7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 7/17/2023
Order Number: 2361378
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN 38761
1400 N MAIN ST
State ID 1000958
SPRINGVILLE, UT 84663
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name :7-ELEVEN 38761 Name :TANKNOLOGY INC.
Address :1400 N MAIN ST State ID 1000958
SPRINGVILLE, UT 84663
Address :11000 N. MoPac Expressway Suite 500
Austin, TX 78759
Phone :385-327-9236 Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?NONE
Total # of Nozzles :12
Products per Nozzle :3
Tanks Manifolded ?No
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
1 Regular
RUL
19782
12620
7162
09:49
2.00
2.00
2.00
1.99
1.99
1.98
1.86
Pass
2 Premium
PUL
7901
2902
4999
09:57
2.00
1.99
1.98
1.97
1.96
1.95
1.81
Pass
Total
27683
15522
12161
All
Comments:
Tester :David Mathie Test Date :7/17/2023
Signature :Work Order :2361378
WO: 2361378
PVVC tested ==>CENTER RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.26 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.65 Fail
PVVC tested ==>CENTER RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 8 0.0170 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.58 Pass
Neg Leak Rate (CFH)0.21 25 0.0530 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.08 Pass
PVVC tested ==>NORTH PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.20 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.48 Fail
PVVC tested ==>NORTH PUL Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 5 0.0106 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.53 Pass
Neg Leak Rate (CFH)0.21
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.02 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0276
Total -ve LR: 0.0530
Test Date 7/17/2023
Technician Name David Mathie
WO #2361378
Facility Name / Loc #7-ELEVEN 38761 38761
Street 1400 N MAIN ST State ID 1000958
City, St, Zip SPRINGVILLE, UT 84663
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2361378
Site ID / Name:38761 / 7-ELEVEN 38761
Address:1400 N MAIN ST State ID 1000958
City:SPRINGVILLE State:UT Zip:84663