMENDATION FOR NEXT INSPECTION: Check DAS for daily zero and span drift. Check the QC program to ensure that monitor drift is being tracked and that the source can identify excessive drift. ATTACHMENTS: Excel spreadsheet review Pacificorp Currant Creek EER 4Q2024 Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No 1 Type Code 100 (Company Information)Type Code Company Manager Company Name AIRS # Phone Number Environmental Contact 1 100 Tyson Kesler 02300026 435-623-3813 David Blackburn 1 100 0 0 0 0 1 Type Code 110 (Point Source Identification)Type Code Point Source Quarter 1 - 4 Year Point Source Operating Hrs. in Quarter 1 110 4 2024 1803.7 1 110 4 2024 2142.9 1 110 0 0 0 1 Type Code 200 (Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date Monitor Location 1 200 CO THERMO 48iQ-LS 1192734481 10 1200 3/12/2020 Shelter 1 200 NOx THERMO 42iQ-LS 1192634350 10 200 10/7/2019 Shelter 1 200 O2 THERMO 48iQ-LS 1192734481 0 25 3/12/2020 Shelter 1 200 CO THERMO 48iQ-LS 1192734482 10 1200 3/12/2020 Shelter 1 200 NOx THERMO 42iQ-LS 1192734472 10 200 3/12/2020 Shelter 1 200 O2 THERMO 48iQ-LS 1192734482 0 25 3/12/2020 Shelter 1 200 0 0 0 0 0 0 1/0/1900 0 1 Type Code310 (Excess Emissions) SUMMARY REPORT Type Code Channel Total Hours of Excess Emissions Excess Emissions - % of Total Operating Hours RC 701 Hours - start up/Shutdown RC 702 Hours- Control Equipment Problems RC 703 Hours - Process Problems RC 704, 706, 707 Hours -Other Known Causes RC 705 Hours - Unknown Causes Emission Limitation Emission Limitation Units Emission Limitation Averaging Period 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 2.25 ppmvd at 15%O23 hour 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3 ppmvd at 15%O23 hour 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 2.25 ppmvd at 15%O23 hour 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3 ppmvd at 15%O23 hour 1 310 0 0 0 0 0 0 0 0 0 1 Type Code 300 (CMS Performance Summary) Type Code Channel Point Source Operating Hours Downtime - % of Total Operating Hours Total CMS Downtime RC 721 Hours - Monitor Malfunction RC 722 Hours - Non-monitor Malfunction RC 723 Hours - QA Calibrations RC 724 Hours - Other Known Causes RC 725 Hours - Unknown Causes 1 TRUE 300 NOx 1803.7 0.22% 4 4 0 0 0 0 1 TRUE 300 CO 1803.7 0.22% 4 4 0 0 0 0 1 TRUE 300 O2 1803.7 0.22% 4 4 0 0 0 0 1 TRUE 300 NOx 2142.9 0.28% 6 0 0 0 6 0 1 TRUE 300 CO 2142.9 0.84% 18 10 0 4 4 0 1 TRUE 300 O2 2142.9 0.70% 15 10 0 0 5 0 1 300 0 0 0 0 0 0 1 Type Code 250 (Performance Specification RATA Results) Type Code Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units of Measurement CEM Value Reference Method Value Relative accuracy Pass/ Fail 1 364 Days 250 NOx 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.7 1.9 12.40% Pass 1 364 Days 250 NOx 01/30/24 01/31/23 11.96712329 lb/mmBtu 0.006 0.007 |d?| = 0.001 Pass 1 364 Days 250 NOx 01/30/24 01/31/23 11.96712329 lb/hr 13 14.6 14.10% Pass 1 364 Days 250 O2 01/30/24 01/31/23 11.96712329 Percent 11.6 11.6 0.70% Pass 1 364 Days 250 CO 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.16 1.25 4.70% Pass 1 364 Days 250 CO 01/30/24 01/31/23 11.96712329 lb/hr 5.4 5.9 11.30% Pass 1 364 Days 250 NOx 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.73 1.76 1.90% Pass 1 364 Days 250 NOx 01/31/24 02/01/23 11.96712329 lb/mmBtu 0.006 0.007 |d?| = 0.000 Pass 1 364 Days 250 NOx 01/31/24 02/01/23 11.96712329 lb/hr 13.1 13.2 2.50% Pass 1 364 Days 250 O2 01/31/24 02/01/23 11.96712329 Percent 11.3 11.3 0.90% Pass 1 364 Days 250 CO 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.63 1.46 |d|+CC = 0.17 Pass 1 364 Days 250 CO 01/31/24 02/01/23 11.96712329 lb/hr 7.5 6.7 13.00% Pass 1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0 Point Source Point Source Point Source HRSG1A HRSG1B 0 HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B 0 HRSG1B HRSG1B HRSG1B 0 HRSG1A HRSG1A HRSG1A PacifiCorp Currant Creek Power Plant 0 HRSG1A HRSG1A HRSG1A HRSG1B HRSG1B HRSG1B 0 HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1B 0 Pacificorp Currant Creek EER 4Q2024 1 Type Code 260 (CGA Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 260 CO 12/11/24 Low DT0038172 09/15/25 P1 ppm 2.5 2.52 0.79% PASS Low 1 Valid Cal. Gas 260 CO 12/11/24 Mid DT0043945 09/20/25 P1 ppm 5.6 5.56 0.12% PASS Low 1 Valid Cal. Gas 260 CO 12/11/24 Low DT0017730 02/19/27 P1 ppm 335.3 333 0.68% PASS High 1 Valid Cal. Gas 260 CO 12/11/24 Mid CC244769 09/19/26 P1 ppm 664.2 666 0.27% PASS High 1 Valid Cal. Gas 260 CO 12/04/24 Low DT0042508 09/15/25 P1 ppm 2.3 2.53 9.09% PASS Low 1 Valid Cal. Gas 260 CO 12/04/24 Mid DT0014586 04/04/25 P1 ppm 5.2 5.44 3.80% PASS Low 1 Valid Cal. Gas 260 CO 12/04/24 Low CC115381 02/19/28 P1 ppm 329.2 327.7 0.47% PASS High 1 Valid Cal. Gas 260 CO 12/04/24 Mid DT0025811 05/09/30 P1 ppm 653.3 668 2.20% PASS High 1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 270 (Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 270 NOx 07/07/21 Low DT0017038 06/15/23 P1 ppm 2.3 2.5 9.09% PASS Low 1 Valid Cal. Gas 270 NOx 12/11/24 Low DT0038172 09/15/25 P1 ppm 1.9 2.57 27.40% PASS Low 1 Valid Cal. Gas 270 NOx 07/07/21 Mid DT0035451 01/30/23 P1 ppm 5.5 5.5 0.92% PASS Low 1 Valid Cal. Gas 270 NOx 12/11/24 Mid DT0043945 09/20/25 P1 ppm 5.3 5.56 4% PASS Low 1 Valid Cal. Gas 270 NOx 12/11/24 High DT0011806 04/16/25 P1 ppm 8.9 9.07 2% PASS Low 1 Valid Cal. Gas 270 NOx 07/07/21 High CC424060 05/25/29 P1 ppm 9.3 9.2 1% PASS Low 1 Valid Cal. Gas 270 NOx 07/07/21 Low CC273025 01/03/22 P1 ppm 49.2 51.1 3.78% PASS High 1 Valid Cal. Gas 270 NOx 12/11/24 Low EB0020343 06/27/26 P1 ppm 50.2 52.8 5.00% PASS High 1 Valid Cal. Gas 270 NOx 12/11/24 Mid CC189567 11/24/25 P1 ppm 106 109 2.80% PASS High 1 Valid Cal. Gas 270 NOx 07/07/21 Mid EB0100508 06/27/26 P1 ppm 111.5 112 0.45% PASS High 1 Valid Cal. Gas 270 NOx 12/11/24 High ALM044650 12/12/31 P1 ppm 179.4 179.3 0.10% PASS High 1 Valid Cal. Gas 270 NOx 07/07/21 High CC131527 05/25/29 P1 ppm 180.4 180 0.22% PASS High 1 Valid Cal. Gas 270 O2 12/11/24 Low DT0017730 02/19/27 P1 Percent 6.2 6.33 2.10% PASS 0 1 Valid Cal. Gas 270 O2 12/11/24 Mid CC244769 09/19/26 P1 Percent 13.8 13.88 0.60% PASS 0 1 Valid Cal. Gas 270 O2 12/11/24 High CC332366 07/18/32 P1 Percent 22.5 22.53 0.10% PASS 0 1 Valid Cal. Gas 270 NOx 12/04/24 Low DT0042508 09/15/25 P1 ppm 2 2.56 22% PASS Low 1 Valid Cal. Gas 270 NOx 12/04/24 Mid DT0014586 04/04/25 P1 ppm 5.1 5.53 8% PASS Low 1 Valid Cal. Gas 270 NOx 12/04/24 High DT0019072 04/16/25 P1 ppm 8.8 8.92 1% PASS Low 1 Valid Cal. Gas 270 NOx 12/04/24 Low EB0074935 07/13/26 P1 ppm 48.1 50.2 4.10% PASS High 1 Valid Cal. Gas 270 NOx 09/04/24 Low EB0074935 07/13/26 P1 ppm 48.1 50.2 4.20% PASS High 1 Valid Cal. Gas 270 NOx 12/04/24 Mid CC188124 06/08/29 P1 ppm 107.9 110.3 2.20% PASS High 1 Valid Cal. Gas 270 NOx 09/04/24 Mid CC188124 06/08/29 P1 ppm 107.9 110.3 2.20% PASS High 1 Valid Cal. Gas 270 NOx 09/04/24 High EB0141282 02/15/32 P1 ppm 176.8 178.8 1.10% PASS High 1 Valid Cal. Gas 270 NOx 12/04/24 High ALM033602 11/04/30 P1 ppm 179 181.8 1.50% PASS High 1 Valid Cal. Gas 270 O2 09/04/24 Low DT0010340 10/19/28 P1 Percent 6.2 6.3 1.60% PASS 0 1 Valid Cal. Gas 270 O2 12/04/24 Low CC115381 02/19/28 P1 Percent 6.2 6.32 1.90% PASS 0 1 Valid Cal. Gas 270 O2 09/04/24 Mid DT0025811 05/09/30 P1 Percent 13.5 13.5 0.00% PASS 0 1 Valid Cal. Gas 270 O2 12/04/24 Mid DT0025811 05/09/30 P1 Percent 13.5 13.53 0.20% PASS 0 1 Valid Cal. Gas 270 O2 09/04/24 High CC219564 04/04/32 P1 Percent 22.6 22.5 0.40% PASS 0 1 Valid Cal. Gas 270 O2 12/04/24 High EB0098581 10/31/30 P1 Percent 22.5 22.59 0.30% PASS 0 1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code Channel Start Date Start Time End Date End Time Hours 1 0 210 0 1/0/00 0:00 1/0/00 0:00 1 1 None Reported 1 0 TC 220 Hours 51.00 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00 1 51.00 TC 300 Hours 0.00 TRUE None Reported None Reported None Reported None Reported None Reported None Reported HRSG1A HRSG1A HRSG1A HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B HRSG1B 0 Point Source Point Source Point Source Yes HRSG1A HRSG1A Type Code 550 (Changes in Operation in Control Equipment When CEM Data Not Available) Type Code 500 (Boiler Operating Days w/o 18 Hours of Data) Type Code 450 (Data Excluded) Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code 220 (Monitor Outage During Point Source Operation) Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) Type Code 240 (CEM Modifications) Type Code 530 (Excess Emissions During Emergency Conditions) HRSG1A HRSG1A HRSG1B HRSG1B HRSG1B HRSG1B 0 HRSG1B HRSG1B HRSG1B HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1A HRSG1B HRSG1B HRSG1A HRSG1A 0 Pacificorp Currant Creek EER 4Q2024 Relative Accuracy Overview Point Source Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units Measured CEM Value Reference Method Value Relative Accuracy Pass/ Fail 2024 HRSG1A NOx 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.7 1.90 12.40% Pass HRSG1A NOx 01/30/24 01/31/23 11.96712329 lb/mmBtu 0.006 0.01 |d?| = 0.001 Pass HRSG1A NOx 01/30/24 01/31/23 11.96712329 lb/hr 13 14.60 14.10% Pass HRSG1A O2 01/30/24 01/31/23 11.96712329 Percent 11.6 11.60 0.70% Pass HRSG1A CO 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.16 1.25 4.70% Pass HRSG1A CO 01/30/24 01/31/23 11.96712329 lb/hr 5.4 5.90 11.30% Pass HRSG1B NOx 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.73 1.76 1.90% Pass HRSG1B NOx 01/31/24 02/01/23 11.96712329 lb/mmBtu 0.006 0.01 |d?| = 0.000 Pass HRSG1B NOx 01/31/24 02/01/23 11.96712329 lb/hr 13.1 13.20 2.50% Pass HRSG1B O2 01/31/24 02/01/23 11.96712329 Percent 11.3 11.30 0.90% Pass HRSG1B CO 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.63 1.46 |d|+CC = 0.17 Pass HRSG1B CO 01/31/24 02/01/23 11.96712329 lb/hr 7.5 6.70 13.00% Pass * NSPS CGA Fourth 2024 Audit Gas Ranges Audit Gas Ranges AP1 Low AP2 Low AP1 High AP2 High HRSG1A CO 12/11/24 10 2.52 2 to 3 HRSG1A CO 12/11/24 10 5.56 5 to 6 HRSG1A CO 12/11/24 1200 333 240 to 360 HRSG1A CO 12/11/24 1200 666 600 to 720 HRSG1B CO 12/4/24 10 2.53 2 to 3 HRSG1B CO 12/4/24 10 5.44 5 to 6 HRSG1B CO 12/4/24 1200 327.7 240 to 360 HRSG1B CO 12/4/24 1200 668 600 to 720 * Acid Rain Audit Linearity Fourth 2024 Low Span Gas Ranges High Span Gas Ranges Low Mid High Low Mid High HRSG1A NOx 7/7/21 10 2.5 2 to 3 HRSG1A NOx 12/11/24 10 2.57 2 to 3 HRSG1A NOx 7/7/21 10 5.5 5 to 6 HRSG1A NOx 12/11/24 10 5.56 5 to 6 HRSG1A NOx 12/11/24 10 9.07 8 to 10 HRSG1A NOx 7/7/21 10 9.2 8 to 10 HRSG1A NOx 7/7/21 200 51.1 40 to 60 HRSG1A NOx 12/11/24 200 52.8 40 to 60 HRSG1A NOx 12/11/24 200 109 100 to 120 HRSG1A NOx 7/7/21 200 112 100 to 120 HRSG1A NOx 12/11/24 200 179.3 160 to 200 HRSG1A NOx 7/7/21 200 180 160 to 200 HRSG1A O2 12/11/24 25 6.33 5 to 7.5 HRSG1A O2 12/11/24 25 13.88 12.5 to 15 HRSG1A O2 12/11/24 25 22.53 20 to 25 HRSG1B NOx 12/4/24 10 2.56 2 to 3 HRSG1B NOx 12/4/24 10 5.53 5 to 6 HRSG1B NOx 12/4/24 10 8.92 8 to 10 HRSG1B NOx 12/4/24 200 50.2 40 to 60 HRSG1B NOx 9/4/24 200 50.2 40 to 60 HRSG1B NOx 12/4/24 200 110.3 100 to 120 HRSG1B NOx 9/4/24 200 110.3 100 to 120 HRSG1B NOx 9/4/24 200 178.8 160 to 200 HRSG1B NOx 12/4/24 200 181.8 160 to 200 HRSG1B O2 9/4/24 25 6.3 5 to 7.5 HRSG1B O2 12/4/24 25 6.32 5 to 7.5 HRSG1B O2 9/4/24 25 13.5 12.5 to 15 HRSG1B O2 12/4/24 25 13.53 12.5 to 15 HRSG1B O2 9/4/24 25 22.5 20 to 25 HRSG1B O2 12/4/24 25 22.59 20 to 25 Audit Gas Used Point Source Channel Audit Date Low Span Point Source Channel Audit Date Low Span Audit Gas Used High Span Audit Gas Used High SpanAudit Gas Used Pacificorp Currant Creek EER 4Q2024 Monitoring Information TC 210, 230, & 240 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 240 (CEM Modifications) - 100 (All) * Count of Channel Column Labels Row Labels (blank) Grand Total (blank) (blank) Grand Total Pacificorp Currant Creek EER 4Q2024 Type Code 220 (Monitor Outage During Point Source Operation) - 600 (All) * Sum of Hours Column Labels Row Labels 724 721 723 Grand Total HRSG1B CO Monitoring system placed in maintenance mode. Changed out low pressure cylinder, recalibrated and returned to service.1 1 Monitor froze up and had to be re-booted 10 10 Analyzer failed calibration. Analyzer placed in maintenance mode for repairs, Unit passed calibration and placed back into service.4 4 Monitoring system placed in maintenance mode while checking system in preparation for quarterly linearity testing.3 3 NOx Monitoring system placed in maintenance mode. Changed out low pressure cylinder, recalibrated and returned to service.1 1 Monitoring system placed in maintenance mode while components were being repaired on another monitor. System returned to normal and calibration error test conducted and passed. 2 2 Monitoring system placed in maintenance mode while checking system in preparation for quarterly linearity testing.3 3 O2 Monitor froze up and had to be re-booted 10 10 Monitoring system placed in maintenance mode while components were being repaired on another monitor. System returned to normal and calibration error test conducted and passed. 2 2 Monitoring system placed in maintenance mode while checking system in preparation for quarterly linearity testing.3 3 HRSG1A CO Monitor placed into maintenance mode, routine maintenance performed, recalibrated 4 4 NOx Monitor placed into maintenance mode, routine maintenance performed, recalibrated 4 4 O2 Monitor placed into maintenance mode, routine maintenance performed, recalibrated 4 4 Grand Total 15 32 4 51 Pacificorp Currant Creek EER 4Q2024 NOx * NOx Type Code 420 (NOx) - 6000 (All) NOx * NOx Count of Magnitude of Emissions Column Labels NOx Row Labels Grand Total NOx Grand Total CO * CO Type Code 440 (CO) - 6000 (All) CO * CO Count of Magnitude of Emissions Column Labels CO Row Labels Grand Total CO Grand Total O2 * O2 Type Code 470 (TRS as O2) - 6000 (All) O2 * O2 Count of Magnitude of Emissions Column Labels O2 Row Labels Grand Total O2 Grand Total Pacificorp Currant Creek EER 4Q2024 Type Code 500 Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of Data) After February 28, 2005 (90% Operating Hours For each 30 BOD) - 500 (All) * Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 510 (F-factor, Equations & Conversion Factors) - 500 (All) Count of F-factor Column Labels Row Labels Grand Total Grand Total * Type Code 520 (Minimum Data Not Obtained <22/30 BODs) - 500 (All) Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 530 (Excess Emissions During Emergency Conditions) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * Type Code 540 (Fuel Pre-treatment Credit SO2) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * TypeCode 550 (Changes in Operation in Control Equipment When CEM Data Not Available) - 500 (All) Column Labels Row Labels Grand Total Grand Total